background image

4

ACCEPTABLE MOTOR MOUNTING POSITIONS

CASING ROTATION

To rotate the casing, remove the 4 motor screws and spin the

casing to the desired flow direction. Reattach the 4 screws

(

5

32

" allens wrench required). Be sure body gasket is seated

evenly to prevent leakage. Tighten motor screws to 34-42 in-

lbs torque.

Position electrical knockout at 6 o’clock position for best programming and LCD viewing orientation. Casing

may be rotated to change flow direction.

Across a Series

Loop System Using

Zone Valves

M

M

Return

Sensor

M

Across Multi-Zone

Radiant Manifolds

with Loop Actuators

iS

erie

s-R

B

C

A

B

C

A

M

M

M

M

M

M

M

M

Outdoor

Sensor

Boiler

Sensor

Supply
Sensor

Supply
Sensor

Return

Sensor

Boiler

Return Sensor

Boiler Protection By-Pass

Duct

Supply

Sensor

Fan Coil Fixed Temperature

Typical Variable Speed Applications:

Supply
Sensor

Boiler Return

Sensor

Mixing

Radiant Injection Set Point with Boiler Protection Option

• Delta-T

- Varies speed to maintain

a constant temperature

differential (∆T)

• Set Point Heat

- Varies speed to maintain

a fixed temperature

• Boiler Protection Option

- Decreases speed to protect

boiler from low return water

temperature and flue gas

condensation

• Boiler Protection

- Increases speed to protect boiler from low return

water temperature and flue gas condensation

• Heating or Chilled

Water Cooling

• Set Point Heat

- Decreases speed

on temperature rise

• Set Point Cool

- Increases speed on

temperature rise

1.    Location:

The circulator can be installed on the supply or return side of the boiler but for best system performance, it should always pump

away from the expansion tank. See piping diagrams in Figures No.1 and No. 2.

Integral Flow Check (IFC

®

) option

- An IFC

®

is included in the carton. If required, press IFC into machined discharge port with plunger

and o-ring facing in, until it snaps into place. Before installing, press IFC plunger to be sure it moves freely. See diagram below.

2.    Mounting position: 

Circulator must be mounted with the motor in the horizontal position. See diagrams below for acceptable motor mounting orientations.

CAUTION: Do not use flat rubber gaskets. Only use O-ring gaskets provided or leaks may result. Warranty will be void.

Содержание 00e VT2218 Series

Страница 1: ...one Valve Control or SR Switching Relay for ON OFF operation Integral Flow Check IFC is included in carton Simply press into discharge flange if required Nut capture feature on flanges for easier fit up Whisper quiet operation BIO Barrier protects the pump from system contaminants SureStart automatic unblocking mode Optional 2 way flange model available to reduce SKU s and provide universal fit up...

Страница 2: ...E RECOMMENDED PURGING STEPS 1 CLOSE V1 PV4 V2 2 OPEN V3 3 OPEN FF VALVE 4 OPEN V2 PV4 TO PURGE LAST ZONE FIRST ZONE 3 5 CLOSE FF VALVE 6 CLOSE V2 PV4 7 REPEAT STEPS 1 TO 6 FOR EACH ADDITIONAL ZONE PURGE ZONE 1 LAST 8 OPEN V1 WHEN ALL ZONES ARE PURGED 9 ADJUST SYSTEM TO DESIRED OPERATING FILL PRESSURE IF REQUIRED ...

Страница 3: ... PURGING STEPS 1 CLOSE V1 PV4 V2 2 OPEN V3 AND ZV3 3 OPEN FF VALVE 4 OPEN V2 PV4 TO PURGE LAST ZONE FIRST ZONE 3 5 CLOSE FF VALVE 6 CLOSE V2 PV4 7 REPEAT STEPS 1 TO 6 FOR EACH ADDITIONAL ZONE PURGE ZONE 1 LAST 8 OPEN V1 WHEN ALL ZONES ARE PURGED 9 ADJUST SYSTEM TO DESIRED OPERATING FILL PRES SURE IF REQUIRED 10 MOVE ALL ZV TO CLOSED AUTOMATIC POSITION ...

Страница 4: ...rential T Set Point Heat Varies speed to maintain a fixed temperature Boiler Protection Option Decreases speed to protect boiler from low return water temperature and flue gas condensation Boiler Protection Increases speed to protect boiler from low return water temperature and flue gas condensation Heating or Chilled Water Cooling Set Point Heat Decreases speed on temperature rise Set Point Cool ...

Страница 5: ...ta T operating mode with a 20 F temperature differential setting If this is your desired operating mode and Delta T setting no programming changes are required CAUTION Never run the circulator dry or permanent damage may result ATTENTION Ne laissez jamais le circulateur tourner à sec des dommages permanents peuvent en résulter The VT2218 has 5 Operating Modes Delta T Varies speed to maintain a fix...

Страница 6: ...Start Cycle to its highest speed until target T is reached Start Cycle will dis play on the LCD screen in place of Watts If T is GREATER than target the pump will immediately go into Variable Speed operation and vary speed to maintain the target T Constant Speed Mode Speeds 1 2 3 4 default Speed 4 In Constant Speed mode the VT2218 will always start and run at the pre set Speed Level 1 through 4 On...

Страница 7: ...n ERROR CODE DESCRIPTION CORRECTIVE ACTION SENSOR 1 MISSING Supply sensor disconnected Reconnect sensor SENSOR 2 MISSING Return sensor disconnected Reconnect sensor SENSOR 1 SHORTED Bad sensor Replace sensor SENSOR 2 SHORTED Bad sensor Replace sensor AC INPUT UNDER VOLTAGE Low voltage problem Check power supply AC INPUT OVER VOLTAGE High voltage problem Check power supply LOCKED ROTOR Probable loc...

Страница 8: ...t or for any application restrictions consult the applicable Taco instruction sheets or contact Taco at 401 942 8000 Taco reserves the right to provide replacement products and parts which are substantially similar in design and functionally equivalent to the defective product or part Taco reserves the right to make changes in details of design construc tion or arrangement of materials of its prod...

Отзывы: