TX7100 Intelligent Optical Smoke Detector
Installation & Operation Manual
4050100265-Rev1.4-0916
TANDA UK
Specifications are subject to change without prior notice
8
4.1 Cleaning
1.
Remove the detector cover by snooping away the four
sides tabs using a flat screw driver and then pulling the
cover from the base. (Figure 11).
2.
Remove the protective screen by pulling it straight out.
(Figure 12).
3.
Carefully vacuum the chamber and screen. If there is
stain, wash with running water and ensure it is completely
dry.
4.
Position
the chamber and screen by aligning three tiny
holes over the sensing component. (Figure 12).
5.
Align the LED tube and tabs and gently pushing the
cover until it locks into place. (Figure 12).
6.
Re-install and test the detector.
5 Troubleshooting Guide
What you notice
What it means
What to do
Address not enrolling
The wiring is lose
The address is duplicate
Conduct maintenance
Re-Commission the detector
Unable to commission
The damage the electronic circuit
Replace the detector
Keep Indicating Fire signal The detector chamber is dirty
Clean the detector
Figure 11
Figure 12: Exploded View