36
[5]Changing Operation Mode
[EXCESS] or [FORCED] charging can be selected for the
charging process.
Select a value between 0 to 10 for DISCHARGE1 THRESHOLD
and DISCHARGE2
THRESHOLD.
The setting value is the target level.
The target level is for the purchasing power kW.
The Remote Control Panel shows different kW because it is set
less than the target level.
The DEPTH OF DISCHARGE (DOD) value changes between 0
and 5 by pressing [CHANGE].
Press [SETUP] on the home screen.
1
Select “OPERATION MODE” using [
↓
] and press [ENTER].
The operating mode changes in the following order of MAX
POWER EXPORT Mode, ECONOMY Mode, HOME BACKUP
Mode and PEAK CUT Mode by pressing [CHANGE] from the
OPERATION MODE menu.*
The parameter changes between 0:00 and 23:00 by pressing
[CHANGE] while BATTERY CHARGE START/FINISH or BATTERY
DISCHARGE1 START/FINISH or BATTERY DISCHARGE2
START/FINISH is selected.
2
3
Select "SAVE" and press [ENTER].
4
MODE
Propriety of setting in each mode are as follows.
CHARGE
TIME
MAX POWER EXPORT
〇
×
×
〇
DISCHARGE1
TIME
〇
×
×
〇
DISCHARGE1
THRESHOLD
×
×
×
〇
DISCHARGE2
THRESHOLD
×
×
×
〇
DEPTH OF
DISCHARGE
〇
〇
×
〇
DISCHARGE2
TIME
×
×
×
〇
CHARGE
PROCEDURE
×
×
×
〇
ECONOMY
HOME BACKUP
PEAK CUT
* EXT-CTL Mode may be displayed depending on the setting at the installation, do not set EXT-CTL Mode.
Settings