                                                                                                       TX7320 Addressable Sounder 

 

 

        Installation & Operation Manual  

                                                                                                                               4050100271-Rev1.0-1215                                                                       

 

 

    TANDA UK  

                                                                                                                                           

Specifications are subject to change without prior notice 

      

 

1 Introduction  

 

1.1 Overview  

The TX7320 Addressable Sounder is alarm warning device used to notify persons in the vicinity of the 
occurrence fire emergency in order the person to take appropriate measures. The unit adopt multi-
application device starting from  the types, parameters and wiring layout in single unit. Parameters 
can be configured according to the requirement which include alarm tone from 17 different tones, 
single address or dual address mode and also setting of power mode to low current consumption in 
a simple programing.  

The  unit  manufactured  base  on  the  requirement  of  EN  54  part  3,  European  Standard.  The  unit  is 
aesthetically pleasing with unobtrusive design that will complement modern building designs and its 
plug-in type assembles make installation and maintenance more convenient to the installer. The unit 
is  compatible  to  the  TX7004  Analogue  Intelligent  Fire  Alarm  Control  Panel,  produced  by  single 
manufacture T&A, to avoid addressable communication compatibility problem.  

1.2 Feature and Benefits  

 

EN54-3 Compliance 

 

Built-in MCU processor and digital addressing  

 

17 tones Programmable sound output  

 

Programmable Evacuate or Pre-alarm/Evacuate signal  

 

Low and normal consumption mode   

 

One or Two addresses mode 

 

Onsite Adjustable Parameters 

 

Loop or external power input  

 

Aesthetically pleasing design 

 

Universal mounting with fix base for simple installation 

1.3 Technical Specification  

 

Listed   

 

 

  

LPCB Pending 

 

Compliance     

 

 

EN54-3 

 

Input Voltage   

 

 

Loop Power: 24VDC [18V to 27.5V] 
External PSU: 24VDC [20V to 27.5V]   

 

  

 

Typical Current  

 

 

Loop: Standby 0.6mA, Alarm: 1.4mA 

[Loop and External PSU] 

 

External PSU: Standby 0.6mA, Alarm: 10mA 

 

Saving Current  

 

 

Standby 1.2mA, Alarm: 4mA 

[Loop powered] 

 

 

 

 

 

 

 

 

 

 

 

Protocol/Addressing    

 

T&A, Value range from 1 to 254 

 

Address Sequence 

 

 

Single Address: Evacuate tone  
Dual Address: 1

st

 Alert Tone / 2

nd

 Evacuate tone 

   

 

Material / Colour  

 

 

ABS / RED Glossy finishing  

 

Dimension / Height 

 

 

Diameter 110 mm / 39.6 (with Base)  

 

Weight  

 

 

 

180g (with Base), 114g (without Base) 

 

Class   

 

 

 

Type A, Indoors 

 

Operating Temperature 

 

-10°C to +50°C 

 

Ingress Protection Rating 

 

IP21 

 

Humidity 

 

  

 

0 to 95% Relative Humidity, Non condensing 

 
 
 
 
 

Содержание TX7320

Страница 1: ...TX7320 Addressable Sounder Installation and Operation Manual TANDA UK Technology Copyright 2015 All right reserved...

Страница 2: ...nstalling the Sounder to ensure proper and safe operation of the system European Union directive 2012 19 EU WEEE directive Products marked with this symbol cannot be disposed of as unsorted municipal...

Страница 3: ...pecification 4 2 Installation 5 2 1 Installation Preparation 5 2 2 Installation and Wiring 5 3 Sounder Configuration 6 3 1 Preparation 6 3 2 Addressing 6 3 3 Single and Dual Address Mode 7 3 4 Typical...

Страница 4: ...ntelligent Fire Alarm Control Panel produced by single manufacture T A to avoid addressable communication compatibility problem 1 2 Feature and Benefits EN54 3 Compliance Built in MCU processor and di...

Страница 5: ...he correct position Do not over tighten the screws otherwise the base will twist Use M4 standard screws 2 Connect the wire in terminal as shown in Figure 2 3 Verify the device number or other device p...

Страница 6: ...ts Program a unique address number for each device according to the project layout before placing from the Terminal Base Warning Disconnect the loop connection whilst connecting to the handheld progra...

Страница 7: ...will produce simultaneously audible signal according to the pre defined tone Table 1 Tone 14 is the default tone and will stop if the panel is reset 1 Attach the programming cable to 1 and 6 Terminals...

Страница 8: ...11 Note If display Success means the entered mode is confirmed If display Fail means failure to program the mode Warning Under saving mode loop powered up to 20 sounder maximum per loop is the recomme...

Страница 9: ...3 3 5s on 0 5s off 7 07 106 6 101 4 2850Hz 0 5s on 0 5s off 3 1 5s off 8 08 106 1 102 3 2850Hz 0 4s on 0 3s off 9 09 99 7 96 6 550Hz 0 7s 1000Hz 0 33s 10 10 105 7 100 8 1500Hz 2700Hz 3Hz 11 11 102 3 9...

Страница 10: ...f display Fail means failure to program the tone Figure16 Tone 14 Tone 16 and Tone 17 are recognized by LPCB 3 Press Exit key to go back Main Menu Press Power to switch off the programmer 3 7 Read Con...

Страница 11: ...running 6 Perform the maintenance on semi annually or depending on the site conditions 5 Troubleshooting Guide What you notice What it means What to do Address not enrolling The wiring is loose The a...

Страница 12: ...27 5V Min 18V 15 87 3 85 1 89 3 98 0 76 7 76 1 76 1 77 3 45 87 3 83 9 86 7 84 4 75 4 76 8 81 0 81 2 75 84 2 81 1 94 3 90 9 81 9 83 7 81 4 82 8 105 84 1 82 4 90 9 87 7 79 5 81 2 79 4 80 2 135 89 7 87 6...

Отзывы: