background image

-4-

ACCEPTABLE MOTOR MOUNTING POSITIONS AND EASY CASING ROTATION

Figure 

Figure 

Figure 6:

Do not detach motor

from pump casing. Simply spin

casing to the proper flow direction.

Spin 

casing 

to 

change 

flow 

direction.

Spin casing 

to change 

flow direction.

4:

5:

Always install with motor in horizontal 

orientation. Position electrical junction box 

at 9 o’clock for best viewing orientation. 

Pump casing may be rotated to change flow 

direction. Locate the arrow on the casing 

body to determine flow direction.

To rotate the pump casing, remove the 4 motor screws. When rotating pump casing position, 

DO NOT detach motor housing from the casing. Damage to the casing O-ring and leakage may result. 

Simply spin casing to the proper flow direction desired as shown in Figure 4 and Figure 5. Reattach 

the 4 screws (1⁄8” allens wrench required). Be sure motor is positioned correctly and is seated evenly 

to prevent leakage or damage to O-ring. Tighten motor screws evenly to 25-38 in-lbs torque.

Integral Flow Check (IFC®) option

 - An IFC® is included in the carton. If required, press IFC into machined discharge port with plunger and 

o-ring facing in, until it snaps into place. Before installing, press IFC plunger to be sure it moves freely. See diagram above.

CAUTION: 

To reduce the possibility of noise transmission, be sure to add vibration dampeners to piping 

when mounting circulator to wall or floor joists.

ATTENTION:

 Pour réduire la possibilité de transmission de bruit, veillez à ajouter des amortisseurs de  

vibration à la tuyauterie lors du montage du circulateur sur des chevêtres de mur ou de plancher.

5.  Filling the system: 

The system must be filled before operating the circulator. The bearings are water lubricated and should not be  

  allowed to operate dry. Filling the system will result in immediate lubrication of the bearings. It is always good practice to flush a new  

  system of foreign matter before startin the circulator.

WARNING:

 Risk of electric shock. To reduce the risk of electric shock, be certain that it is connected only to a properly 

grounded, grounding-type receptacle. Follow all local electrical and plumbing codes.

AVERTISSEMENT: 

Risque de choc électrique. Pour réduire le risque de choc électrique, veillez à ce qu’elle soit raccordée 

uniquement à un réceptacle de type mise à la terre proprement mis à la terre. Respectez tous les codes de plomberie et 

électriques locaux.

WARNING: 

Use supply wires suitable for 90°C. 

AVERTISSEMENT: 

Employer des fils d’alimentation adeqauts pour 90°C.

WARNING: 

Disconnect power when servicing. 

CAUTION: 

Use flexible conduit only. Not for use with rigid conduit.

WARNING:

 SERVICING OF DOUBLE-INSULATED APPLIANCES. A double-insulated appliance is marked with one or more of the 

following: The words “DOUBLE INSULATION” or “DOUBLE INSULATED” or the double insulation symbol (square within a square). 

In a double-insulated appliance, two systems of insulation are provided instead of grounding. No grounding means is provided 

on a double-insulated appliance, nor should a means for grounding be added. Servicing a double-insulated appliance requires 

extreme care and knowledge of the system, and should be done by qualified service personnel. Replacement parts for a dou-

ble-insulated appliance must be identical to the parts they replace.

Содержание 0018e-SF4

Страница 1: ...tivation Proportional pressure TRV Panel Radiator variable speed 2 variable pressure differential settings Med or High Constant pressure ZV Zone Valve variable speed 2 constant pressure differential settings Med or High Fixed speed ZONE CIRC zoning with circulators infinitely adjustable MIN MAX settings 4 operating modes in 0018eTM Mobile App activation Fixed Speed infinitely adjustable MIN MAX se...

Страница 2: ...lité de liquides CAUTION Installations at elevations over 5000 feet must have higher fill pressure of 20 psi minimum to prevent pump cavitation and flashing Premature failure may result Adjust expansion tank pressure to equal fill pressure A larger size expansion tank may be required ATTENTION Des installations à des altitudes de plus de 1600 mètres doivent présenter une pression de remplissage pl...

Страница 3: ... system piping The circulator flanges incorporate a nut grabber feature for easier installation 4 Union Model Install the union tailpiece fitting set sold separately best suited for your system piping See union fitting options chart on the back cover Install circulator by attaching pump casing to each union tailpiece fitting Tighten union nut onto circulator threading being careful not to overtigh...

Страница 4: ...tage du circulateur sur des chevêtres de mur ou de plancher 5 Filling the system The system must be filled before operating the circulator The bearings are water lubricated and should not be allowed to operate dry Filling the system will result in immediate lubrication of the bearings It is always good practice to flush a new system of foreign matter before startin the circulator WARNING Risk of e...

Страница 5: ...ection The 0018e is a double insulated circulator No grounding wire is necessary 7 Start the circulator When purging the system it is recommended to run the circulator at manual full speed operation long enough to remove remaining air from the bearing chamber To do this turn the dial clockwise to the ZONE CIRC MAX position This is especially important when installing the circulator in the off seas...

Страница 6: ...018e_UserManual 1 Search for Taco 0018e ECM Circulator mobile app within the App Store or Google Play on your mobile device 2 Download the Taco 0018e ECM Circulator mobile app for free and install it on your mobile device 3 Once complete you are able to start using the app Additional operating instructions can be found on the app itself Turn the selector dial counter clockwise to the Bluetooth set...

Страница 7: ...resents full operating range Blue LED min max ZONE CIRC FIXED SPEED MODE 0018e Performance Curves In TRV Panel Radiator Proportional pressure mode the circulator maintains a proportional pressure differential Δp v as heating load increases or decreases Flow will change in relationship to the change in pressure differential Selection options are Medium or High If unsure on proper setting select Med...

Страница 8: ...nt supply voltage Verify that the power supply matches the data on the name plate Building does not get warm LED on The circulator performance is too low Increase the suction head Increase speed or P setting 7 Troubleshooting the error codes Listed below are potential diagnostic error codes which will appear on the LED display in case of a malfunction Unlocking Procedure A red light in the LED ind...

Страница 9: ... SFL 050T 1 2 NPT SFL 050S 1 2 Sweat SFL 075T 3 4 NPT SFL 075S 3 4 Sweat SFL 100T 1 NPT SFL 100S 1 Sweat SFL 125T 1 1 4 NPT SFL 125S 1 1 4 Sweat SFL 150T 1 1 2 NPT SFL 150S 1 1 2 Sweat SPEED Taco Grundfos Wilo Xylem B G Armstrong Minimum 003 006 Alpha 15 55 Low Compass 1 Medium 007 008 0015 Low 0015 Med UP 15 42 UPS 15 58 Low UPS 15 58 Med Alpha 15 55 Med Star S 21 1 Star S 21 2 NBF 1 2 Astro 230 ...

Страница 10: ...nada applicables aux appareils radio exempts de licence L exploitation est autorisée aux deux conditions suivantes 1 l appareil ne doit pas produire de brouillage et 2 l utilisateur de l appareil doit accepter tout brouillage radioélectrique subi même si le brouillage est susceptible d en compromettre le fonctionnement Under Industry Canada regulations this radio transmitter may only operate using...

Страница 11: ... 11 NOTES ...

Страница 12: ...consequential damages so these limitations or exclusions may not apply to you LIMITED WARRANTY STATEMENT Taco Inc will repair or replace without charge at the company s option any Taco product which is proven defective under normal use within three 3 years from the date code In order to obtain service under this warranty it is the responsibility of the purchaser to promptly notify the local Taco s...

Отзывы: