1.  Location: 

The circulator can be installed on the supply or return side of the boiler but for best system    

 

  performance, it should always pump away from the expansion tank. See piping diagrams in Figure 2 & Figure 3.

NOTE: Two shorter 1-1/4” x 7/16” flange bolts are provided with the circulator to

use on the discharge flange to prevent interference with the circulator casing.

CAUTION: Do not use flat rubber gaskets. Only use O-ring gaskets provided or leaks may result. Warranty will be void.

2.  Mounting position: 

Circulator must be mounted with the motor in the horizontal position. See Figure 4 & Figure 5  

  below for acceptable and unacceptable motor mounting orientations. See Figure 6 for Rotating Control Cover.

 

CAUTION: To reduce the possibility of noise transmission, be sure to add vibration dampeners to piping when mounting

 

circulator to wall or floor joists. 

 

ATTENTION : Pour réduire la possibilité de transmission de bruit, veillez à ajouter des amortisseurs de vibration à

 

la tuyauterie lors du montage du circulateur sur des chevêtres de mur ou de plancher.

3.   Filling the system: 

Fill the system with tap water or a maximum of 50% propylene-glycol and water solution.    

  The system must be filled before operating the circulator. The bearings are water lubricated and should not  

 

  be allowed to operate dry. Filling the system will result in immediate lubrication of the bearings. It is always  

 

  good practice to flush a new system of foreign matter before starting the circulator.

 

WARNING: Risk of electric shock. To reduce the risk of electric shock, be certain that it is connected only to a properly

 

grounded, grounding-type receptacle. Follow all local electrical and plumbing codes.

 

AVERTISSEMENT : Risque de choc électrique. Pour réduire le risque de choc électrique, veillez à ce qu’elle soit raccordée uniquement  

 

 

à un réceptacle de type mise à la terre proprement mis à la terre. Respectez tous les codes de plomberie et électriques locaux.

 

WARNING: Use supply wires suitable for 90°C.

 

AVERTISSEMENT : Employer des fils d’alimentation adeqauts pour 90°C. 

 

WARNING: Disconnect power when servicing.

 

AVERTISSEMENT : Couper l’alimentation lors de l’entretien.

 

 

CAUTION: Use flexible conduit only. Not for use with rigid conduit.

 

ATTENTION : N’utiliser que du conduit flexible ; n’est pas fait pour du conduit rigide.

-4-

Figure 4 — Acceptable Mounting Positions

Flow

Flow

Flow

Flow

Figure 6 — Rotating Control Cover

Figure 5 — Unacceptable Mounting Positions

The 0026e is equipped 

with a symmetrical control 

cover connected to the 

pump with a ribbon cable. 

The cover can be removed, 

rotated and repositioned 

for best viewing and user 

operation. It allows the 

installer to mount the 

circulator casing in any flow 

direction, then rotate the 

cover to the upright position. 

Remove the 4 cover screws, 

rotate cover to upright 

position, reattach cover 

with 4 screws.

Содержание 0026e

Страница 1: ...ier fit up Dual electrical knockouts and removable quick connect terminal strip for easy wiring Whisper quiet operation BIO Barrier protects the pump from system contaminants SureStart automatic unblocking and air purging mode Rotatable control cover to allow any pump body orientation INSTALLATION WARNING Do not use in swimming pool or spa areas Pump has not been investigated for these application...

Страница 2: ...NE 1 ZONE 2 ZONE 3 ZONE 1 ZONE 2 ZONE 3 FC FC Optional Location FC FC ZONE 1 ZONE 2 ZONE 3 FC FC Optional Location FC FC V3 V3 V3 V2 V2 V2 P P P EXPANSION TANK V1 V1 PV4 P EXPANSION TANK BOILER EXPANSION TANK BOILER V3 V2 P V3 V2 P V3 V2 P V3 V2 P V3 V2 P V3 V2 P V1 PV4 V1 Figure 2 PREFERRED PIPING FOR CIRCULATORS ON BOILER SUPPLY PREFERRED PIPING FOR CIRCULATORS ON BOILER RETURN PREFERRED PRIMARY...

Страница 3: ...NE 3 ZONE 1 ZONE 2 ZONE 3 ZONE 1 ZONE 2 ZONE 3 KEY V1 V2 V3 SHUT OFF ISOLATION VALVE P TACO 0026e CIRCULATOR FF FAST FILL BOILER FEED VALVE PV4 PURGE VALVE ZV ZONE VALVE MOD CON BOILER EXPANSION TANK EXPANSION TANK BOILER EXPANSION TANK BOILER Figure 3 PREFERRED PIPING FOR ZONE VALVES ON BOILER SUPPLY ALTERNATE PIPING FOR ZONE VALVES ON BOILER RETURN PREFERRED PRIMARY SECONDARY PIPING FOR ZONE VAL...

Страница 4: ...he system will result in immediate lubrication of the bearings It is always good practice to flush a new system of foreign matter before starting the circulator WARNING Risk of electric shock To reduce the risk of electric shock be certain that it is connected only to a properly grounded grounding type receptacle Follow all local electrical and plumbing codes AVERTISSEMENT Risque de choc électriqu...

Страница 5: ...hecirculatorfor0 10VDCOperation See Page 9 5 Start the circulator When purging the system it is recommended to run the circulator at full speed long enough to remove all remaining air from the bearing chamber This is especially important when installing the circulator in the off season Turn the dial to the HIGH setting for maximum fixed speed A blue LED will illuminate when the 0026e is powered on...

Страница 6: ...t on back page The 0026e has 5 Operating Settings activeADAPT Automatic self adjusting proportional pressure variable speed Violet LED LOW 8 feet of head constant pressure variable speed Orange LED MEDIUM 16 feet of head constant pressure variable speed Orange LED HIGH 26 feet of head max full fixed speed Blue LED 0 10V DC Analog external input or PWM pulse width modulation input from building con...

Страница 7: ... 16 18 20 22 24 26 28 30 32 34 36 38 50 40 42 44 46 48 Flow Rate Q GPM 0 4 6 2 8 10 12 14 16 18 20 22 24 26 28 Head ft 6 0026e High Efficiency Circulator activeADAPT Range Purple LED activeADAPT activeADAPT Mode activeADAPT is an operating mode designed for constant circulation systems On this setting the circulator will sense changes in system flow and head conditions and adjust the operating cur...

Страница 8: ...gh Efficiency Circulator Maximum Curve Fixed Speed Blue LED 2 0 Flow Rate Q GPM 0 2 4 6 8 10 12 Head ft 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 14 16 18 20 22 24 26 28 HIGH Head 26 ft 0026e High Efficiency Circulator Maximum Curve Fixed Speed Blue LED Fixed Speed Mode At High setting the circulator always operates at full speed ...

Страница 9: ...or external signal wiring 3 Disconnect the connector 4 from control board 5 4 Insert the cable 6 into the cable gland M12x1 5 7 and screw it to the cover 5 Strip the wires 5 mmMIN and insert them into the connector 4 then secure them with the screws 8 6 Re connect the connector 4 to the electronic board close the cover and secure it with the screws Figure 8 External connection for 0 10V DC PWM sig...

Страница 10: ... 10V DC analog signal external input PWM Pulse Width Modulation 2V 4V 6V 8V 10V 0 140 100 120 80 40 20 60 2 0 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 Head ft 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 0 10V 0 10V Power W 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 0 Flow Rate Q GPM Flow Rate Q GPM 0026e High Efficiency Circulator 0 10V DC Perfor...

Страница 11: ...e replaced FAULTS CONTROL PANEL CAUSE S E I D E M E R S The circulator is noisy LED on Suction pressure is insufficient cavitation Increase the system suction pressure within the permissible range LED on Presence of foreign bodies in the impeller Disassemble the motor and clean the impeller Loud noises of water circulation Flashing white LED Air in the system Circulator may be air bound Vent the s...

Страница 12: ...f its products without notification TACO OFFERS THIS WARRANTY IN LIEU OF ALL OTHER EXPRESS WARRANTIES ANY WARRANTY IMPLIED BY LAW INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS IS IN EFFECT ONLY FOR THE DURA TION OF THE EXPRESS WARRANTY SET FORTH IN THE FIRST PARAGRAPH ABOVE THE ABOVE WARRANTIES ARE IN LIEU OF ALL OTHER WARRANTIES EXPRESS OR STATUTORY OR ANY OTHER WARRANTY OBLIGATION ON THE PA...

Отзывы: