AIR
-IQ INS
TALL GUIDE_R3
AIR-IQ shown with
sleeve and flare
If unit is installed with damper inserted in a wall, actuator must
be face-mounted and appropriate face-mounting accessories
will be required.
For additional details, refer to TAMCO Motor Mounting Methods
at http://www.tamcodampers.com/inGdeCD_motorMnt.php
" INSTALLED IN DUCT” MOUNT TYPE:
•
If AIR-IQ unit is manufactured with the 3" flare, the unit is intended to be located at end of duct work.
The minimum distance from the outside
edge of the flare to the trailing edge of the intake louver must be no less than 7".
•
If AIR-IQ unit is manufactured as "Sleeve Only", without the 3" flare, the unit may be inserted within the duct or in the opening, so that the
minimum distance from the outside edge of the sleeve to the trailing edge of the intake louver is a minimum of 10".
•
Installation of AIR-IQ unit is carried out by affixing only the damper inside the duct work. Do not use sleeve or flare to secure unit in duct work.
• AIR-IQ unit must be installed square.
•
An "Installed In Duct" Mount Type AIR-IQ unit damper's finished,
outside
frame dimensions are ½" smaller than the specified duct width and
height dimensions, to allow for clearance to insert the damper frame into the duct work.
• Ensure that the duct is square and large enough to allow the AIR-IQ Unit to be installed square.
• If required, make a hole in the duct work to allow extension of the drive rod.
•
Verify that the AIR-IQ unit is square and then secure the bottom damper frame to the floor of the duct using a 90° mounting angle.
•
Operate the damper manually to confirm proper sealing.
• As each mounting angle is installed, verify operation to ensure the damper is sealing correctly.
• Caulk all joints.
AIR-IQ: TYPICAL, SINGLE-SECTION, HORIZONTAL-BLADE DAMPER
PROBES MOUNTED PARALLEL TO BLADES
INSTALLED IN DUCT MOUNT TYPE
B*
1"
¼"
1"
¼"
clearance
3"
3"
B
B - 2.5”
1"
2"
A*
A - 3.5”
A + 2.5”
B
+
3.5”
Non-ducted application
4"
5"
6" 6" 4"
3"
15"
Ducted application
18"
7"
Minimum distance to
trailing edge of intake louver
4"
Minimum 4" clearance for EBTRON insertion
style sensor probes and electronic actuator. Does
not include access for wiring after installation of
assembly.
See specific EBTRON and TAMCO
series
technical documentation for more information.
Airflow
Inside Sleeve dimensions:
Parallel to blade = A - 3.5"
Perpendicular to blade = B - 2.5"
Outside Damper Frame dimensions:
Parallel to blade = A - 0.5"
Perpendicular to blade = B - 0.5"
Outside Flare dimensions:
Parallel to blade = A + 2.5"
Perpendicular to blade = B + 3.5"
*NOTES:
A x B:
= Always opening dimensions
Width
= A: Always dimension
parallel to blades
Height
= B: Always dimension
perpendicular to blades