SKY
-
30
-
7.8 Connecting the Drain Hose
Connect
the rubber syphon to the drain hose connection. See Fig. 7-8 for details.
Fig. 7-8
7.9 Connecting the Refrigerant Lines and Refrigerant Charge
7.9.1 Connecting the Refrigerant Lines
•
To connect the refrigerant lines use only "L" type sealed, dehydrated copper refrigerant
tubing. No other type may be used. The use of other types of tubing will void the
manufacturer's warranty.
•
Do not open service valves and do not remove protecting caps from tubing ends until all the
connections are made.
•
Take care to avoid links or flattening of the tubing.
•
Bend tubing with special bending tools to avoid the formation of sharp bends.
•
Keep the tubing free of dirt, sand, moisture and other contaminants to avoid damaging the
refrigerant system.