background image

AIR

-IQ INS

TALL GUIDE_R3

AIR-IQ shown with 

sleeve and flare

If unit is installed with damper inserted in a wall, actuator must 

be face-mounted and appropriate face-mounting accessories 

will be required.

For additional details, refer to TAMCO Motor Mounting Methods 

at http://www.tamcodampers.com/inGdeCD_motorMnt.php

" INSTALLED IN DUCT” MOUNT TYPE:

• 

If AIR-IQ unit is manufactured with the 3" flare, the unit is intended to be located at end of duct work. 

The minimum distance from the outside 

edge of the flare to the trailing edge of the intake louver must be no less than 7".

 

• 

If AIR-IQ unit is manufactured as "Sleeve Only", without the 3" flare, the unit may be inserted within the duct or in the opening, so that the

 

minimum distance from the outside edge of the sleeve to the trailing edge of the intake louver is a minimum of 10".

• 

Installation of AIR-IQ unit is carried out by affixing only the damper inside the duct work. Do not use sleeve or flare to secure unit in duct work.

•  AIR-IQ unit must be installed square. 

• 

An "Installed In Duct" Mount Type AIR-IQ unit damper's finished, 

outside

 frame dimensions are ½" smaller than the specified duct width and 

height dimensions, to allow for clearance to insert the damper frame into the duct work. 

•  Ensure that the duct is square and large enough to allow the AIR-IQ Unit to be installed square. 

•  If required, make a hole in the duct work to allow extension of the drive rod. 

• 

Verify that the AIR-IQ unit is square and then secure the bottom damper frame to the floor of the duct using a 90° mounting angle. 

• 

Operate the damper manually to confirm proper sealing. 

•  As each mounting angle is installed, verify operation to ensure the damper is sealing correctly. 

•  Caulk all joints. 

AIR-IQ: TYPICAL, SINGLE-SECTION, HORIZONTAL-BLADE DAMPER 

PROBES MOUNTED PARALLEL TO BLADES

INSTALLED IN DUCT MOUNT TYPE

B*

1"

¼"

1"

¼"

clearance

3"

3"

B

B - 2.5”

1"

2"

A*

A - 3.5”

A + 2.5”

B

+

 3.5”

Non-ducted application

4"

5"

6" 6" 4"

3"

15"

Ducted application

18"

7"

Minimum distance to 

trailing edge of intake louver

4"

Minimum 4" clearance for EBTRON insertion 

style sensor probes and electronic actuator. Does 

not include access for wiring after installation of 

assembly. 

See specific EBTRON and TAMCO 

series 

technical documentation for more information.

Airflow

Inside Sleeve dimensions:

Parallel to blade = A - 3.5" 

Perpendicular to blade = B - 2.5"

Outside Damper Frame dimensions: 

Parallel to blade = A - 0.5" 

Perpendicular to blade = B - 0.5"

Outside Flare dimensions: 

Parallel to blade = A + 2.5" 

Perpendicular to blade = B + 3.5"

*NOTES:

 A x B:

  =  Always opening dimensions

 Width

  =  A: Always dimension 

parallel to blades

 Height

 =  B: Always dimension 

perpendicular to blades

TAMCO, Inc. • 27 Iber Road, Stittsville, Ontario, Canada, K2S 1E6 • Toll Free: 800.561.3449 • Toll Free Fax: 800.668.8476 • www.tamcodampers.com 

EBTRON, Inc. • 1663 Hwy. 701 S., Loris, SC USA 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • www.ebtron.com

5

Содержание AIR-IQ

Страница 1: ...0 561 3449 Toll Free Fax 800 668 8476 www tamcodampers com EBTRON Inc 1663 Hwy 701 S Loris SC USA 29569 Toll Free 800 2EBTRON 232 8766 Fax 843 756 1838 www ebtron com AIR IQ Air Flow Measurement Damper ADMD Packaged Solution AIR IQ INSTALL GUIDE_R3 INSTALLATION GUIDELINES ...

Страница 2: ...nual TM_GTx116 under separate cover LIMITED PRODUCT WARRANTY DESCRIPTION AIR IQ products are warranted against defects in materials or workmanship for 36 months from the date of shipment Should the product or component parts qualify as a warrantable failure within this time period the product or component involved will be repaired or replaced at the factory of origin in accordance with the TAMCO o...

Страница 3: ...ons or issues not covered in this document contact TAMCO Customer Service at 1 800 561 3449 EBTRON Airflow Measurement Station Refer to the EBTRON Technical Manual TM_GTx116 under separate cover for airflow measurement station wiring instrument setup and operation For additional assistance with EBTRON Airflow Measurement Station questions or issues not covered in the Technical Manual contact your ...

Страница 4: ...r flanges correct by bending them back into position gently taking care not to disturb the EBTRON sensor probes and transmitter Do not install the AIR IQ Unit if damage is more than superficial if uncertain as to extent of damage or if the damper does not seal correctly Call TAMCO customer service at 1 800 561 3449 Operate the damper section manually on a flat section of floor to verify correct bl...

Страница 5: ...are If required make a hole in the duct work to allow extension of the drive rod Verify that the AIR IQ unit is square and then secure the bottom damper frame to the floor of the duct using a 90 mounting angle Operate the damper manually to confirm proper sealing As each mounting angle is installed verify operation to ensure the damper is sealing correctly Caulk all joints AIR IQ TYPICAL SINGLE SE...

Страница 6: ... 5 A 3 5 4 Jumpers will always be on the face of damper downstream from the louver Airflow Minimum 4 clearance for EBTRON insertion style sensor probes and electronic actuator Does not include access for wiring after installation of assembly See specific EBTRON and TAMCO series technical documentation for more information Inside Sleeve dimensions Parallel to blade A 2 5 Perpendicular to blade B 2 ...

Страница 7: ...square Verify that the duct flange or hole is square flat and even Verify that the unit AIR IQ unit is square Operate the damper to verify free movement of the blades and correct sealing Secure the damper to the duct work or opening Re verify that the damper is square If the AIR IQ unit is manufactured as Sleeve Only and ducted on both sides repeat the procedure for the other flange Caulk all join...

Страница 8: ...blade B Outside Damper Frame dimensions Parallel to blade A 2 Perpendicular to blade B 2 Outside Flare dimensions Parallel to blade A 6 Perpendicular to blade B 6 NOTES A x B Always opening dimensions Width A Always dimension parallel to blades Height B Always dimension perpendicular to blades AIR IQ shown with sleeve and flare AIR IQ TYPICAL TWO SECTION HORIZONTAL BLADE DAMPER PROBES MOUNTED PARA...

Отзывы: