background image

F-24853-4

©

 

Copyright 2006 TAC All Rights Reserved.

5

Table-2 illustrates the numbering scheme and software 
assignments of the eight 0-11 Vdc analog inputs. When 
making these assignments, the first entry is the option slot 
number on the connection MSC-MPC controller and the 
second entry is the number of the analog input being used.

For example, when plugged into option slot number 2, analog 
input number 1 has an assignment of AI 21.

Table-2 Software Assignments for 0-11 Vdc Analog 

Input.

INPNT = AI# (as shown below) /NOT

Calculating SCALE and OFSET Using MOCALC

MOCALC comes standard with the DOS Configuration Tool 
and is used to determine the proper values for SCALE and 
OFSET when provided with the desired values to be displayed 
from given input parameters. MOCALC is typically used to 
calibrate the display in engineering units in accordance with 
measurements taken. In some cases it can be used to correct 
for tolerance errors in input or output readings.

To use MOCALC, several parameters must be measured 
prior to running the program. First, the physical property to be 
measured or controlled is sampled near the high end of its 
scale and the corresponding bit value is recorded.Then 
another reading is taken with the property at the low end of its 
scale and the bit value displayed by the system is again 
recorded. Once this information is determined, the MOCALC 
program is able to calculate the appropriate values for SCALE 
and OFSET. Note that the characteristics of the variable must 
be linear to use MOCALC. 

The sample calculations below are for a Belimo SM24 
Actuator with the P500 feedback option that will be used to 
control a valve from 0 to 100 percent open.

For the point to be calibrated, set OFSET = 0 and SCALE = 
4096.

With the feedback wired, drive the actuator/valve fully open 
(100%). Record the measured bit value displayed by the 
system for this point. This is the “bit high value”. Next, drive 
the actuator/valve fully closed (0%). Record the measured bit 
value again. This is the “bit low value”.

You are now ready to execute the MOCALC program.

1. From the C:\XCM directory, type MOCALC and press 

ENTER.

2. At the enter number prompt, type 1 to select Formulas for 

Scale and OFSET.

3. At the Enter Number prompt, type 6 to select Formulas for 

Bit High...Bit Low.

The program prompts you for the device range high and range 
low values. These values are the range of the points display, 
which in this case is from 0 to 100 percent (open). You will 
also need to enter the recorded bit values when the actuator 
was driven to these two positions. MOCALC will then compute 
the proper SCALE and OFSET for the point to display linearly 
across the actuator’s travel range.

Please Enter Device Range High Value

Number:

100

Please Enter Device Range Low Value 

Number:

0

Please Enter Recorded BIT HIGH Value 

Number:

3298

Please Enter Recorded BIT LOW Value

Number:

517

SCALE:

147.28

OFSET:

-18.59

In the example above, the desired display range for the 
actuator is 0 to 100 (percent open). The corresponding low 
and high bit values were recorded as 517 and 3298, 
respectively. 

MOCALC determined SCALE to be 147.28 and OFSET to be 
-18.59.

The formulas used by MOCALC are as follows:

SCALE = 4096 * (RANHI - RANLO)

(BITHI - BITLO)

OFSET = RANLO (SCALE * BITLO)

4096

Option Slot # On The MSC-MPC Controller

AI#

1

2

3

4

AI1

AI 11

AI 21

AI 31

AI 41

AI2

AI 12

AI 22

AI 32

AI 42

AI3

AI 13

AI 23

AI 33

AI 43

AI4

AI 14

AI 24

AI 34

AI 44

AI5

AI 15

AI 25

AI 35

AI 45

AI6

AI 16

AI 26

AI 36

AI 46

AI7

AI 17

AI 27

AI 37

AI 47

AI8

AI 18

AI 28

AI 38

AI 48

SCALE

OFSET

CVTYP

11

0

LIN 1

Содержание MPC-8AI

Страница 1: ...C to 115 C 0 06 C resolution 0 11 Vdc 0 005 volt resolution 4 20 mA 0 01 mA resolution Contact Inputs Used for status monitoring of dry contacts Operating Environment 32 to 122 F 0 to 50 C 5 85 RH non...

Страница 2: ...2 Copyright 2006 TAC All Rights Reserved F 24853 4 Figure 1 TAC MicroSmart MPC 8AI Analog Input Module...

Страница 3: ...rams and software assignments are provided below Note When installing the MPC 8AI be sure that the controller is fully seated to the backplate before and after the backplate is fastened to the enclosu...

Страница 4: ...g the element OFSET simply subtract 77 from the value given in the table for OFSET 0 11 Vdc Analog Inputs When configured as a voltage sensor input the universal analog input measures between 0 and 11...

Страница 5: ...percent open For the point to be calibrated set OFSET 0 and SCALE 4096 With the feedback wired drive the actuator valve fully open 100 Record the measured bit value displayed by the system for this p...

Страница 6: ...rmally closed contact input excluding pulse inputs This input utilizes a 1K ohm 1 1 4 watt supervision resistor installed with the input device The device is terminated to the appropriate AI connector...

Страница 7: ...e assignment required for the corresponding hardware address of the selected contact input is shown in Table 5 below Table 5 Assignments for AIs used as Normally Closed Contact Inputs INPNT AI as show...

Страница 8: ...marks and registered trademarks are the property of their respective owners Information contained within this document is subject to change without notice F 24853 4 www tac com TAC 1354 Clifford Avenu...

Отзывы: