3 Detector Configuration
3.1 Preparation
The TX7930 handheld programmer is used to configure smoke detectors soft address and parameter.
This tools are not included, must be purchased separately. The programmer is packed with twin 1.5V
AA battery and cable, ready for usage once received.
It is mandatory for the commissioning personnel to have programmer tool in order to adjust the
detector conferring to the site situation and environmental requirements.
Program a unique address number for each device according to the project layout before placing
from the Terminal Base.
Warning:
Disconnect the loop connection whilst connecting to the handheld programmer.
3.2 Write: Addressing
1.
Connect the programming cable to 1 and
6 terminals (Figure 3). Press
“Power”
to
switch on the unit.
2.
Switch-on the programmer, then press
button “
Write”
or number “
2
” to enter Write
Address mode (Figure 4).
3.
Input the desire device address value from
1 to 254, and then press “
Write”
to save the
new address (Figure 5).
Note:
If display
“Success”,
means the
entered address is confirmed. If display
“Fail”,
means failure to program the
address (Figure 6).
4.
Press “
Exit”
key to go back Main Menu. Press “
Power”
key
to switch-off the programmer.
3.3 Set: LED On/Off
1.
The LED indicator can be turn-off if desired, the sensing ability of the detector will not disrupt
even the LED is off.
2.
Attach the programming cable to 1 and 6 Terminals of detector. Press
“Power”
to switch-on
the unit.
3.
Switch-on the programmer, then press button
“4”
to enter to Setting
mode (Figure 7).
4.
Input the
“1”
then press
“Write”
to change the setting (Figure 8) and LED will turn-off. To
resume the default setting, press
“Clear”
and then press
“Write”.
Figure 4
Figure 5
Figure 6
1
. Read
2. Write
T
3. R/W Config
7
4. Set
Address: 001
Next Address: 002
Success
Address: 001
Fail