Tanda TX7110 Скачать руководство пользователя страница 7

                                                                                                       TX7110 Intelligent Heat Detector 

 

 

        Installation & Operation Manual  

                                                                                                                                4050100263-Rev1.4-0916 

 

 

    TANDA UK  

                                                                                                                                           

Specifications are subject to change without prior notice 

 

 

 

Figure 3

 

3 Detector Configuration  

 

3.1 Preparation     

The TX7930 handheld programmer is used to configure heat detectors soft address and parameters. 
This tools are not included, must be purchased separately. The programmer is packed with twin 1.5V 
AA battery and cable, ready for usage once received.  

It  is  mandatory  for  the  commissioning  personnel  to  have  programmer  tool  enable  to  adjust  the 
detector conferring to the site situation and environmental requirements.  

Program a unique address number for each device according to the project layout before placing 
from the Terminal Base.  

Warning

: Disconnect the loop connection whilst connecting to the handheld programmer.  

3.2 Write: Addressing      

1.

 

Connect the programming cable to 1 and 
6  terminals  (Figure  3).  Press 

“Power”

  to 

switch on the unit. 

2.

 

Switch-on  the  programmer,  then  press 
button “

Write”

 or number “

2

” to enter Write

 

Address mode (Figure 4). 

3.

 

Input the desire device address value from 
1 to 254, and then press “

Write” 

to save the 

new address (Figure 5). 

 

Note:

  

If display 

“Success”, 

means the 

entered address is confirmed. If display 

“Fail”,

 means failure to program the 

address (Figure 6). 

 

 

 

 

 

 

 

  

      

 

4.

 

Press 

“Exit”

 key to go back Main Menu. Press 

“Power” 

key

 

to switch-off the programmer.  

3.3 Set: LED On/Off       

1.

 

The LED indicator can be turn-off if desired, the sensing ability of the detector will not disrupt 
even the LED is off. 

2.

 

Attach the programming cable to 1 and 6 Terminals of detector. Press 

“Power”

 to switch-on 

the unit.  

3.

 

Switch-on the programmer, then press button 

“4” 

to enter to Setting mode (Figure 7).  

4.

 

Input  the 

“1”

  then  press 

“Write”

  to  change  the  setting  (Figure  8)  and  LED  will  turn-off.  To 

resume the default setting, press 

“Clear”

 and then press 

“Write”.

  

 

      

Figure 4

 

      

Figure 5

 

      

Figure 6

 

1. Read 
2. Write   

3. R/W Config  

4. Set 

 

 

Address: 001 
Next Address: 002 

Success  

 

Address: 001 

 

Fail  

 

Содержание TX7110

Страница 1: ......

Страница 2: ...TX7110 Intelligent Heat Detector Installation and Operation Manual TANDA UK Technology Copyright 2015 All right reserved...

Страница 3: ...his symbol cannot be disposed of as unsorted municipal waste in the European Union For proper recycling return this product to your local supplier upon the purchase of equivalent new equipment or disp...

Страница 4: ...Introduction 4 1 1 Overview 4 1 2 Feature and Benefits 4 1 3 Technical Specification 4 2 Installation 5 2 1 Installation Preparation 5 2 2 Installation and Wiring 5 3 Detector Configuration 6 3 1 Pre...

Страница 5: ...patterns for a faster and safer response Once it is confirmed the LED indicates the sensor status and parallel sending communication signal to the control panel The TX7110 detector is compatible to th...

Страница 6: ...o a sudden increase in temperature this makes ideal for areas where smoke detector is unsuitable 2 2 Installation and Wiring 1 Mount the T A standard base on standard one 1 gang electrical back box Do...

Страница 7: ...le to 1 and 6 terminals Figure 3 Press Power to switch on the unit 2 Switch on the programmer then press button Write or number 2 to enter Write Address mode Figure 4 3 Input the desire device address...

Страница 8: ...Disable the detector on the control panel to prevent false alarm 3 Do not attempt to adjust or modify the detector it may affect the ability of the detector to respond to a fire condition and will voi...

Страница 9: ...rogram the detector Appendix 1 Limitation of Heat Detectors The heat detector cannot last forever In order to keep the detector working in good condition please maintain the equipment continuously acc...

Отзывы: