AIR-IQ shown
with sleeve only
“FLANGED-TO-DUCT” MOUNT TYPE
•
If AIR-IQ unit is manufactured with the 3" flare, the unit is intended to be flanged to the end of duct work or flanged to wall or opening. The
minimum distance from the outside edge of the flare to the trailing edge of the intake louver must be no less than 7".
•
If AIR-IQ unit is manufactured as "Sleeve Only", without the 3" flare, the unit may be flanged to the duct, so that the
minimum distance from the
outside edge of the sleeve to the trailing edge of the intake louver is a minimum of 10".
• AIR-IQ unit must be installed square.
•
A "Flanged to Duct" Mount Type AIR-IQ unit damper's finished,
inside
frame dimensions are equal to the specified duct or opening size.
•
If the AIR-IQ unit is manufactured with the 3" flare, the unit will be secured to the duct or opening using the damper flanges only, leaving the
flare side free. The overall damper frame width and height dimensions are 2" larger than the duct or opening dimensions.
•
If AIR-IQ unit is manufactured as "Sleeve Only", without the 3" flare, both sides of the unit can be secured to the duct work or openings. Both the
damper's and the sleeve's overall, outside frame/flange dimensions are 2" larger than the duct or opening dimensions.
•
Do not assume that the duct or opening is square. Verify that the duct flange or hole is square, flat and even.
• Verify that the unit AIR-IQ unit is square. Operate the damper to verify free movement of the blades and correct sealing.
• Secure the damper to the duct work or opening. Re-verify that the damper is square.
•
If the AIR-IQ unit is manufactured as "Sleeve Only" and ducted on both sides, repeat the procedure for the other flange.
• Caulk all joints.
3"
Non-ducted application
4"
5"
6" 6" 4"
3"
15"
Ducted application
18"
7"
Minimum distance to
trailing edge of intake louver
1"
1"
1"
B
+
6”
B
B
A*
A + 6”
4"
B*
3"
Minimum 4" clearance for EBTRON insertion
style sensor probes and electronic actuator. Does
not include access for wiring after installation of
assembly.
See specific EBTRON and TAMCO series
technical documentation for more information.
Airflow
Inside Sleeve dimensions:
Parallel to blade = A
Perpendicular to blade = B
Outside Damper Frame dimensions:
Parallel to blade = A + 2"
Perpendicular to blade = B + 2"
Outside Flare dimensions:
Parallel to blade = A + 6"
Perpendicular to blade = B + 6"
*NOTES:
A x B:
= Always opening dimensions
Width
= A: Always dimension
parallel to blades
Height
= B: Always dimension
perpendicular to blades
AIR-IQ: TYPICAL, SINGLE-SECTION, HORIZONTAL-BLADE DAMPER
PROBES MOUNTED PARALLEL TO BLADES
FLANGED TO DUCT MOUNT TYPE