Talkpool OY1410 Скачать руководство пользователя страница 3

Physical installation

 

 
When the sensors have been digitally configured it is time to physically activate and install 
them. The OY1410 is dedicated to use together with BMeters’ IWM-PL3 or IWM-PL4 units.  
 
First install and configure the IWM-PL3 or IWM-PL4 unit according to BMeters’ instruction. 
It is important to configure it according to the table below: 

Setting 

Value 

K index 

Set depending on watermeter, see table below 

Pulse ratio X 

Set to same a K-index 

OUT3 

Absolute count 

Pulse length 

80 

 
The K-index and Pulse ratio X defines the number of liters per pulse. It is important that the 
Oy1410 is configured with the same setting. The table below shows the settings for different 
watermeter models: 
 

Watermeter model 

K index 

Pulse Ratio X  IWM Pulse Ratio on OY1410 

GMDM-I AF 

GMDM-I AC 

GMB-I 

WDE-K50 AF  
(up to DN125) 

10 

10 

10 

WDE-K50 AF 
(DN150 and DN200) 

100 

100 

100 

WDE-K50 AC 
(up to DN125) 

10 

10 

10 

WDE-K50 AC 
(DN150 and DN200) 

100 

100 

100 

 
 

 

Содержание OY1410

Страница 1: ...epool visualization layer and information for advanced users The OY1400 Industrial communication and control unit is designed with focus on ease of use and reliable operation in LoRaWAN networks The p...

Страница 2: ...Dev EUI also can be found on the outside of the unit 2 App Key These codes are unique for each sensor The Dev EUI can be seen as a simple identification code the App Key is a securely generated authe...

Страница 3: ...Set depending on watermeter see table below Pulse ratio X Set to same a K index OUT3 Absolute count Pulse length 80 The K index and Pulse ratio X defines the number of liters per pulse It is important...

Страница 4: ...circuits if it is left unconnected inside the OY1410 Feed the cable though the left cable gland Connect the IWM PL3 or IWM PL4 according to the table below as illustrated by the picture to the right W...

Страница 5: ...r If you require more advanced information on the OY1410 Pulse meter please check the next sections 3 Open the unit connect the sensor and verify the jumper settings 4 Install batteries activating the...

Страница 6: ...he fraud detection indicator in the LoRa uplink message will be set in coming reports until the fraud detection indicator has been explicitly cleared using a LoRa downlink request The OY1410 also dete...

Страница 7: ...Field Bytes Value Description Note Type 1 xx 0x01 Data 0x02 Command NACK Index 1 xx Command Index Data As defined for Command Index only for Type Data Downlink command network device Field Bytes Value...

Страница 8: ...endian Minutes 1 10080 Query Set No Measurement interval in minutes Setting measurement interval resets the measurement timer 0x2B IWM data Counter Status Uint32 followed by Uint8 Big endian Count fol...

Страница 9: ...is 1234HEX 4660 Status bit 0 is set indicating a reset has been detected Setting the reporting interval to 1440 minutes 24 hours Downlink command 012605A0 Reset the Status bits Downlink command 012D0...

Отзывы: