4
Flow
The flow rate through the T-KJr. is limited to a
maximum of 5.8 GPM. The temperature setting,
along with the supply temperature of the water will
determine the flow rate the unit puts out. Consult
the flow charts on the last page of this manual to
determine the possible outlet temperature and flow
rate combinations. Based on the United States
Department of Energy method of testing water
heater output, the T-KJr. is rated for 180 gallons
per hour, or 3.0 GPM, at a 77
°
F rise above the
inlet temperature. Refer to the following chart of
typical household flow rates to determine what the
T-KJr. can do in a household application.
Remember that for bathing, cold water will be
mixed for a comfortable temperature, increasing
the flow output rate.
Freeze Prevention
This unit comes equipped with heaters that
discourage the unit from freezing. For this freeze
prevention system to operate there has to be
electrical power to the unit.
The freeze prevention devices will not work if the
electrical power source is disconnected.
The unit has been rated for temperatures down to
5º F (-15º C) in a wind free environment. The wind
chill factor will cause the unit to freeze at
temperatures above 5º F (-15º C), even if the unit
is installed indoors.
For indoor installation in areas where the
temperature will be well below freezing for
extended periods of time, use the included
“thermostat extension cable” to relocate the
internal thermostat located on the fan motor to the
outdoors. This will sense the ambient air
temperature and turn on the internal heater blocks
on to prevent the heat exchanger from freezing.
Install a TK-TV03 backflow prevention kit so that
cold air will not backflow into the flue and cause
the unit to freeze. Do not install the water heater in
an area with extremely cold weather. This will void
your warranty and Takagi Industrial Co. USA Inc.
will not be responsible for any damage that occurs.
WARNING
: The pipe heaters are located on the
Flash Water Heater. Any hot or cold water pipes
located outside of the unit will not be protected.
Properly protect and insulate these pipes from
freezing.
If the heater will not be in use for a long period of
time or if the temperatures will drop below 5º F (-
15º C) with the wind chill factor, turn off heater and
drain the unit of water. This applies to indoor and
outdoor installations. This will keep the unit from
freezing and being damaged. Frozen heat
exchangers are not covered under warranty.
Follow these instructions carefully:
1. Turn off the power supply to the Flash Water
Heater.
2. Close manual gas control valve.
3. Close manual water shut off valve.
4. Open all hot water taps in the house.
(Bathroom, kitchen, laundry room, etc.). When
the water flow has ceased, close all hot water
taps.
5. Have a bucket to catch the water from the
unit’s drain plugs. Remove the drain plugs to
drain the water out of the unit.
6. Let drain for 5 minutes.
7. Securely screw the drain plugs back into place.
Follow these steps when it is again safe to use the
water heater:
1. Make sure all hot water taps are closed and
the drain plugs are securely attached.
2. Purge the water line of debris.
3. Open manual water control valve located on
the water supply line.
4. Open all the hot water taps to verify water
flows to the taps. Close hot water taps.
5. Open manual gas control valve located on the
gas supply line.
6. Turn on the power supply to the Flash Water
Heater.
Household Flow Rates
Appliance / Use
Flow Rate
(GPM)
Lavatory Faucet
1.0
Bath Tub
4.0
Shower
2.0
Kitchen Sink
1.5
Dishwasher
1.5
Washing Machine
2.0
Taken from UPC 1997
Содержание T-KJr
Страница 7: ...6 Wiring Diagram...
Страница 17: ...16 This system will also need a pump of 1 12 hp or greater depending on the application situation...
Страница 24: ...23 Case Burner Gas Manifold...
Страница 25: ...24 Water Way...