Selector switch
39
Selector switch
The selector switch has 16 different positions. Each position has two functions (e.g. switch
position
diff2 / T2
). The value, which is nearer to the selector switch, will be displayed without
pressing of the yellow key “
Eingabe
” (e.g.
T2
). By pressing the yellow key “
Eingabe
” (= in-
put) the second value will be displayed (e.g.
diff2
). The blue keys “
ab
” (= down) resp. “
auf
”
(= up) change the settings. Holding the key pressed increases resp. decreases constantly the
value, short taps cause a change of 1.
The interior legend (e.g.
T5
= displayed temperature of sensor 5) has
no direct connection
to the outside legend (e.g.
min1
= temperature limit of the tank). E.g. in diagram 0 the sensor
T5
has connection with
min1
, but
T3
corresponds with
max1
.
T1 - T6
Actual temperature of the sensors
A1 - A4
State of the outputs („Ein“ = ON, „Aut“ = automatic mode, „Aus“ = OFF)
The changing occurs by pressing the blue keys
ab/auf
(down/up).
diff1 - 4
Difference temperatures, setting range: 0 to 99 K
min1, 2
Minimal thresholds, setting range: 0 to 150 °C
max1 - 4
Limit of storage temperature, setting range: 0 to 150 °C
F1e - F3e
Switch-on time of time windows 1 to 3
F1a - F3a
Switch-off time of time windows 1 to 3
Uhr
Time (resolution: 10 minutes), setting by the blue keys
ab
/
auf
(down/up).
F>A
Assignment menu (which time window interacts with which output)
Setting: see chapter „Assignment of the time windows”
Prog
Selection of the program number according to the chosen diagram. The pro-
gram number defines the
basic function
of the controller and is the
most im-
portant input
. Setting by the blue keys
ab
/
auf
(down/up)
Vorr
Priority menu. Assignment of priority 0 to 4 to the outputs: 0 = no priority, 1 =
highest, 4 = lowest priority; setting: see chapter “Assignment of priority”
Vers
Actual software version (important for enquiry calls); it cannot be changed.
Menü
Main menu for access to the sub menus of the controller