⑦
㈯
PRODUCT NAME
FLAME SENSOR
FS-5000E
Ultraviolet rays detection (Detected wave length <185 to 260nm>)
33ft. (10m) [Gas Flame of Lighter in front of sensor : approx. : 2.75”(7cm)]
100ft. (30m) [Flame of N-heptane on fire plate 15cm×15cm : approx. : 23.62”(60cm)
*The
fl
ame size is rough.
Vertical : approx. 75° (upward :15°)
Horizontal : approx. 100° (downward :60°)
Vertical : downward 90° (horizontal-vertical)
Horizontal : 180°
H (100%), L (50%) [selectable by switch]
1sec., 6secs., 15secs., 30secs. [selectable by switch]
10V to 30VDC (non-polarity)
35mA or less
Dry contact relay Form C (alarm : open/close)
Contact capacity : 30V (AC/DC) 0.5A or less (resistance load)
Operation time : The following are selectable
Detection time + off delay operation approx. 2 secs. - 1 min.
Detection time + off delay operation approx. 5 secs. - 10 mins.
Output operation : The following are selectable
Same time as above continuous output
Same time as above intermittent output (Flashing)
Operation mode (day/night time discernment function)
: 5 lux (night time operation) -
∞
lux (day time operation) adjustment volume
LED(yellow) blinking and lights on /or LED disable. [selectable by switch]
Operation LED (red) : synchronous dry contact relay
Memory indication LED (yellow) : After blinking for 3 minutes and auto reset after 47 minutes
or reset by manual
Lead wiring, power supply : 2 / dry contact : 3
−
4°F to
+
122°F (
−
20
℃
to
+
50
℃
)
Indoor, Outdoor
approx. 19.3 oz (550g)
Sensor part : PC resin (white), Adjustment, mounting part : AES resin (white)
Tapping screw
φ
6× 30 (SUS) : 4 pcs , Tapping screw
φ
4× 8 (SUS) : 1 pc.
Band : 1 pc. Area mask seal : 1 pc.
Pole attachment (for the end) : BP-01, Pole attachment (for the middle) : BP-02, Vise : BV-03
10
SPECIFICATIONS
TROUBLE
CHECK
9
TROUBLE SHOOTING
Completely inactive
CORRECTIVE ACTION
Sometimes inactive
The LED lights but the
connected device
inactivates
Activate without
fl
ame
Maintenance
When the sensor is dirty, clean the cover with a soft cloth moistened with a small amount of cleaning solution.
Do not use chemicals such as thinner or alcohol. Check operation once a week.
Do not fail to check operation whenever furniture in the vicinity is moved.When the battery is low, change it for a new one immediately.
If the battery is not changed, the sensor may not operate.
OPTIONAL
ACCESSORIES
APPEARANCE
WEIGHT
INSTALLATION
AMBIENT TEMP. RANGE
WIRING
LED
ALARM MEMORY
*
*
*
*
ALARM OUTPUT
POWER CONSUMPTION
POWER SUPPLY
Detection timer
SENSITIVITY
ADJUSTMENT
Sensitivity
Adjustment
range
Angle
Distance
DETECTION AREA
DETECTION SYSTEM
MODEL NO.
・
Correct supply or replace broken wiring
・
Correct supply or replace broken wiring
・
Remove the interrupting object
・
Re-adjust the detection area set up
(Refer to "4. DETECTION AREA")
・
Re-adjust the operation mode
(Refer to "7. OPERATION AND FUNCTION")
・
Re-adjust the detection timer set up
・
No power supply (Broken or improper wiring)
・
Low voltage
・
Interrupting object in front of detection area (Including glass)
・
Improper detection area set up
(Including detection distance)
・
Improper operation mode set up
・
Improper detection timer set up
・
Improper detection area set up
(Including detection distance)
・
Improper operation mode set up
・
Detection window soiled
・
Improper detection timer, sensitivity set up
・
Re-adjust the detection area set up
(Refer to "4. DETECTION AREA")
・
Re-adjust the operation mode
(Refer to "7. OPERATION AND FUNCTION")
・
Wipe with soft dry cloth
・
Re-adjust the detection timer, sensitivity set up
・
Unstable power supply
・
Large electrical noise source such as radio station or wireless
station nearby
・
Unexpected ultraviolet ray nearby
(Refer to "3. PRECAUTIONS")
・
Sparking object such as welding construction site, railway
pantograph nearby
・
Correct power supply
・
Relocate the sensor
・
Remove the object / Relocate the sensor / Adjust the
angle / Mask the area by seal / Set up sensitivity to "L" /
Set up detection timer to the next longer time.
(Refer to "4. DETECTION AREA")
・
Relocate the sensor / Adjust the angle / Mask the area
by seal / Set up sensitivity to "L" / Set up detection timer
to the next longer time.
(Refer to "4. DETECTION AREA")
・
Poor contact output connection or broken wire
・
Improper output connection
・
Improper connected units
・
Check the wiring or connection
・
Check the output terminal by tester etc.
・
Check the connected units
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●