background image

4

©

 

Copyright 2008 TAC All Rights Reserved.

F-25906-2

Figure-3 Wiring Diagram for TP-1611 and TP-1616.

Figure-4 Function Diagram for TP-1611 and TP-1616.

TP-1611, TP-1616

Remote Sensor 11

Remote Sensor 12

Heating 2

24 Vac Supply 4

Fan Medium 21

Fan Supply 19

Fan High 22

N

L

1

2

Fan Low 20

Cooling 6

24 Vac Supply 1

AT-1005

Remote

Sensor

S2 

S1

24 Vac

Supply

3

1   Switch 1, Fan On/Off.

2   Switch 2, Fan Speed.

3   Adjustable Dead Band, 0.5 to 7.5 °C (0.9 to 13.5 °F).

4   0 to 10Vdc Analog Output.

MP-55XX

or

MF-631X3

Actuator

4

4

MP-55XX

or

MF-631X3

Actuator

Temp.

Output
Voltage

10 Vdc

Heating

Cooling

Setpoint

(Nominal Value)

Output Voltage

Temperature

Dead
Band

(Adjustable)

Propo

rtional Cooling

Proportional Heating

Proportional Band

1.5 °C (2.7 °F)

Proportional Band

1.5 °C (2.7 °F)

Содержание TP-1601

Страница 1: ...ures 24 Vac or Vdc operation Fixed throttling range see Table 1 6 to 9 and 0 to 10 volt analog output Fast easy installation Celsuis and Fahrenheit versions available Low profile styling International...

Страница 2: ...d Dimensions Refer to Figure 5 Locations NEMA Type 1 indoor only Table 1 Model Chart for TP 16XX Series Thermostats ACCESSORIES AT 1005 Remote Sensor TOOLS Digital Volt ohm Meter DVM Appropriate drill...

Страница 3: ...2 Function Diagram for TP 1601 TP 1601 Actuator Supply 2 Com 4 Fan Medium 21 Fan Supply 19 Fan High 22 N L 1 2 Fan Low 20 Cooling 6 20 Vdc Supply 1 S2 S1 MP 52XX Actuator Black Black Yellow Red Blue G...

Страница 4: ...6 24 Vac Supply 1 AT 1005 Remote Sensor S2 S1 24 Vac Supply 3 1 Switch 1 Fan On Off 2 Switch 2 Fan Speed 3 Adjustable Dead Band 0 5 to 7 5 C 0 9 to 13 5 F 4 0 to 10Vdc Analog Output MP 55XX or MF 631...

Страница 5: ...ox for a thermostat orient the junction box horizontally if possible C A U T I O N Do not exceed the ratings of the thermostat Doing so may result in damage to the thermo stat Do not locate the thermo...

Страница 6: ...driver to expose the screw which secures the housing to the thermostat mechanism 2 Remove the attaching screw and separate the housing from the thermostat mechanism 3 Extend from the wall the wires th...

Страница 7: ...heating circuit is activated if applicable 2 Gradually turn the temperature setpoint dial lower to a temperature that is below ambi ent Verify that the cooing circuit is activated ADJUSTMENTS No fiel...

Страница 8: ...marks and registered trademarks are the property of their respective owners Information contained within this document is subject to change without notice F 25906 2 www tac com TAC 1354 Clifford Avenu...

Отзывы: