Tanda TX7100 Скачать руководство пользователя страница 6

                                                                                                       TX7100 Intelligent Optical Smoke Detector 

 

 

        Installation & Operation Manual  

                                                                                                                               4050100265-Rev1.4-0916                                                                  

 

 

       TANDA UK 

                                                                                                                                           

Specifications are subject to change without prior notice 

 

 

 

 

Figure 3

 

3 Detector Configuration  

 

3.1 Preparation  

The TX7930 handheld programmer is used to configure smoke detectors soft address and parameter. 
This tools are not included, must be purchased separately.  The programmer is packed with twin 1.5V 
AA battery and cable, ready for usage once received.  

It  is  mandatory  for  the  commissioning  personnel  to  have  programmer  tool  in  order  to  adjust  the 
detector conferring to the site situation and environmental requirements.  

Program a unique address number for each device according to the project layout before placing 
from the Terminal Base.  

Warning: 

Disconnect the loop connection whilst connecting to the handheld programmer. 

 

3.2 Write: Addressing      

1.

 

Connect the programming cable to 1 and 
6  terminals  (Figure  3).  Press 

“Power”

  to 

switch on the unit. 

2.

 

Switch-on  the  programmer,  then  press 
button “

Write”

 or number “

2

” to enter Write

 

Address mode (Figure 4). 

3.

 

Input the desire device address value from 
1 to 254, and then press “

Write” 

to save the 

new address (Figure 5). 

 

Note:

  

If display 

“Success”, 

means the 

entered address is confirmed. If display 

“Fail”,

 means failure to program the 

address (Figure 6). 

 

 

 

 

 

 

 

 

4.

 

Press “

Exit”

 key to go back Main Menu. Press “

Power” 

key

 

to switch-off the programmer.  

3.3 Set: LED On/Off  

1.

 

The LED indicator can be turn-off if desired, the sensing ability of the detector will not disrupt 
even the LED is off. 

2.

 

Attach the programming cable to 1 and 6 Terminals of detector. Press 

“Power”

 to switch-on 

the unit.  

3.

 

Switch-on the programmer, then press button 

“4” 

to enter to Setting

 

mode (Figure 7).  

4.

 

Input  the 

“1”

  then  press 

“Write”

  to  change  the  setting  (Figure  8)  and  LED  will  turn-off.  To 

resume the default setting, press 

“Clear”

 and then press 

“Write”.

  

 

      

Figure 4

 

      

Figure 5

 

      

Figure 6

 

1

. Read 

2. Write   

3. R/W Config  

4. Set 

 

Address: 001 
Next Address: 002 

 

Success  

Address: 001 
 

 

  Fail  

Содержание TX7100

Страница 1: ...TX7100 Intelligent Addressable Optical Smoke Detector Installation and Operation Manual TANDA UK Technology Copyright 2015 All right reserved ...

Страница 2: ... marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union For proper recycling return this product to your local supplier upon the purchase of equivalent new equipment or dispose of it at designated collection points For more information please visit the website at www recyclethis info EN54 Part 7 Compliance TX7100 Intelligent Smoke Detector complies with the...

Страница 3: ...troduction 4 1 1 Overview 4 1 2 Feature and Benefits 4 1 3 Technical Specification 4 2 Installation 5 2 1 Installation Preparation 5 2 2 Installation and Wiring 5 3 Detector Configuration 6 3 1 Preparation 6 3 2 Write Addressing 6 3 3 Set LED On Off 6 3 4 Read Configuration 7 4 General Maintenance 7 4 1 Cleaning 8 5 Troubleshooting Guide 8 Appendix 1 9 Limitation of Smoke Detectors 9 ...

Страница 4: ...e scenarios and smoke patterns for a faster and safer response Once it is confirmed the LED indicates the sensor status and parallel sending communication signal to the control panel The TX7100 detector is compatible to the TX7004 Analogue Intelligent Fire Alarm Control Panel produced by single manufacture T A to avoid addressable communication compatibility problem 1 2 Feature and Benefits EN54 7...

Страница 5: ...take place such kitchens or similar areas where steam and condensation are present Where exhaust fumes are present like car parks Where smoke particles will not be produced by fire Plant Rooms unless full discussions regarding the room contents and status subject to a fire have been made between Client and Manufacturer Boiler and Generator Rooms 2 2 Installation and Wiring 1 Mount the T A standard...

Страница 6: ...ng cable to 1 and 6 terminals Figure 3 Press Power to switch on the unit 2 Switch on the programmer then press button Write or number 2 to enter Write Address mode Figure 4 3 Input the desire device address value from 1 to 254 and then press Write to save the new address Figure 5 Note If display Success means the entered address is confirmed If display Fail means failure to program the address Fig...

Страница 7: ...ol panel to prevent false alarm 3 Do not attempt to adjust or modify the detector it may affect the ability of the detector to respond to a fire condition and will void the manufacturer s warranty 4 Use a damp cloth to clean the detector Do not use cleaning chemicals that may leave residue on the electronic parts and smoke chamber 5 Notify again proper personnel after conducting the maintenance an...

Страница 8: ...ash with running water and ensure it is completely dry 4 Position the chamber and screen by aligning three tiny holes over the sensing component Figure 12 5 Align the LED tube and tabs and gently pushing the cover until it locks into place Figure 12 6 Re install and test the detector 5 Troubleshooting Guide What you notice What it means What to do Address not enrolling The wiring is lose The addre...

Страница 9: ...leaking gas improper storage of flammable materials like diluents and other safety hazards arson or children playing with fire The alarm of a smoke detector used in high velocity environment will be delayed due to dilution of smoke by frequent and fast airflow What s more the smoke detector has to be frequently maintained for it is exposed to more dust contamination The smoke detector cannot last ...

Отзывы: