12.2.2 CIRCULATOR SETTING MAX PRO MOD.
Change the performance of the circulator (head) according to the need, using the
“SET”
,
DOWN
and
UP
buttons.
LED
Function
Setting
Purple color (**)
ActiveADAPT (*)
1)
Press the
“SET”
button for
2 s
, the LED indicating the
operating status starts flashing quickly.
2)
Press the
UP
or
DOWN
buttons to select the new
operating mode and the desired value for the constant,
proportional and variable power curves (see display
below).
3)
Press the
“SET”
button to confirm the desired operating
mode and value.
Orange color (**)
Constant Curve
(C1 - C2 - C3 - C4 - C5)
Green color (**)
Proportional Curve
(P1 - P2 - P3 - P4 - P5)
Blue color (**)
Variable power curve
MIN - MAX (0÷100%)
Yellow color (**)
External input
0-10 V or PWM
Constant Curve
(C1 - C2 - C3 - C4 - C5)
Proportional Curve
(P1 - P2 - P3 - P4 - P5)
Variable power curve
MIN - MAX (0÷100%)
(*)
Factory settings
(**)
Turns white to indicate the presence of air in the system or red to indicate the presence of an error
TAB. 19 (Set-up of the circulator MAX PRO mod.)