                                                                                                       TX7300 Addressable Sounder Strobe 

 

 

        Installation & Operation Manual  

                                                                                                                               4050100270-Rev1.2-0916                                                                      

 

 

    TANDA UK  

                                                                                                                                           

Specifications are subject to change without prior notice 

11 

     

4 General Maintenance   

 

1.

 

Inform the suitable personnel before conducting the maintenance. 

2.

 

Disable the alarm warning device on the control panel to prevent false alarm. 

3.

 

Do  not  attempt  to  repair  the  circuitry  of  the  alarm  warning  device,  it  may  affect  the 
operation to respond to a fire condition and will void the manufacturer’s warranty.  

4.

 

Use a damp cloth to clean the surface.  

5.

 

Notify again proper personnel after conducting the maintenance and make sure to enable 
the alarm warning device and confirm if up and running.  

6.

 

Perform the maintenance on semi-annually or depending on the site conditions.  

5 Troubleshooting Guide    

 

What you notice 

What it means 

What to do 

Address not enrolling 

The wiring is loose 

The address is duplicate 

Conduct maintenance 

Re-Commission the device 

Unable to commission 

The damage the electronic circuit 

Replace the device 

 

Appendix 1  

 

Operational Performance Data for LPCB Approved Tones 

 
1. Tone 14 – Volume dB(A) 

 

Typical Mode dB(A) 

Saving Mode dB(A) 

Angle 

Horizontal Plane 

Vertical Plane 

Horizontal Plane 

Vertical Plane 

Max27.5V 

Min 20V 

Max27.5V 

Min 20V 

Max27.5V 

Min 18V 

Max27.5V 

Min 18V 

15° 

92.1 

87.8 

95.8 

91.2 

84.8 

86.6 

83.9 

84.1 

45° 

93.1 

88.6 

96.7 

91.7 

84.8 

83.6 

89.0 

88.6 

75° 

96.5 

92.7 

101.1 

97.1 

88.1 

89.2 

90.8 

89.2 

105° 

94.5 

90.2 

101.3 

96.1 

86.2 

84.8 

91.2 

90.1 

135° 

91.7 

86.9 

99.4 

94.6 

84.8 

82.2 

84.9 

84.2 

165° 

89.6 

84.9 

97.8 

93.3 

83.5 

84.1 

84.7 

84.0 

Table 2 

 

 

 

Содержание TX7300

Страница 1: ...TX7300 Addressable Sounder Strobe Installation and Operation Manual TANDA UK Technology Copyright 2015 All right reserved ...

Страница 2: ... symbol cannot be disposed of as unsorted municipal waste in the European Union For proper recycling return this product to your local supplier upon the purchase of equivalent new equipment or dispose of it at designated collection points For more information please visit the website at www recyclethis info EN54 Part 3 Compliance TX7300 Addressable Sounder Strobe complies with the requirements of ...

Страница 3: ...cation 4 2 Installation 5 2 1 Installation Preparation 5 2 2 Installation and Wiring 5 3 Sounder Strobe Configuration 6 3 1 Preparation 6 3 2 Addressing 6 3 3 Single and Dual Address Mode 7 3 4 Typical and Saving Mode 8 3 5 Sounder Strobe Type 8 3 6 Tones Selection 9 3 7 Read Configuration 10 4 General Maintenance 11 5 Troubleshooting Guide 11 Appendix 1 11 Operational Performance Data for LPCB Ap...

Страница 4: ...e Intelligent Fire Alarm Control Panel produced by single manufacture T A to avoid addressable communication compatibility problem 1 2 Feature and Benefits EN54 3 Compliance Built in MCU processor and digital addressing 17 tones Programmable sound output Programmable types such as Sounder Strobe Sounder or Strobe alone Programmable Evacuate or Pre alarm Evacuate signal Low and normal consumption m...

Страница 5: ...the correct position Do not over tighten the screws otherwise the base will twist Use M4 standard screws 2 Connect the wire in terminal as shown in Figure 2 3 Verify the device number or other device parameters if desired using handheld programmer then stick on the label before attaching sounder strobe The sticker labels are available on the control panel 3 Attach the sounder to the base point the...

Страница 6: ...ental requirements Program a unique address number for each device according to the project layout before placing from the Terminal Base Warning Disconnect the loop connection whilst connecting to the handheld programmer 3 2 Addressing 1 Connect the programming cable to Z1 and Z2 terminals Figure 4 Press Power to switch on the unit 2 Switch on the programmer then press button Write or number 2 to ...

Страница 7: ...e 2nd address sounder Evacuate Stage will produce visible signal of 1 4 flashes per second at 1 20 Hz frequency with simultaneously audible signal according to the pre defined tone Table 1 Tone 14 is the default tone and will stop if the panel is reset 1 Attach the programming cable to 1 and 6 Terminals of sounder Press Power to switch on the unit 2 Switch on the programmer then press button 3 to ...

Страница 8: ... the desire mode Figure 11 Note If display Success means the entered mode is confirmed If display Fail means failure to program the mode Warning Under saving mode loop powered up to 20 sounder strobe maximum per loop is the recommended 4 Press Exit key to go back Main Menu Press Power key to switch off the programmer 3 5 Sounder Strobe Type 1 Attach the programming cable to 1 and 6 Terminals of so...

Страница 9: ... 102 7 98 8 500Hz 1200Hz 3 3 5s on 0 5s off 7 07 106 6 101 4 2850Hz 0 5s on 0 5s off 3 1 5s off 8 08 106 1 102 3 2850Hz 0 4s on 0 3s off 9 09 99 7 96 6 550Hz 0 7s 1000Hz 0 33s 10 10 105 7 100 8 1500Hz 2700Hz 3Hz 11 11 102 3 97 0 2400Hz 12 12 102 4 97 0 500Hz 1200Hz 0 33Hz 13 13 104 4 100 6 2400Hz 2900Hz 9Hz 14 14 105 7 102 0 2400Hz 2900Hz 3Hz Default 15 15 102 0 99 2 800Hz 970Hz 3Hz 16 16 102 1 98...

Страница 10: ... 16 If display Fail means failure to program the tone Figure16 Tone 14 Tone 16 and Tone 17 are recognized by LPCB 3 Press Exit key to go back Main Menu Press Power to switch off the programmer 3 7 Read Configuration 1 Attach the programming cable to 1 and 6 terminals of sounder strobe Press Power to switch on the unit 2 Switch on the programmer then press button Read or 1 to enter to Read mode Fig...

Страница 11: ...d running 6 Perform the maintenance on semi annually or depending on the site conditions 5 Troubleshooting Guide What you notice What it means What to do Address not enrolling The wiring is loose The address is duplicate Conduct maintenance Re Commission the device Unable to commission The damage the electronic circuit Replace the device Appendix 1 Operational Performance Data for LPCB Approved To...

Страница 12: ...91 2 86 8 95 6 91 7 86 8 84 0 88 0 85 3 105 91 7 87 3 96 7 92 4 83 9 81 6 85 0 82 1 135 90 0 86 0 90 5 86 2 83 4 79 9 87 9 85 5 165 86 7 82 9 90 9 86 6 80 4 77 6 83 4 80 5 Table 3 3 Tone 17 Volume dB A Typical Mode dB A Saving Mode dB A Angle Horizontal Plane Vertical Plane Horizontal Plane Vertical Plane Max27 5V Min 20V Max27 5V Min 20V Max27 5V Min 18V Max27 5V Min 18V 15 87 3 85 1 89 3 98 0 76...

Страница 13: ...odes and laws Take specific maintenance measures on the basis of different environments This alarm warning device contains electronic parts Even though it is made to last for a long period of time any of these parts could fail at any time Therefore test your alarm warning device at least every half year according to national codes or laws Any fire alarm devices or any other components of the syste...

Отзывы: