TX7100 Intelligent Optical Smoke Detector
Installation & Operation Manual
4050100265-Rev1.4-0916
TANDA UK
Specifications are subject to change without prior notice
7
5.
Press
“Exit”
key to go back Main Menu. Press
“Power”
to switch off the programmer.
3.4 Read Configuration
1.
Attach the programming cable to 1 and 6 terminals of detector. Press
“Power”
to switch on
the unit.
2.
Switch-on the programmer, then press button
“Read”
or
“1”
to enter to Read
mode (Figure 9).
The programmer will display the configuration after few seconds. (Figure 10).
3.
Press
“Exit”
key to go back Main Menu. Press
“Power”
to switch off the programmer.
4 General Maintenance
1.
Inform the suitable personnel before conducting the maintenance.
2.
Disable the detector on the control panel to prevent false alarm.
3.
Do not attempt to adjust or modify the detector, it may affect the ability of the detector to
respond to a fire condition and will void the manufacturer’s warranty.
4.
Use a damp cloth to clean the detector. Do not use cleaning chemicals that may leave
residue on the electronic parts and smoke chamber.
5.
Notify again proper personnel after conducting the maintenance and make sure to enable
the detector and confirm if up and running.
6.
Perform the maintenance on semi-annually or quarterly depending on the site conditions.
1. Read
2. Write
T
3. R/W Config
7
4. Set
Address: 123
Sensitivity: 001
Base Value: 007
ID: 123456789012
Parameter Description
0-
LED On (Default)
1-
LED Off
Read Description
Address
: Unique number
assigned
Sensitivity
: For future use
Base Value
: Detector status
value
ID
: Detector serial number
Figure 7
Figure 8
Figure 9
Figure 10
1. Read
2. Write T
3. R/W Config
7
4. Set
Parameter: 1
Success