background image

2

©

 

Copyright 2008 TAC All Rights Reserved.

F-25906-2

SPECIFICATIONS

Setpoint Dial Range:

 55 to 85 °F or 5 to 30 °C.

 

Refer to Table-1  for scale.

Operating Voltage: 

 24 Vac, 50/60 Hz.

Power Consumption:

 0.35 Watts at 24V.

Fan Power Supply: 

24 to 240 Vac, 50/60 Hz.

Sensing Element: 

Electronic sensor.

Dead Band Tolerance: 

Adjustable, 0.5 to 7.5 °C ( 0.9 to 13.5 °F)

Load: 

3 mA (max.)

Analog Output: 

Refer to Table-1 .

Amp Ratings, 

Refer to Table-1 .

Connections: 

 

Coded screw terminals.

Cover: 

White plastic.

Mounting: 

Directly to wall surface or onto flush junction box. Mounting plate may be 

required.

Dimensions: 

Refer to Figure-5 .

Locations: 

NEMA Type 1 indoor only.

Table-1

Model Chart for TP-16XX Series Thermostats.

ACCESSORIES

AT-1005

Remote Sensor

TOOLS

Digital Volt-ohm Meter (DVM)
Appropriate drill and drill bit for mounting screws
Appropriate screwdrivers for mounting screws and terminal connections

Model

Number

Description

Thermostat

Scale

Range

Electrical Switches and Ratings

Analog Output

On-Off
Switch

Fan Speed

Switch

Switching Current at 250Vac

Resistive (Inductive) Amps

Span

Throttling

Range

TP-1601 

a

Cooling Only

Thermostat

5 to 30 °C

X

X

N/A

6 to 9 Vdc

1 °C

(1.8 °F)

TP-1611 

b

Heating & Cooling

Thermostat

5 to 30 °C

X

X

6 (3)

0 to 10 Vdc

1.5 °C

(2.7 °F)

TP-1616 

b

55 to 85 °F

X

X

a

For use with MP-52XX actuators.

b

For use with 0 to 10 Vdc input actuators.

Содержание TP-1601

Страница 1: ...ures 24 Vac or Vdc operation Fixed throttling range see Table 1 6 to 9 and 0 to 10 volt analog output Fast easy installation Celsuis and Fahrenheit versions available Low profile styling International...

Страница 2: ...d Dimensions Refer to Figure 5 Locations NEMA Type 1 indoor only Table 1 Model Chart for TP 16XX Series Thermostats ACCESSORIES AT 1005 Remote Sensor TOOLS Digital Volt ohm Meter DVM Appropriate drill...

Страница 3: ...2 Function Diagram for TP 1601 TP 1601 Actuator Supply 2 Com 4 Fan Medium 21 Fan Supply 19 Fan High 22 N L 1 2 Fan Low 20 Cooling 6 20 Vdc Supply 1 S2 S1 MP 52XX Actuator Black Black Yellow Red Blue G...

Страница 4: ...6 24 Vac Supply 1 AT 1005 Remote Sensor S2 S1 24 Vac Supply 3 1 Switch 1 Fan On Off 2 Switch 2 Fan Speed 3 Adjustable Dead Band 0 5 to 7 5 C 0 9 to 13 5 F 4 0 to 10Vdc Analog Output MP 55XX or MF 631...

Страница 5: ...ox for a thermostat orient the junction box horizontally if possible C A U T I O N Do not exceed the ratings of the thermostat Doing so may result in damage to the thermo stat Do not locate the thermo...

Страница 6: ...driver to expose the screw which secures the housing to the thermostat mechanism 2 Remove the attaching screw and separate the housing from the thermostat mechanism 3 Extend from the wall the wires th...

Страница 7: ...heating circuit is activated if applicable 2 Gradually turn the temperature setpoint dial lower to a temperature that is below ambi ent Verify that the cooing circuit is activated ADJUSTMENTS No fiel...

Страница 8: ...marks and registered trademarks are the property of their respective owners Information contained within this document is subject to change without notice F 25906 2 www tac com TAC 1354 Clifford Avenu...

Отзывы: