At this field the user defines the pressure difference between the filter’s inlet and outlet
that when reached, a flushing cycle will take place. The DP set-point field will disappear if
there is no Electronic DP connected. In this case the Digital DP input can be used. 

Up to version 1.02 of the Filtron 1-10, a nonzero value Set-point would have caused the
controller to ignore the Digital DP input completely, but a zero Set-point would make the
Digital DP effective and cause the Electronic DP to be ignored. 

Starting from version 1.03 a change was made so that a nonzero Set-point does no longer
cause the Digital DP input to be ignored, but instead a closed contact Digital DP input will
cause the unit to keep on executing flushing cycles as long as the contact remains closed,
ignoring the looping limit. When the DP contact reopens, the flushing stops right away
without completing the running flushing cycle. 

Starting from version 1.05 everything explained above for version 1.03 holds, but instead
of executing complete flushing cycles while the Digital DP input is closed, it will be only
valve No. 1 which will remain open as long as the contact is closed.

Starting from version 1.03 if there is no Analog DP connected or when the set-point equals
zero the unit refers to the Digital DP in the normal way, namely when the contact of the
Digital DP is constantly closed it will execute consecutive flushing cycles until reaching the
Looping Limit and then declare an endless Looping problem. 

When the pressure is expressed in BAR the range of values is 0.1 – 2.0 BAR. 

When the pressure is expressed in PSI the range of values is 1- 30 PSI. The closed Digital DP
contact will be indicated by the symbol :

The information contained herein may be changed by Deeco Services without notice. Deeco Services shall not be held liable for any errors

National Service and Supply Centre

35 Wakefield Street, Alicetown 5010

www.deeco.co.nz

The Flush Time

5-20 sec in steps of 1 sec
20-55 sec in steps of 5 sec
1-6 min in steps of 0.5 min

Defines the duration of the flushing time per station. The following options are selectable:  

The DP Set Point

Содержание Filtron 1-10

Страница 1: ...e changed by Deeco Services without notice Deeco Services shall not be held liable for any errors National Service and Supply Centre 35 Wakefield Street Alicetown 5010 www deeco co nz Filtron 1 10 DC...

Страница 2: ...switching is boosted by a charge pump The AC model contains an internal transformer that can be powered by 110V or 220V from which it generates the 24V AC for the solenoids Flushing cycles may be tri...

Страница 3: ...Street Alicetown 5010 www deeco co nz How to Program the Controller The controller is equipped with an LCD display and 4 keys as displayed below When the unit is left untouched for a minute the displa...

Страница 4: ...ENTER key again will set the selected value to the current field and move the focus to the next editable field which will start blinking Once entering this process of passing through the editable fiel...

Страница 5: ...e for version 1 03 holds but instead of executing complete flushing cycles while the Digital DP input is closed it will be only valve No 1 which will remain open as long as the contact is closed Start...

Страница 6: ...or will be triggered by the DP signal depending on which happens first No matter how the flushing cycle started the interval to the next cycle will start to be measured again after each ending of flus...

Страница 7: ...ds each of 2 outputs are used in the particular case How the outputs will be allocated depends on the definitions made during the configuration process described below The following rules apply 1 2 3...

Страница 8: ...ne output for alarm activation Delay Valve Yes No allocating an output for Delay Valve activation View Outputs This is a special mode that enables passing through the list of outputs to see how each o...

Страница 9: ...ive flushing cycles triggered by the DP sensor exceeds the Looping limit defined during configuration The fact that endless looping problem was detected will be indicated on the display and will cause...

Страница 10: ...pressure will be connected to the red point and the one that comes from the outlet Lower pressure will go to the black point It is important to put a small filter of 120 mesh not supplied between the...

Страница 11: ...ional Service and Supply Centre 35 Wakefield Street Alicetown 5010 www deeco co nz Manual Activation A flushing sequence can be manually activated by the MANUAL key When manually activated the palm ic...

Страница 12: ...ned herein may be changed by Deeco Services without notice Deeco Services shall not be held liable for any errors National Service and Supply Centre 35 Wakefield Street Alicetown 5010 www deeco co nz...

Страница 13: ...National Service and Supply Centre 35 Wakefield Street Alicetown 5010 www deeco co nz Wiring Diagram The external DP sensor is optional and it is intended for use in cases there is no embedded electro...

Страница 14: ...errors National Service and Supply Centre 35 Wakefield Street Alicetown 5010 www deeco co nz The external DP sensor is optional and it is intended for use in cases there is no embedded electronic DP...

Страница 15: ...dry battery or 12v rechargeable battery with solar panel of 2 watts 12v DC latching solenoids Embedded electronic analog DP sensor Dry contact pressure sensor 0 60 C DC Model Power Source Outputs DP...

Отзывы: