APPX
Appendix 1 Error Code List
List of error codes displayed in detailed information 3
The following table shows the list of error codes displayed in detailed information 3 and their respective causes and corrective
actions.
Error code
Error cause
Corrective action
0001H
A specified option driver is not loaded.
• Reinstall the option driver, then restart the MES interface
module.
• Turn the power OFF and ON or reset the CPU module.
• If the problem is still not resolved, contact the publisher of the
option driver.
0002H
A module specified when loading an option driver does not
exist.
0003H
A specified version.txt does not exist.
0004H
Required information (type information) is not included in the
context file.
0005H
Required information in the context file is insufficient.
0006H
A module of an installed option driver is incorrect.
(A file is corrupted or overwritten etc.)
0007H
The format of the context file is incorrect.
0008H
API of an option driver is called even though the option driver
has not been initialized.
0009H
A registered license file is invalid.
• Delete the registered license file, then register a new one.
• Start the temporary authentication of the option driver to be
used.
000AH
A checksum and a value (CODE2) do not match in the
context file.
• Retry the writing of the settings with MES Interface Function
Configuration Tool.
• Delete a tool add-in and add it again, then set an option driver
again.
• If the problem is still not resolved, contact the publisher of the
option driver.
000BH
A checksum for an option driver does not match a value
(CODE1) in the context file.
• Reinstall the option driver, then restart the MES interface
module.
• Turn the power OFF and ON or reset the CPU module.
• If the problem is still not resolved, contact the publisher of the
option driver.
000CH
The OPD version of the context file is newer than that in the
add-in adapter.
• Install the latest option driver, then restart the MES interface
module.
• If the problem is still not resolved, contact the publisher of the
option driver.
000DH
The major version of the context file is newer than that in the
add-in adapter.
000EH
Opening a port of an access target device fails.
• Check whether the access target device setting is correct.
• Check the status of the access target device.
• Check whether the route to the access target device is correct.
• Check whether there is any problem in the route to the access
target device.
000FH
The communication setting of an access target device is not
proper.
0010H
A response equivalent to NAK is received from an access
target device.
0011H
The length of received data is short.
• Install the latest option driver, then restart the MES interface
module.
• If the problem is still not resolved, contact the publisher of the
option driver.
0012H
Parameters set in an MES interface module are incorrect.
• Check whether writing to a read-only device is performed.
• Retry the writing of the settings with MES Interface Function
Configuration Tool.
• Delete a tool add-in and add it again, then set an option driver
again.
0013H
An unexpected error has occurred.
• Install the latest option driver, then restart the MES interface
module.
• If the problem is still not resolved, contact the publisher of the
option driver.
Содержание MITSUBISHI ELECTRIC MELSEC iQ-R Series
Страница 2: ......
Страница 12: ...10 1 OPTION DRIVER 1 1 Software Configuration MEMO...
Страница 14: ...12 2 COMMON SPECIFICATIONS MEMO...
Страница 58: ...56 MEMO...
Страница 61: ......