MIR-6030CP
3
-Channel RTD
,analoge
input / 6-Channel
digital output controller and Data Logger Programmable
for time variable set point
systems
AI channel number
2
Inputs
One 0-10VDC, 0/4-20MA DC , 0-5VDC
Two PT1000
Measurement Range
0
to
100 C
-50 to 50, 0 to 500C
RS-485 (2-wire)
Output speed (in bps)
38.4K
Maximum distance
4000 ft. (1200 m.)
Accuracy
±0.5% or better
Zero drift
±6
μ
V/
C
Span drift
±25 ppm/C
Isolation-rated voltage 3000 V
DC
CMR @ 50/60 Hz
150 dB
NMR @ 50/60 Hz
100 dB
A/D resolution Error
0.1%
Sampling rate
1 samples/second Max
Input impedance
Voltage: 2 M
Ω
, Current: 125
Ω
LED indicator
1 digit
alarm
Digital output Sink
current Power
6 channels open collector to 30 V 300 mA
Watchdog timer
1.6 second (System)
Power supply
+15 to +2
5
V
DC
(non-regulated)
Power consumption
2 W @ 20 V
DC
Burn-out detection
Yes