2
©
Copyright 2008 TAC All Rights Reserved.
F-25906-2
SPECIFICATIONS
Setpoint Dial Range:
55 to 85 °F or 5 to 30 °C.
Refer to Table-1 for scale.
Operating Voltage:
24 Vac, 50/60 Hz.
Power Consumption:
0.35 Watts at 24V.
Fan Power Supply:
24 to 240 Vac, 50/60 Hz.
Sensing Element:
Electronic sensor.
Dead Band Tolerance:
Adjustable, 0.5 to 7.5 °C ( 0.9 to 13.5 °F)
Load:
3 mA (max.)
Analog Output:
Refer to Table-1 .
Amp Ratings,
Refer to Table-1 .
Connections:
Coded screw terminals.
Cover:
White plastic.
Mounting:
Directly to wall surface or onto flush junction box. Mounting plate may be
required.
Dimensions:
Refer to Figure-5 .
Locations:
NEMA Type 1 indoor only.
Table-1
Model Chart for TP-16XX Series Thermostats.
ACCESSORIES
AT-1005
Remote Sensor
TOOLS
Digital Volt-ohm Meter (DVM)
Appropriate drill and drill bit for mounting screws
Appropriate screwdrivers for mounting screws and terminal connections
Model
Number
Description
Thermostat
Scale
Range
Electrical Switches and Ratings
Analog Output
On-Off
Switch
Fan Speed
Switch
Switching Current at 250Vac
Resistive (Inductive) Amps
Span
Throttling
Range
TP-1601
a
Cooling Only
Thermostat
5 to 30 °C
X
X
N/A
6 to 9 Vdc
1 °C
(1.8 °F)
TP-1611
b
Heating & Cooling
Thermostat
5 to 30 °C
X
X
6 (3)
0 to 10 Vdc
1.5 °C
(2.7 °F)
TP-1616
b
55 to 85 °F
X
X
a
For use with MP-52XX actuators.
b
For use with 0 to 10 Vdc input actuators.