time), you would see rust mix up water in red, flow out from tap. That is normal, just keep 

draining and the rust will disappear after a while. 

 

Before asking for service or repairing, check the following points: 

 

Condition 

Cause 

Normal 

operation 

 

White  aerosol  or  globule 
is give out 

 

Make  sound  of  “hiss” 
every now and then 

 

Air supply motor stop automatically to defrost. 

 

At the beginning and the end of defrost process, sound is 
give out in motor valve. 

 

During the  process  of  just  after  have  stopped,  sound like 
water  flow  occur,  which  will  be  amplified  at  the  first  2

minutes, this is caused by the process of refrigerant current 
or water. 

 

Slight “hiss” is caused by heat exchanger as temperature 
changes. The sound give out because of heat expands and 
cold contracts of heat exchanger. 

Please check 

that again 

 

Stop operation or start up 
automatically 

 

Check the timer whether it is correctly set 

 

Detect antifreezing mode is operating 

 

No operate 

 

Whether the power is cut 

 

Whether the manual power supply switch is off 

 

Whether fuse is broken 

 

Whether  the  protection  device  works  (Operation  lamp  is 
lightened) 

 

Whether it is the time set(Operation lamp is lightened) 

 

Inefficient heating 

Whether the inlet and outlet of heat pump units is blocked 

 

In  case  of the  flowing  malfunctions,  please  cut  off the  manual  power  switch  and  contact  the  local 

dealer or after service center: 

  The  fuse  was  burnt  out  frequently  or  the  earth  leakage  protective  device  was  broken  up 

frequently. 

  Only the red indication will be flashed. 

2.10 Trouble shooting 

Code

 

Explanation

 

Solution 

E2 

Outdoor unit and wire controller 
communication error 

Check whether the communication wire is damaged. 

Check whether the communication wire is correctly connected to the 
motherboard. 

Check whether voltage provided is too low. 

Check whether the signal of communication wire is in strong 
electromagnetic interference. 

E3 

Outlet 

water 

temperature   

sensor Tout error 

Check whether the Tout temperature sensor is damaged. 

Check whether the Tout temperature sensor is correctly connected to the 
motherboard. 
Check whether the signal of Tout sensor is in strong electromagnetic 
interference. 

E4 

Inlet water temperature sensor 
T6 error 

Check whether the T6 temperature sensor is damaged. 

Check whether the T6 temperature sensor is correctly connected to the 
motherboard. 

Содержание Ansal LRSJ-80/NYN1

Страница 1: ...n Domestic Pool Type Heat Pump Water Heater Technical Manual Applicable Model LRSJ 60 NYN1 LRSJ 80 NYN1 LRSJ 120 NYN1 LRSJ 140 NYN1 Tadiran reserves the right to discontinue or change specification or...

Страница 2: ...ication performance 4 2 1 Features 4 2 2 Refrigerant circuit 5 2 3 Unit outlook 5 2 4 Specifications 6 2 5 Performance diagram 8 2 6 Wiring diagram 16 2 7 Installation 18 2 8 Trial run 26 2 9 Maintena...

Страница 3: ...385 220 240V 50Hz 1Ph LRSJ 80 NYN1 66 75 1015 705 385 220 240V 50Hz 1Ph LRSJ 120 NYN1 75 85 1050 855 315 220 240V 50Hz 1Ph LRSJ 140 NYN1 75 85 1050 855 315 220 240V 50Hz 1Ph 1 2 External appearance 1...

Страница 4: ...ge fire explosion etc Environmental protection Environment friendly refrigerant R410A is used No discharge of poisonous gas No pollution to atmosphere and environment Easy operation and automatic cont...

Страница 5: ...RSJ 140 NYN1 Evaporator Copper tube and aluminum fin type heat exchanger Titanium tube heat exchanger Titanium tube heat exchanger is use for heat exchange between refrigerant and water Fan Axial fan...

Страница 6: ...5 705 385 1050 855 315 1050 855 315 Packing W H D mm 1095 840 445 1095 840 445 1160 980 410 1160 980 410 Net gross weight kg 64 73 66 75 75 85 75 85 Outdoor noise level dB A 58 58 58 58 Refrigerant ty...

Страница 7: ...766 792 Number of circuits 5 5 8 8 Water pipeline Water inlet pipe 50 50 50 50 Water outlet pipe 50 50 50 50 Water circulating pipe 25 25 25 25 Max pressure MPa 0 4 0 4 0 4 0 4 The volume flow of wate...

Страница 8: ...mestic Pool Type Technical Manual 2 5 Performance diagram 2 5 1 Unit capacity and energy efficiency diagram in heating mode Model LRSJ 60 NYN1 Notes The test conditions inlet water temperature is 27 o...

Страница 9: ...Tadiran Domestic Pool Type Technical Manual TCAC RTSM 20150203 9 Model LRSJ 80 NYN1 Notes The test conditions inlet water temperature is 27 outlet water temperature is 29...

Страница 10: ...TCAC RTSM 20150203 Tadiran Domestic Pool Type Technical Manual Model LRSJ 120 NYN1 Notes The test conditions inlet water temperature is 27 outlet water temperature is 29...

Страница 11: ...Tadiran Domestic Pool Type Technical Manual TCAC RTSM 20150203 11 Model LRSJ 140 NYN1 Notes The test conditions inlet water temperature is 27 outlet water temperature is 29...

Страница 12: ...03 Tadiran Domestic Pool Type Technical Manual 2 5 2 Unit capacity and energy efficiency diagram in cooling mode Model LRSJ 60 NYN1 Notes The test conditions inlet water temperature is 27 water flow v...

Страница 13: ...Tadiran Domestic Pool Type Technical Manual TCAC RTSM 20150203 13 Model LRSJ 80 NYN1 Notes The test conditions inlet water temperature is 27 water flow volume is 3 5m3 h...

Страница 14: ...TCAC RTSM 20150203 Tadiran Domestic Pool Type Technical Manual Model LRSJ 120 NYN1 Notes The test conditions inlet water temperature is 27 water flow volume is 5 0m3 h...

Страница 15: ...Tadiran Domestic Pool Type Technical Manual TCAC RTSM 20150203 15 Model LRSJ 140 NYN1 Notes The test conditions inlet water temperature is 27 water flow volume is5 8m3 h...

Страница 16: ...TCAC RTSM 20150203 Tadiran Domestic Pool Type Technical Manual 2 6 Wiring diagram Model LRSJ 60 NYN1 LRSJ 80 NYN1...

Страница 17: ...Tadiran Domestic Pool Type Technical Manual TCAC RTSM 20150203 17 Model LRSJ 120 NYN1 LRSJ 140 NYN1...

Страница 18: ...tal Do not install the heat pump close to inflammable gas source Do not install the heat pump close to a road or path to protect the appliance against mud splashing Avoid places that are subject to st...

Страница 19: ...estic Pool Type Technical Manual TCAC RTSM 20150203 19 Space of foot screw bolts unit mm Model A B C D E F LRSJ 60 NYN1 LRSJ 80 NYN1 610 390 170 1015 385 705 LRSJ 120 NYN1 LRSJ 140 NYN1 590 333 165 10...

Страница 20: ...efore operation please confirm that the specifications of connective pipes are correct and thermal insulation layer have been wrapped on pipes It requires that all pipes have been sealed up and no wat...

Страница 21: ...h 5 8m3 h Water treatment In order to use our appliances under the best conditions the following parameters must be respected Maximum concentration of free chlorine is 2 5 mg L Maximum concentration...

Страница 22: ...it is not equipped with power cord User could select power cable by reference to power supply specifications Shield wire must be employed for signal wire Select the power supply capacity and wire size...

Страница 23: ...of the unit for the security reason it is required that a leakage protector should be installed in the external electric control box of the unit according to the requirement on the above diagram Cabl...

Страница 24: ...d out The photo of main control board PCB I O Ports description Code Part name Code Part name N C No connect Tp Temperature sensor of compressor air exhaust Tout Outlet water temperature sensor Pro_H...

Страница 25: ...Tadiran Domestic Pool Type Technical Manual TCAC RTSM 20150203 25...

Страница 26: ...ally in the heating mode Whether the outlet water temperature is normal Whether there is vibration or abnormal sound when operating Whether there is refrigerant leakage 2 9 Maintenance Before leave th...

Страница 27: ...is broken Whether the protection device works Operation lamp is lightened Whether it is the time set Operation lamp is lightened Inefficient heating Whether the inlet and outlet of heat pump units is...

Страница 28: ...temperature sensor is correctly connected to the motherboard Check whether the signal of Tp sensor is in strong electromagnetic interference P0 System high pressure protection 4 4MPa active 3 2MPa ina...

Страница 29: ...e fans are restarted This cloud is evacuated to the back of the unit Operation condition of the heat pump water heater For proper using of water heater please operate at the outdoor temperature 7 38 W...

Страница 30: ...bout RCCB Outdoor unit must use RCCB be install a RCCB between in user power supply and the outdoor unit In case the unit cannot act but not attribute to power failure please check these RCCB switches...

Страница 31: ...rature and blank when screen protection Codes are showed at the malfunction or protection time ALARM indicator It will flashing at the malfunction or protection time Names of keys on the wire controll...

Страница 32: ...L TEMP 2 Mode Selection The unit is enhanced with three operation modes Cool Mode Heat Mode and Pump Mode Cool Mode The unit cools down swimming pool water by compressor drive according to heat pump p...

Страница 33: ...ating 4 Pump 8 standby 4th Fan speed 0 OFF 1 Low 2 High 5th Ambient temperature Value of T4 6th Compressor discharge temperature Value of Tp 7th Pipe temperature Value of T3 8th Inlet water temperatur...

Страница 34: ...68355 74 1 43498 114 0 42304 5 46 5725 35 6 40021 75 1 38703 115 0 41164 4 44 36 6 13059 76 1 34105 116 0 4006 3 41 5878 37 5 87359 77 1 29078 117 0 38991 2 39 8239 38 5 62961 78 1 25423 118 0 37956 1...

Страница 35: ...7 261 4 33 38 89 73 8 643 113 2 559 6 247 8 34 37 3 74 8 358 114 2 489 5 234 9 35 35 78 75 8 084 115 2 422 4 222 8 36 34 32 76 7 82 116 2 357 3 211 4 37 32 94 77 7 566 117 2 294 2 200 7 38 31 62 78 7...

Отзывы: