Function description 

 
The OY1410 counts the pulses output by the IWM-PL3 or IWM-PL4. The corresponding 
water volume depends on the set “Pulse ratio X”-value in the IWM-PL3 or IWM-PL4, which 
in turn depends on the type of water meter used. To get the OY1410 to report water volume in 
liter it is required to set the IWM Pulse Ratio to the same value as Pulse Ratio X in the IWM-
PL3 or IWM-PL4. 
 
The OY1410 also supervises the fraud signal from the IWM-PL3 or IWM-PL4. If a fraud 
condition is detect based on the output from the IWM unit the fraud detection indicator in the 
LoRa uplink message will be set in coming reports until the fraud detection indicator has been 
explicitly cleared using a LoRa downlink request.  
 
The OY1410 also detects if the batteries are replaced, since it will not be able to count the 
pulses from the IWM-PL3 or IWM-PL4 while the batteries are not inserted. When the 
batteries have been replaced the reset detection indicator in the LoRa uplink message will be 
set in the coming reports until the reset detection indicator has been explicitly cleared using a 
LoRa downlink request. Note: The reset signal is also set during the first startup. 
 
It is possible to set the counter value in the OY1410 to a preset value using a LoRa downlink 
request. 
 

Содержание OY1410

Страница 1: ...epool visualization layer and information for advanced users The OY1400 Industrial communication and control unit is designed with focus on ease of use and reliable operation in LoRaWAN networks The p...

Страница 2: ...Dev EUI also can be found on the outside of the unit 2 App Key These codes are unique for each sensor The Dev EUI can be seen as a simple identification code the App Key is a securely generated authe...

Страница 3: ...Set depending on watermeter see table below Pulse ratio X Set to same a K index OUT3 Absolute count Pulse length 80 The K index and Pulse ratio X defines the number of liters per pulse It is important...

Страница 4: ...circuits if it is left unconnected inside the OY1410 Feed the cable though the left cable gland Connect the IWM PL3 or IWM PL4 according to the table below as illustrated by the picture to the right W...

Страница 5: ...r If you require more advanced information on the OY1410 Pulse meter please check the next sections 3 Open the unit connect the sensor and verify the jumper settings 4 Install batteries activating the...

Страница 6: ...he fraud detection indicator in the LoRa uplink message will be set in coming reports until the fraud detection indicator has been explicitly cleared using a LoRa downlink request The OY1410 also dete...

Страница 7: ...Field Bytes Value Description Note Type 1 xx 0x01 Data 0x02 Command NACK Index 1 xx Command Index Data As defined for Command Index only for Type Data Downlink command network device Field Bytes Value...

Страница 8: ...endian Minutes 1 10080 Query Set No Measurement interval in minutes Setting measurement interval resets the measurement timer 0x2B IWM data Counter Status Uint32 followed by Uint8 Big endian Count fol...

Страница 9: ...is 1234HEX 4660 Status bit 0 is set indicating a reset has been detected Setting the reporting interval to 1440 minutes 24 hours Downlink command 012605A0 Reset the Status bits Downlink command 012D0...