Alarm Memory Function


8

OPERATION CHECK

Check operation after wiring and installation.

(1) Detection area

(2) Operation

6

ON

6

OFF

ADJUSTING BOX

ALARM MEMORY

MEMORY

Does not indicate

Detection timer

Sensitivity

Delay time

Day light

Alarm memory function

Memory auto reset

Environment monitor 

1 sec.

H

2 secs.

Night & Day

ON

ON

OFF

Environment monitoring function

No ultraviolet 

source for 

false alarm.

A little ultraviolet 

source for

false alarm.

Much ultraviolet 

source

for false alarm.

LED OFF

Blinking
 (slow)

Blinking
 (fast)

LED lights ON

OFF

ON

The strength is showed by operation LED (red).

Memory auto reset

(Factory set:On)

Blinking  (3 minutes)
Light on (Until resetting by manual)

OFF

ON

ON

OFF

Blinking  (3 minutes)

Memory LED (yellow)

Setting

Light on (Auto reset after 47 minutes later)

Choose the set up according to the purpose and environment.

Activate the sensor again and check the operation LED (red), and connected machines and tools.

Set up the area angle reffering to the 

"4. 1. Detection area" picture.         Put power on.

Turn on a lighter more than 1 sec. within the detection area.  Check the angle and size of area by operation LED (red) and 
connected machines and tools.

In case it includes unnecessary areas, adjust it by changing angle or masking the area.

In case of resetting this function during blinking and lighting, 
turn the power off and on again. 
(power on reset operation)

Set up for area check.  (Factory set)

Indicates   [Factory set]

Manual reset : Power supply off and on again or "Alarm memory 
                        function" off.

This function monitors the strength of nuisance by ultraviolet 
in installed environment to check whether there is a cause of 
false alarm.

When the performance of this sensor becomes unstable, please 
use this function to check the strength of ultraviolet.

(Factory set : OFF)

This function enables identification of individual sensors in 
multiple sensor configuration. 
After raising an alarm, the memory indication LED (yellow) 
blinks for 3 minutes and then lights for 47 minutes.
When an alarm is caused again during the lighting, it will light 
for another 47 minutes. <re-trigger operation>

The operation LED (red) may be "light on" 2~3 times per 1 
minute in even normal environment. In case of more frequent 
lighting,  there may be a nuisance ultraviolet source in the site. 
Therefore, please set sensitivity "L" and detection timer more 
than "6 secs".

In case operation LED (red) lights on or blinking continue more 
than set detection timer, Please adjust sensitivity "L" and 
detection timer more than above operation LED (red) duration 
time.

The environment of ultraviolet is not always equable. 
It may 

fl

uctuate by varied factors.  

When the performance of this 

fl

ame sensor becomes unstable 

after installation, please adjust sensitivity to downward and 
detection timer to the next longer time.

The alarm signal outputs at setting level (sensitivity, detection 
timer) even environment monitoring function is "ON".

1: 

2: 

Содержание FS-5000E

Страница 1: ...nnect equipment that exceeds the indicated output capacity It may cause fire We appreciate your purchase of a TAKEX flame sensor This sensor will provide long and dependable service when properly inst...

Страница 2: ...the unit from falling and to maintain resistance to rain A high installation location is recommended to prevent vandal ism over 2 5m This product is for installation on walls ceilings and under eaves...

Страница 3: ...AME OF N HEPTANE 23 62 60cm 66 20 m 49 15 m 33 10 m 16 5 5 m 16 5 5 m 33 10 m 49 15 m 66 20 m 16 5 5 m 33 10 m 49 15 m 66 20 m 83 25 m 100 30 m 16 5 5 m 33 10 m 49 15 m 66 20 m 83 25 m 100 30 m 16 5 5...

Страница 4: ...emporary and confirm the area and operation Make a hole through the 4 mounting holes knock outs by a driver etc Fix the mounting box by the 4 6 30 tapping screws to the surface Fix the mounting base t...

Страница 5: ...om of the sensor The adjustment volume can be turned by coins Do not turn strongly it may cause damage This product detects ultraviolet ray included in flames and outputs an alarm Outdoor installation...

Страница 6: ...power on reset operation Set up for area check Factory set Indicates Factory set Manual reset Power supply off and on again or Alarm memory function off This function monitors the strength of nuisance...

Страница 7: ...week Do not fail to check operation whenever furniture in the vicinity is moved When the battery is low change it for a new one immediately If the battery is not changed the sensor may not operate OP...

Страница 8: ...product repairs made after our Warranty Period has expired No 04 990 1406 In Japan Takex America Inc 4 15 Howleys Road Notting Hill VIC 3168 Tel 61 03 9544 2477 Fax 61 03 9543 2342 Takenaka Engineerin...

Отзывы: