7.1.13 Menu item "Offset 0.005"
This menu item offers an additional offset of 0.005°C. The
value of 0.005°C is added to the selected SP value. The
SP can be selected with 0.01°C accuracy.
7.1.14 Menu item "Restart"
Restarts system and activates tuning
7.2
PID settings
Default settings
P = 2 .. 25
I = 0 .. 25
D = 0
Following shows influence on stability with different PID
settings
Temperature
:
75°C
Proportional band (Pb) :
25
Integrator
:
16
Differentiator
:
0
Min/max
:
± 0,015
Temperature
:
75°C
Proportional band (Pb) :
50
Integrator
:
25
Differentiator
:
0
Min/max
:
± 0,018°C
Temperature
:
75°C
Proportional band (Pb) :
100
Integrator
:
25
Differentiator
:
0
Min/max
:
± 0,045°C
SP 75°C
0,029
± 0,015
SP 75°C
0,036
± 0,018
SP 75°C
0,089