MIR-6030AP
3-Channel analog input & 6-Channel
digital output controller and Data Logger,
Programmable for time variable set point
AI channel number
3
Input range
0-10VDC, 0/4-20MA DC , 0-5VDC
Output speed (in bps)
Maximum distance
RS-485 (2-wire)
38.4K
4000 ft. (1200 m.)
Accuracy
±0.5% or better
Zero drift
±6
μ
V/
C
Span drift
±25 ppm/C
Isolation-rated voltage 3000 V
DC
CMR @ 50/60 Hz
150 dB
NMR @ 50/60 Hz
100 dB
A/D resolution Error
0.1%
Sampling rate
1 samples/second Max
Input impedance
Voltage: 2 M
Ω
, Current: 125
Ω
LED indicator
1 digit alarm
Digital output Sink
current Power
6 channels open collector to 30 V 300 mA
Watchdog timer
1.6 second (System)
Power supply
+15 to +2
5
V
DC
(non-regulated)
Power consumption
2 W @ 20 V
DC
Burn-out detection
Yes
Содержание MIR 6000 Series
Страница 1: ...MIR 6000 Controller and Data logger Modules User s Manual...
Страница 13: ...Installation Guideline 2...
Страница 22: ...RS 485 Network E...