                                                                                                       TX7110 Intelligent Heat Detector 

 

 

        Installation & Operation Manual  

                                                                                                                                4050100263-Rev1.4-0916 

 

 

    TANDA UK  

                                                                                                                                           

Specifications are subject to change without prior notice 

1 Introduction  

 

1.1 Overview  

The TX7110 Intelligent Fixed and Rate of Rise Heat Detector is reliable for application in places where 
may  have  high  dust  level  or  smoky  environments,  making  a  normal  smoke  detector  undesirable.   
The unit manufactured base on the sensitivity requirement of EN 54 part 5, European Standard. The 
unit is aesthetically pleasing with unobtrusive design that will complement modern building designs. 
The unit incorporates an intelligent processor that provides inbuilt A/D converter,  and Self-Diagnosis 
and History log. 

In  the  event  of  fire,  the  integral  microprocessor  analyses  the  signal  according  to  factors  such  as 
signal  strength  and  rate  of  increase,  then  confirms  these  patterns  with  the  pre-programmed  fire 
scenarios, heat patterns including rate of rise temperature patterns, for a faster and safer response. 
Once it is confirmed, the LED indicates the sensor status and parallel sending communication signal 
to the control panel. The TX7110 detector is compatible to the TX7004 Analogue Intelligent Fire Alarm 
Control  Panel,  produced  by  single  manufacture  T&A,  to  avoid  addressable  communication 
compatibility problem.  

1.2 Feature and Benefits  

 

EN54-5 Compliance 

 

Using microprocessor technology with memory capacity up to 10 events 

 

Analogue sensor and digital addressing  

 

Provide real time algorithm to the control panel 

 

360 degree visual indicator  

 

Onsite Adjustable Parameter 

 

Ancillary remote indicator output  

 

Aesthetically pleasing design 

1.3 Technical Specification  

 

Listed   

 

 

  

LPCB Certification 

 

Compliance     

 

 

EN 54-5:2000 + A1:2002 

 

Input Voltage   

 

 

24VDC [16V to 28V] 

 

Current Consumption  Standby  

0.6mA, Alarm: 4mA 

 

Protocol/Addressing    

 

T&A, Value range from 1 to 254 

 

Heat Class Type 

 

 

A1R 

 

Indicator   

 

 

 

Single LED / 360 degree Visual  

 

Material / Colour  

 

 

ABS / White Glossy finishing  

 

Dimension / Height    

 

Diameter 99.7 mm / 57 mm 

 

Weight  

 

 

 

127g (with Base), 72g (without Base) 

 

Operating Temperature 

 

-10°C to +50°C 

 

Humidity 

 

  

 

0 to 95% Relative Humidity, Non condensing 

  
 

 

 
 
 
 
 
 
 
 
 
 

 

Содержание TX7110

Страница 1: ......

Страница 2: ...TX7110 Intelligent Heat Detector Installation and Operation Manual TANDA UK Technology Copyright 2015 All right reserved...

Страница 3: ...his symbol cannot be disposed of as unsorted municipal waste in the European Union For proper recycling return this product to your local supplier upon the purchase of equivalent new equipment or disp...

Страница 4: ...Introduction 4 1 1 Overview 4 1 2 Feature and Benefits 4 1 3 Technical Specification 4 2 Installation 5 2 1 Installation Preparation 5 2 2 Installation and Wiring 5 3 Detector Configuration 6 3 1 Pre...

Страница 5: ...patterns for a faster and safer response Once it is confirmed the LED indicates the sensor status and parallel sending communication signal to the control panel The TX7110 detector is compatible to th...

Страница 6: ...o a sudden increase in temperature this makes ideal for areas where smoke detector is unsuitable 2 2 Installation and Wiring 1 Mount the T A standard base on standard one 1 gang electrical back box Do...

Страница 7: ...le to 1 and 6 terminals Figure 3 Press Power to switch on the unit 2 Switch on the programmer then press button Write or number 2 to enter Write Address mode Figure 4 3 Input the desire device address...

Страница 8: ...Disable the detector on the control panel to prevent false alarm 3 Do not attempt to adjust or modify the detector it may affect the ability of the detector to respond to a fire condition and will voi...

Страница 9: ...rogram the detector Appendix 1 Limitation of Heat Detectors The heat detector cannot last forever In order to keep the detector working in good condition please maintain the equipment continuously acc...

Отзывы: