12.2.5 STANDBY MODE (MAX PRO MOD.)
In the operating mode with external connection for 0-10 V / PWM signal, the
“Standby”
mode is indicated by the yellow
LED (flashing slowly) and the word
“Stb”
on the display
(see FIG. 12)
.
FIG. 12 (Standby mode)
12.2.6 ANALOGUE INPUT
In the
“external input”
mode, the circulator accepts either a DC voltage signal or a PWM signal. The selection of the
signal type is automatically made by the circulator without operator intervention.
12.2.7 INPUT 0-10V
The circulator operates at variable speed depending on the DC input voltage.
At voltages below 1.5 V, the circulator is in “standby” mode.
At voltages between 2 V and 10 V, the circulator operates at a variable speed depending on the voltage:
- 0% for a voltage not exceeding or equal to 2 V
- 50% at 6 V
- 100% for voltages greater than or equal to 10 V
Between 1.5 V and 2 V the circulator can be in “standby” or at minimum speed depending on the previous state
(hysteresis).
FIG. 13 (Analogue input)
INFORMATION
IF THE INPUT REMAINS DISCONNECTED, THE CIRCULATOR GOES INTO STANDBY MODE.