ACCEPTABLE MOTOR MOUNTING POSITIONS AND EZ CASING ROTATION

WARNING: Use supply wires suitable for 90°C. AVERTISSEMENT: Employer des fils d’alimentation adeqauts pour 90°C.

1. Location: The circulator can be installed on the supply or return side of the boiler but for best system performance, it should always

pump away from the expansion tank. See piping diagrams in Figure 2 and Figure 3.

2. Mounting position: Circulator must be mounted with the motor in the horizontal position. See diagrams below for acceptable motor

mounting orientations.

3. Filling the system: Fill the system with  tap water or a  maximum of 50% propylene-glycol  and water solution. The system must

be filled before operating the circulator. The  bearings  are  water  lubricated  and should not be allowed to operate dry. Filling the

system will result in immediate  lubrication of  the bearings. It is  always good practice to flush a new system of foreign matter before

starting the circulator.

CAUTION: To reduce the possibility of noise transmission, be sure to add vibration dampeners to piping when mounting circulator

to wall or floor joists.

ATTENTION: Pour réduire la possibilité de transmission de bruit, veillez à ajouter des amortisseurs de vibration à la tuyauterie

lors du montage du circulateur sur des chevêtres de mur ou de plancher.

WARNING: Risk of electric shock. To reduce the risk of electric shock, be certain that it is connected only to a properly grounded,

grounding-type receptacle. Follow all local electrical and plumbing codes.

AVERTISSEMENT: Risque de choc électrique. Pour réduire le risque de choc électrique, veillez à ce qu'elle soit raccordée unique-

ment à un réceptacle de type mise à la terre proprement mis à la terre. Respectez tous les codes de plomberie et électriques

locaux.

WARNING: Disconnect power when servicing.

AVERTISSEMENT : Couper l'alimentation lors de 

l'entretien.

CAUTION: Use flexible conduit only. Not for use with rigid conduit.

ATTENTION : N'utiliser que du conduit flexible ; n’est pas fait pour

du conduit rigide.

CAUTION: Do not use flat rubber gaskets. Only use O-ring gaskets provided or leaks may result. Warranty will be void.

WARNING: SERVICING OF DOUBLE-INSULATED APPLIANCES. A double-insulated appliance is marked with one or more of the

following: The words “DOUBLE INSULATION” or “DOUBLE INSULATED” or the double insulation symbol (square within a square).

In a double-insulated appliance, two systems of insulation are provided instead of grounding. No grounding means is provided

on a double-insulated appliance, nor should a means for grounding be added. Servicing a double-insulated appliance requires

extreme care and knowledge of the system, and should be done by qualified service personnel. Replacement parts for a double-

insulated appliance must be identical to the parts they replace.

AVERTISSEMENT : ENTRETIEN DES APPAREILS À DOUBLE ISOLATION. Un appareil à double isolation est marqué avec un ou

plusieurs des éléments suivants : les mots « DOUBLE INSULATION » ou « DOUBLE INSULATED » ou le symbole de double iso-

lation (carré dans un carré). Dans un appareil à double isolation, deux systèmes d'isolation sont fournis plutôt que la mise à la

terre ; aucun moyen de mise à la terre n’est fourni ni ne doit être ajouté. L'entretien d'un appareil à double isolation exige de

grandes précautions et une connaissance approfondie du système, et doit être effectué par un technicien qualifié. Les pièces de

rechange pour un appareil à double isolation doivent être identiques aux pièces remplacées.

Integral Flow Check (IFC

®

) option - An IFC

®

is included in carton. If required, press IFC into machined discharge port with plunger and o-ring

facing in, until it snaps into place. Before installing, press IFC plunger to be sure it moves freely. See Figures: 4 & 5 above.

Always install with motor in horizontal orien-

tation.  Position  electrical  junction  box  at  9

o’clock    for  best  viewing  orientation.  Pump

casing may be rotated to change flow direc-

tion. Locate the arrow on the casing body to

determine flow direction.

To rotate the pump casing, remove the 4 motor screws.  When rotating pump casing posi-

tion, DO NOT detach motor housing from the casing. Damage to the casing O-ring and leak-

age may result. Simply spin casing to the proper flow direction desired as shown in Figure 4

and Figure 5. Reattach the 4 screws (

1

8

" allens wrench required). Be sure motor is positioned

correctly and is seated evenly to prevent leakage or damage to O-ring. Tighten motor screws

evenly to 25-38 in-lbs torque.

CAUTION: When rotating pump body position, do not detach motor housing from the casing. Damage to the casing O-ring and leak-

age may result.

Figure 4:

Figure 5:

Figure 6: 

Do not detach motor frame from pump

casing. Simply spin casing to the

proper flow direction.

Spin casing 

to change 

flow direction.

Spin 

casing 

to 

change 

flow 

direction.

X

-4-

Содержание 007e-2

Страница 1: ... protects the pump from system contaminants SureStart automatic unblocking and air purging mode Optional 2 way universal flange model for easy fit up to any flange orientation Integral Flow Check IFC included Field installed Green Mode active system monitoring and power optimization WARNING Do not use in swimming pool or spa areas Pump has not been investigated for these applications AVERTISSEMENT...

Страница 2: ...Figure 2 2 ...

Страница 3: ...NG STEPS 1 CLOSE V1 PV4 V2 2 OPEN V3 AND ZV3 3 OPEN FF VALVE 4 OPEN V2 PV4 TO PURGE LAST ZONE FIRST ZONE 3 5 CLOSE FF VALVE 6 CLOSE V2 PV4 7 REPEAT STEPS 1 TO 6 FOR EACH ADDITIONAL ZONE PURGE ZONE 1 LAST 8 OPEN V1 WHEN ALL ZONES ARE PURGED 9 ADJUST SYSTEM TO DESIRED OPERATING FILL PRESSURE IF REQUIRED 10 MOVE ALL ZV TO CLOSED AUTOMATIC POSITION Figure 3 3 ...

Страница 4: ...or the double insulation symbol square within a square In a double insulated appliance two systems of insulation are provided instead of grounding No grounding means is provided on a double insulated appliance nor should a means for grounding be added Servicing a double insulated appliance requires extreme care and knowledge of the system and should be done by qualified service personnel Replaceme...

Страница 5: ...This is especially important when installing the circu lator in the off season An orange LED will illuminate when the 007e 2 is powered on 6 Green Mode Responsive technology actively monitors system condi tions and automatically adjusts to optimize power consumption In this mode the LED changes to green CAUTION Never run the circulator dry or permanent damage may result ATTENTION Ne laissez jamais...

Страница 6: ... LED indicates the circulator is locked or sticking Disconnect and connect power supply to start the automatic release process The circulator makes 100 attempts to restart process lasts approximately 15 minutes Every restart is signalled by a short white flash of LED light If the locking is not removed through the automatic release pr ocess after 100 attempts to restart the circulator it goes into...

Страница 7: ...ws 5 per bag 0010 025 RP Integral Flow Check IFC 007 007 RP Flange gasket set Replacement Parts 2021 LIMITED WARRANTY STATEMENT Taco Inc will repair or replace without charge at the company s option any Taco High Efficiency circulator or circulator part which is proven defective under normal use within three 3 years from the date of manufacture In order to obtain service under this warranty it is ...

Страница 8: ...of pipe or closed loop hydronic heating systems Not suitable for chilled water systems Taco circulator pumps are for indoor use only employer uniquement a l interieur Acceptable for use with water or maximum of 50 water glycol solution FEATURES ECM performance equivalent to Taco s legendary 007 circulator Use with Taco SmartPlug Instant Hot Water Control for hot water when you need it Multi color ...

Страница 9: ... additives to systems using TACO equipment voids the warranty Consult factory for fluid compatibility ATTENTION L ajout de liquides à base de pétrole ou de certains additifs chimiques à des systèmes utilisant un équipement TACO annule la garantie Consultez le fabricant pour con naître la compatibilité de liquides CAUTION Installations at elevations over 5000 feet must have higher fill pressure of ...

Страница 10: ...n system Open all isolation valves Once system is filled close the fixture at the highest point in the system Close isolation valve on pump discharge Option No 1 location Open drain valve on pump discharge until all remaining air has been purged Close drain valve Operate pump until all remaining air is purged from bearing chamber 2 3 4 5 6 7 ...

Страница 11: ...Open FF valve Open V2 PV4 to purge last zone First Zone 3 Close FF Valve Close V2 PV4 Repeat steps 1 to 6 for each additional zone purge zone 1 last Open V1 when all zones are purged Adjust system to desired operating fill pressure if required 2 3 4 5 6 7 8 9 V1 V2 V3 Shut off Isolation Valve P Taco circulator with IFC installed FF Fast Fill Boiler Feed Valve PV4 Purge Valve ...

Страница 12: ... the circulator See page 3 for recommended air purging steps CAUTION To reduce the possibility of noise transmission be sure to add vibration dampeners to piping when mounting circulator to wall or floor joists ATTENTION Pour réduire la possibilité de transmission de bruit veillez à ajouter des amortisseurs de vibration à la tuyauterie lors du montage du circulateur sur des chevêtres de mur ou de ...

Страница 13: ...e CAUTION Never run the circulator dry or permanent damage may result ATTENTION Ne laissez jamais le circulateur tourner à sec des dommages permanents peuvent en résulter CAUTION Do not attempt to remove LED panel from circulator Serious damage to circulator electronics may result ATTENTION N essayez pas de retirer le panneau de LED du circulateur Des dommages sérieux à l électronique du circulate...

Страница 14: ... 7 Orange LED Green LED Proportional Pressure Mode 007e Performance Curves Normal Mode Green Mode 007e Performance Curves ...

Страница 15: ...k for impeller rotation 7 If the circulator still doesn t run it will need to be replaced FAULTS CONTROL PANEL CAUSES REMEDIES The circulator is noisy LED on Suction pressure is insufficient cavitation Increase the system suction pressure within the permissible range LED on Presence of foreign bodies in the impeller Disassemble the motor and clean the impeller Loud noises of water circulation Flas...

Страница 16: ...SOLDSEPARATELY Part Description UFS 050S 1 2 Sweat tailpiece set UFS 050T 1 2 NPT tailpiece set UFS 050P 1 2 Press tailpiece set UFS 075S 3 4 Sweat tailpiece set UFS 075T 3 4 NPT tailpiece set UFS 075P 3 4 Press tailpiece set Lead FreeShut Off FLANGE SOLDSEPARATELY Part Description SFL 050T 1 2 NPT SFL 050S 1 2 Sweat SFL 075T 3 4 NPT SFL 075S 3 4 Sweat SFL 100T 1 NPT SFL 100S 1 Sweat SFL 125T 1 1 ...

Страница 17: ... 10 NOTES ...

Страница 18: ... 11 NOTES ...

Страница 19: ...consequential damages so these limitations or exclusions may not apply to you LIMITED WARRANTY STATEMENT Taco Inc will repair or replace without charge at the company s option any Taco product which is proven defective under normal use within three 3 years from the date code In order to obtain service under this warranty it is the responsibility of the purchaser to promptly notify the local Taco s...

Отзывы: