PRODUCT NAME

FLAME SENSOR

FS-5000E

Ultraviolet rays detection (Detected wave length <185 to 260nm>) 

                             33ft. (10m) [Gas Flame of Lighter in front of sensor : approx. :  2.75”(7cm)]
                             100ft. (30m) [Flame of N-heptane on fire plate 15cm×15cm : approx. : 23.62”(60cm)
                             *The 

fl

ame size is rough.

                             Vertical      : approx. 75° (upward :15°)
                             Horizontal  : approx. 100° (downward :60°) 

                             Vertical      : downward 90° (horizontal-vertical)
                             Horizontal  : 180° 

                             H (100%), L (50%) [selectable by switch]

                             1sec., 6secs., 15secs., 30secs. [selectable by switch]

10V to 30VDC (non-polarity)

35mA or less

Dry contact relay Form C (alarm : open/close)
Contact capacity : 30V (AC/DC) 0.5A or less (resistance load)
Operation time : The following are selectable
    Detection time + off delay operation approx. 2 secs. - 1 min.
    Detection time + off delay operation approx. 5 secs. - 10 mins.
Output operation : The following are selectable
    Same time as above    continuous output
    Same time as above    intermittent output (Flashing)
Operation mode (day/night time discernment function)
       : 5 lux (night time operation) - 

 lux (day time operation) adjustment volume

LED(yellow) blinking and lights on /or LED disable. [selectable by switch] 

Operation LED (red) : synchronous dry contact relay
Memory indication LED (yellow) : After blinking for 3 minutes and auto reset after 47 minutes
                                                      or reset by manual

Lead wiring, power supply : 2 / dry contact : 3 

4°F to 

122°F  (

20

 to 

50

)

Indoor, Outdoor

approx. 19.3 oz (550g)

Sensor part : PC resin (white), Adjustment,  mounting part : AES resin (white)

Tapping screw 

φ

6× 30 (SUS)  : 4 pcs ,  Tapping screw 

φ

4×  8  (SUS)  : 1 pc.

Band   : 1 pc.  Area mask seal : 1 pc.

Pole attachment (for the end) : BP-01,  Pole attachment (for the middle) : BP-02,  Vise : BV-03

10

SPECIFICATIONS

TROUBLE

CHECK

9

TROUBLE SHOOTING

Completely inactive

CORRECTIVE ACTION

Sometimes inactive

The LED lights but the 
connected device
inactivates 

Activate without 

fl

ame

Maintenance

When the sensor is dirty, clean the cover with a soft cloth moistened with a small amount of cleaning solution.
Do not use chemicals such as thinner or alcohol. Check operation once a week.
Do not fail to check operation whenever furniture in the vicinity is moved.When the battery is low, change it for a new one immediately.  
If the battery is not changed, the sensor may not operate.

OPTIONAL

ACCESSORIES

 

APPEARANCE

WEIGHT

INSTALLATION

AMBIENT TEMP. RANGE

WIRING

LED

ALARM MEMORY

 



ALARM OUTPUT

POWER CONSUMPTION

POWER SUPPLY

Detection timer

SENSITIVITY
ADJUSTMENT

Sensitivity

Adjustment
range 

Angle

Distance

DETECTION AREA

 

DETECTION SYSTEM

MODEL NO.

Correct supply or replace broken wiring

Correct supply or replace broken wiring

Remove the interrupting object

Re-adjust the detection area set up

      

(Refer to "4. DETECTION AREA")

Re-adjust the operation mode 

     

(Refer to "7. OPERATION AND FUNCTION")

Re-adjust the detection timer set up

No power supply (Broken or improper wiring)

Low voltage

Interrupting object in front of detection area (Including glass)

Improper detection area set up 

  

(Including detection distance)

Improper operation mode set up

Improper detection timer set up

Improper detection area set up 

      (Including detection distance)

Improper operation mode set up

Detection window soiled

Improper detection timer, sensitivity set up

Re-adjust the detection area set up

                               (Refer to "4. DETECTION AREA")

Re-adjust the operation mode

               (Refer to "7. OPERATION AND FUNCTION")

Wipe with soft dry cloth

Re-adjust the detection timer, sensitivity set up

Unstable power supply

Large electrical noise source such as radio station or wireless

    station nearby

Unexpected ultraviolet ray nearby

   (Refer to "3. PRECAUTIONS")

Sparking object such as welding construction site, railway 

    pantograph nearby

Correct power supply

Relocate the sensor

Remove the object / Relocate the sensor / Adjust the

    angle / Mask the area by seal / Set up sensitivity to "L" /
    Set up detection timer to the next longer time.
    (Refer to "4. DETECTION AREA")

Relocate the sensor / Adjust the angle / Mask the area 

    by seal / Set up sensitivity to "L" / Set up detection timer
    to the next longer time.
    (Refer to "4. DETECTION AREA")

Poor contact output connection or broken wire

Improper output connection

Improper connected units

Check the wiring or connection

Check the output terminal by tester etc.

Check the connected units

Содержание FS-5000E

Страница 1: ...nnect equipment that exceeds the indicated output capacity It may cause fire We appreciate your purchase of a TAKEX flame sensor This sensor will provide long and dependable service when properly inst...

Страница 2: ...the unit from falling and to maintain resistance to rain A high installation location is recommended to prevent vandal ism over 2 5m This product is for installation on walls ceilings and under eaves...

Страница 3: ...AME OF N HEPTANE 23 62 60cm 66 20 m 49 15 m 33 10 m 16 5 5 m 16 5 5 m 33 10 m 49 15 m 66 20 m 16 5 5 m 33 10 m 49 15 m 66 20 m 83 25 m 100 30 m 16 5 5 m 33 10 m 49 15 m 66 20 m 83 25 m 100 30 m 16 5 5...

Страница 4: ...emporary and confirm the area and operation Make a hole through the 4 mounting holes knock outs by a driver etc Fix the mounting box by the 4 6 30 tapping screws to the surface Fix the mounting base t...

Страница 5: ...om of the sensor The adjustment volume can be turned by coins Do not turn strongly it may cause damage This product detects ultraviolet ray included in flames and outputs an alarm Outdoor installation...

Страница 6: ...power on reset operation Set up for area check Factory set Indicates Factory set Manual reset Power supply off and on again or Alarm memory function off This function monitors the strength of nuisance...

Страница 7: ...week Do not fail to check operation whenever furniture in the vicinity is moved When the battery is low change it for a new one immediately If the battery is not changed the sensor may not operate OP...

Страница 8: ...product repairs made after our Warranty Period has expired No 04 990 1406 In Japan Takex America Inc 4 15 Howleys Road Notting Hill VIC 3168 Tel 61 03 9544 2477 Fax 61 03 9543 2342 Takenaka Engineerin...

Отзывы: