                                                                                                       TX7300 Addressable Sounder Strobe 

 

 

        Installation & Operation Manual  

                                                                                                                               4050100270-Rev1.2-0916                                                                      

 

 

    TANDA UK  

                                                                                                                                           

Specifications are subject to change without prior notice 

     

1 Introduction  

 

1.1 Overview  

The TX7300 Addressable Sounder Strobe is alarm warning device used to notify persons in the vicinity 
of the occurrence fire emergency in order the person to take appropriate measures. The unit adopt 
multi-application  device  starting  from  the  types,  parameters  and  wiring  layout  in  single  unit.  The 
TX7300 can change into different alarm warning types such as sounder-strobe type, sounder type or 
strobe  type  using  programming  tool.  In  addition,  parameters  can  be  configured  according  to  the 
requirement which include alarm tone from 17 different tones, single address or dual address mode 
and also setting of power mode to low current consumption in a simple programming.  

The  unit  manufactured  base  on  the  requirement  of  EN  54  part  3,  European  Standard.  The  unit  is 
aesthetically pleasing with unobtrusive design that will complement modern building designs and its 
plug-in type assembles make installation and maintenance more convenient to the installer. The unit 
is  compatible  to  the  TX7004  Analogue  Intelligent  Fire  Alarm  Control  Panel,  produced  by  single 
manufacture T&A, to avoid addressable communication compatibility problem.  

1.2 Feature and Benefits  

 

EN54-3 Compliance 

 

Built-in MCU processor and digital addressing  

 

17 tones Programmable sound output  

 

Programmable types such as Sounder-Strobe, Sounder or Strobe alone 

 

Programmable Evacuate or Pre-alarm/Evacuate signal  

 

Low and normal consumption mode   

 

One or Two addresses mode 

 

10 Highlights LED status cluster   

 

Onsite Adjustable Parameters 

 

Loop or external power input  

 

Aesthetically pleasing design 

 

Universal mounting with fix base for simple installation 

 

1.3 Technical Specification  

 

Listed   

 

 

  

LPCB Certification 

 

Compliance     

 

 

EN 54-3:2001 + A1:2002 + A2:2006 

 

Input Voltage   

 

 

Loop Power: 24VDC [18V to 27.5V] 
External PSU: 24 VDC [20V to 27.5V]   

  

 

Typical Current  

 

 

Loop: Standby 0.6mA, Alarm: 1.5mA 

[Loop and External PSU] 

 

External PSU: Standby 0.6mA, Alarm: 15mA 

 

Saving Current  

 

 

Standby 1.2mA, Alarm: 9mA 

[Loop powered] 

 

 

 

 

 

 

 

 

 

 

 

Protocol/Addressing    

 

T&A, Value range from 1 to 254 

 

Address Sequence 

 

 

Single Address: Evacuate tone  
Dual Address: 1

st

 Alert Tone / 2

nd

 Evacuate tone 

 

Strobe Light  

   

 

 

10 Highlights LED  

 

Material / Colour  

 

 

ABS / RED Glossy finishing  

 

Dimension / Height 

 

 

Diameter 110 mm / 39.6 (with Base)  

 

Weight  

 

 

 

176g (with Base), 110g (Without Base) 

 

Class   

 

 

 

Type A, Indoors 

 

Operating Temperature 

 

-10°C to +50°C 

 

Ingress Protection Rating 

 

IP21 

 

Humidity 

 

  

 

0 to 95% Relative Humidity, Non condensing 

Содержание TX7300

Страница 1: ...TX7300 Addressable Sounder Strobe Installation and Operation Manual TANDA UK Technology Copyright 2015 All right reserved ...

Страница 2: ... symbol cannot be disposed of as unsorted municipal waste in the European Union For proper recycling return this product to your local supplier upon the purchase of equivalent new equipment or dispose of it at designated collection points For more information please visit the website at www recyclethis info EN54 Part 3 Compliance TX7300 Addressable Sounder Strobe complies with the requirements of ...

Страница 3: ...cation 4 2 Installation 5 2 1 Installation Preparation 5 2 2 Installation and Wiring 5 3 Sounder Strobe Configuration 6 3 1 Preparation 6 3 2 Addressing 6 3 3 Single and Dual Address Mode 7 3 4 Typical and Saving Mode 8 3 5 Sounder Strobe Type 8 3 6 Tones Selection 9 3 7 Read Configuration 10 4 General Maintenance 11 5 Troubleshooting Guide 11 Appendix 1 11 Operational Performance Data for LPCB Ap...

Страница 4: ...e Intelligent Fire Alarm Control Panel produced by single manufacture T A to avoid addressable communication compatibility problem 1 2 Feature and Benefits EN54 3 Compliance Built in MCU processor and digital addressing 17 tones Programmable sound output Programmable types such as Sounder Strobe Sounder or Strobe alone Programmable Evacuate or Pre alarm Evacuate signal Low and normal consumption m...

Страница 5: ...the correct position Do not over tighten the screws otherwise the base will twist Use M4 standard screws 2 Connect the wire in terminal as shown in Figure 2 3 Verify the device number or other device parameters if desired using handheld programmer then stick on the label before attaching sounder strobe The sticker labels are available on the control panel 3 Attach the sounder to the base point the...

Страница 6: ...ental requirements Program a unique address number for each device according to the project layout before placing from the Terminal Base Warning Disconnect the loop connection whilst connecting to the handheld programmer 3 2 Addressing 1 Connect the programming cable to Z1 and Z2 terminals Figure 4 Press Power to switch on the unit 2 Switch on the programmer then press button Write or number 2 to ...

Страница 7: ...e 2nd address sounder Evacuate Stage will produce visible signal of 1 4 flashes per second at 1 20 Hz frequency with simultaneously audible signal according to the pre defined tone Table 1 Tone 14 is the default tone and will stop if the panel is reset 1 Attach the programming cable to 1 and 6 Terminals of sounder Press Power to switch on the unit 2 Switch on the programmer then press button 3 to ...

Страница 8: ... the desire mode Figure 11 Note If display Success means the entered mode is confirmed If display Fail means failure to program the mode Warning Under saving mode loop powered up to 20 sounder strobe maximum per loop is the recommended 4 Press Exit key to go back Main Menu Press Power key to switch off the programmer 3 5 Sounder Strobe Type 1 Attach the programming cable to 1 and 6 Terminals of so...

Страница 9: ... 102 7 98 8 500Hz 1200Hz 3 3 5s on 0 5s off 7 07 106 6 101 4 2850Hz 0 5s on 0 5s off 3 1 5s off 8 08 106 1 102 3 2850Hz 0 4s on 0 3s off 9 09 99 7 96 6 550Hz 0 7s 1000Hz 0 33s 10 10 105 7 100 8 1500Hz 2700Hz 3Hz 11 11 102 3 97 0 2400Hz 12 12 102 4 97 0 500Hz 1200Hz 0 33Hz 13 13 104 4 100 6 2400Hz 2900Hz 9Hz 14 14 105 7 102 0 2400Hz 2900Hz 3Hz Default 15 15 102 0 99 2 800Hz 970Hz 3Hz 16 16 102 1 98...

Страница 10: ... 16 If display Fail means failure to program the tone Figure16 Tone 14 Tone 16 and Tone 17 are recognized by LPCB 3 Press Exit key to go back Main Menu Press Power to switch off the programmer 3 7 Read Configuration 1 Attach the programming cable to 1 and 6 terminals of sounder strobe Press Power to switch on the unit 2 Switch on the programmer then press button Read or 1 to enter to Read mode Fig...

Страница 11: ...d running 6 Perform the maintenance on semi annually or depending on the site conditions 5 Troubleshooting Guide What you notice What it means What to do Address not enrolling The wiring is loose The address is duplicate Conduct maintenance Re Commission the device Unable to commission The damage the electronic circuit Replace the device Appendix 1 Operational Performance Data for LPCB Approved To...

Страница 12: ...91 2 86 8 95 6 91 7 86 8 84 0 88 0 85 3 105 91 7 87 3 96 7 92 4 83 9 81 6 85 0 82 1 135 90 0 86 0 90 5 86 2 83 4 79 9 87 9 85 5 165 86 7 82 9 90 9 86 6 80 4 77 6 83 4 80 5 Table 3 3 Tone 17 Volume dB A Typical Mode dB A Saving Mode dB A Angle Horizontal Plane Vertical Plane Horizontal Plane Vertical Plane Max27 5V Min 20V Max27 5V Min 20V Max27 5V Min 18V Max27 5V Min 18V 15 87 3 85 1 89 3 98 0 76...

Страница 13: ...odes and laws Take specific maintenance measures on the basis of different environments This alarm warning device contains electronic parts Even though it is made to last for a long period of time any of these parts could fail at any time Therefore test your alarm warning device at least every half year according to national codes or laws Any fire alarm devices or any other components of the syste...