background image

HOT

NEUTRAL

GROUND

BLACK

WHITE

GREEN

SCREW

TERMINAL BOX

• Disconnect AC power supply. Remove terminal box cover. Thread a wiring connector into npt knockout. 

Note:

To install an angle connector

removal of sensor cap may be required for clearance. Connect hot wire to black lead and neutral wire to white lead. Connect ground wire to Green

Ground screw. Replace terminal box cover.

      •   Remove sensor cap. Slide sensor wires through grommet in sensor cap. See diagram above.

      •   Attach sensor wires provided as shown:

              - Delta-T mode uses supply and return (S + R).

              - Set Point mode uses supply (S) for system sensor and return (R) for boiler protection return sensor.

      •   Attach sensors to supply and return piping using the zip-ties provided. See diagram above.

              - In Delta-T mode, place sensors on system supply and return.

               - In Set Point Heat mode, place supply sensor on system loop supply. If boiler protection option is used, place return sensor on boiler return.

      •   Insulate pipe around sensors as shown.

5.    Start the circulator:

Note:

When power is applied to the circulator it will go through a 10 second diagnostic delay before starting. The LCD will illu-

minate for the first 5 minutes of a run cycle. Press any of the programming buttons to re-illuminate the LCD.
When air purging the system, it is recommended to run the circulator at full speed long enough to remove all remaining air from the bear-

ing chamber. This is especially important when installing the circulator in the off-season.

Full Speed Over-Ride Feature:

To run the pump at full speed during the fast fill, start-up and purge process, press and hold the 

UP

button for 3 seconds until  “Full

Speed Override” appears on the LCD display. To return to the programmed, normal operating mode, press the 

SET

button.

“SureStart”

Feature:

In rare cases where a locked rotor may occur, the SureStart feature will activate automatically and rapidly vibrate

to unblock the rotor and continue normal operation.

6.    Programming your VT2218 circulator:

Note:

The VT2218 is factory-programmed for 

Delta-T

operating mode with a 

20°F

temperature differential setting. If this is your

desired operating mode and Delta-T setting, no programming changes are required.

CAUTION: Never run the circulator dry or permanent damage may result.
ATTENTION: Ne laissez jamais le circulateur tourner à sec, des dommages permanents peuvent en résulter.

The VT2218 has 5 Operating Modes:

     •   Delta-T - Varies speed to maintain a fixed temperature differential (factory pre-set mode).
     •   Constant Speed - 4 fixed speeds (see pump curves on previous page to select desired performance).
     •   Set Point Heat - Increases speed to increase temperature (includes Boiler Protection option).
     •   Set Point Cool - Increases speed to lower temperature.
     •   Boiler Protection - Varies speed to maintain minimum boiler return temperature.

WARNING: Use supply wires suitable for 90°C,
AVERTISSEMENT: Employer des fils d’alimentation adeqauts pour 90°C.

3.    Fill the system with tap water or a maximum of 50% propylene-glycol and water solution:

The system must be filled before operating the circulator. The bearings are water lubricated and should not be allowed to operate

dry. Filling the system will result in immediate lubrication of the bearings. It is always good practice to flush a new system of foreign

matter before starting the circulator.

CAUTION:  To  reduce  the  possibility  of  noise  transmission,  be  sure  to  add  vibration  dampeners  to  piping  when
mounting circulator to wall or floor joists.
ATTENTION: Pour réduire la possibilité de transmission de bruit, veillez à ajouter des amortisseurs de vibration à la
tuyauterie lors du montage du circulateur sur des chevêtres de mur ou de plancher.

WARNING: Risk of electric shock. To reduce the risk of electric shock, be certain that it is connected only to a prop-
erly grounded, grounding-type receptacle. Follow all local electrical and plumbing codes.
AVERTISSEMENT: Risque de choc électrique. Pour réduire le risque de choc électrique, veillez à ce qu'elle soit rac-
cordée uniquement à un réceptacle de type mise à la terre proprement mis à la terre. Respectez tous les codes de
plomberie et électriques locaux.

4.    Wiring the circulator:

Sensor Cap with Grommet

Return Sensor (R)

Supply Sensor (S)

Common

Sensor Cap with Grommet

5

Содержание 00e VT2218 Series

Страница 1: ...one Valve Control or SR Switching Relay for ON OFF operation Integral Flow Check IFC is included in carton Simply press into discharge flange if required Nut capture feature on flanges for easier fit up Whisper quiet operation BIO Barrier protects the pump from system contaminants SureStart automatic unblocking mode Optional 2 way flange model available to reduce SKU s and provide universal fit up...

Страница 2: ...E RECOMMENDED PURGING STEPS 1 CLOSE V1 PV4 V2 2 OPEN V3 3 OPEN FF VALVE 4 OPEN V2 PV4 TO PURGE LAST ZONE FIRST ZONE 3 5 CLOSE FF VALVE 6 CLOSE V2 PV4 7 REPEAT STEPS 1 TO 6 FOR EACH ADDITIONAL ZONE PURGE ZONE 1 LAST 8 OPEN V1 WHEN ALL ZONES ARE PURGED 9 ADJUST SYSTEM TO DESIRED OPERATING FILL PRESSURE IF REQUIRED ...

Страница 3: ... PURGING STEPS 1 CLOSE V1 PV4 V2 2 OPEN V3 AND ZV3 3 OPEN FF VALVE 4 OPEN V2 PV4 TO PURGE LAST ZONE FIRST ZONE 3 5 CLOSE FF VALVE 6 CLOSE V2 PV4 7 REPEAT STEPS 1 TO 6 FOR EACH ADDITIONAL ZONE PURGE ZONE 1 LAST 8 OPEN V1 WHEN ALL ZONES ARE PURGED 9 ADJUST SYSTEM TO DESIRED OPERATING FILL PRES SURE IF REQUIRED 10 MOVE ALL ZV TO CLOSED AUTOMATIC POSITION ...

Страница 4: ...rential T Set Point Heat Varies speed to maintain a fixed temperature Boiler Protection Option Decreases speed to protect boiler from low return water temperature and flue gas condensation Boiler Protection Increases speed to protect boiler from low return water temperature and flue gas condensation Heating or Chilled Water Cooling Set Point Heat Decreases speed on temperature rise Set Point Cool ...

Страница 5: ...ta T operating mode with a 20 F temperature differential setting If this is your desired operating mode and Delta T setting no programming changes are required CAUTION Never run the circulator dry or permanent damage may result ATTENTION Ne laissez jamais le circulateur tourner à sec des dommages permanents peuvent en résulter The VT2218 has 5 Operating Modes Delta T Varies speed to maintain a fix...

Страница 6: ...Start Cycle to its highest speed until target T is reached Start Cycle will dis play on the LCD screen in place of Watts If T is GREATER than target the pump will immediately go into Variable Speed operation and vary speed to maintain the target T Constant Speed Mode Speeds 1 2 3 4 default Speed 4 In Constant Speed mode the VT2218 will always start and run at the pre set Speed Level 1 through 4 On...

Страница 7: ...n ERROR CODE DESCRIPTION CORRECTIVE ACTION SENSOR 1 MISSING Supply sensor disconnected Reconnect sensor SENSOR 2 MISSING Return sensor disconnected Reconnect sensor SENSOR 1 SHORTED Bad sensor Replace sensor SENSOR 2 SHORTED Bad sensor Replace sensor AC INPUT UNDER VOLTAGE Low voltage problem Check power supply AC INPUT OVER VOLTAGE High voltage problem Check power supply LOCKED ROTOR Probable loc...

Страница 8: ...t or for any application restrictions consult the applicable Taco instruction sheets or contact Taco at 401 942 8000 Taco reserves the right to provide replacement products and parts which are substantially similar in design and functionally equivalent to the defective product or part Taco reserves the right to make changes in details of design construc tion or arrangement of materials of its prod...

Отзывы: