9 (10)
DIM119E
F-27506-1
VB-73XX Three Way Globe Valve, Forta Floating Control Setup Reference
Forta Floating Control Auxiliary Switch (Optional) Setup Reference
Valve Type
Valve position with
D2 powered
Switch 1 Switch 2 Switch 7
Power up
Position
Power to D2
input terminal
Feedback
signal
Power to D1
input terminal
Feedback
signal
VB-731x stem up
open B to AB
OFF
ON
OFF
Retract Full
Flow B to AB
Retract Full
Flow B to AB
2 vdc
Extend No Flow
B to AB
10 vdc
VB-731x stem down
closed B to AB
OFF
ON
ON
Retract Full
Flow B to AB
Extend No Flow
B to AB
10 vdc
Retract Full Flow
B to AB
2 vdc
VB-731x stem up
open B to AB
ON
ON
OFF
Extend Full
Flow A to AB
Extend No Flow
B to AB
2 vdc
Retract Full Flow
B to AB
10 vdc
VB-731x stem down
closed B to AB
ON
ON
ON
Extend Full
Flow A to AB
Retract Full Flow
B to AB
10 vdc
Extend No Flow
B to AB
2 vdc
VB-732x stem up flow
B to AB
OFF
ON
OFF
Retract Full
Flow B to AB
Retract Full Flow
B to AB
2 vdc
Extend No Flow
B to AB
10 vdc
VB-732x stem down
flow B to A
OFF
ON
ON
Retract Full
Flow B to AB
Extend No Flow
B to AB
10 vdc
Retract Full Flow
B to AB
2 vdc
VB-732x stem up flow
B to AB
ON
ON
OFF
Extend Full
Flow B to A
Extend No Flow
B to AB
2 vdc
Retract Full Flow
B to AB
10 vdc
VB-732x stem down
flow B to A
ON
ON
ON
Extend Full
Flow B to A
Retract Full Flow
B to AB
10 vdc
Extend No Flow
B to AB
2 vdc
Table 5
VB-73x3 3 way valves
Forta M400A / M800A Base Floating Configuration
Program Switch Position
Desired Valve Operations
Programming Notes:
The above switch positions are the base programming configurations, in the base configurations all other switches
should be
switched off
. Once the base programming configuration has been set up you may wish to add additional programming
features and functions that are listed below.
Switch 1
CLOSE
OPEN
Switch 2
CLOSE
OPEN
% of Valve Travel
0
10
20
30
40
50
60
70
80
90
100
Table 6
Auxiliary Switches
2 - SPDT
Closed
Open
Closed
Open
Closed
Open
Closed
Open
KC1 - K1
X
X
X
X
KC1 - K2
X
X
X
X
KC2 - K3
X
X
X
X
KC2 - K4
X
X
X
X
Floating Control
(contact made)
D1 action
D2 action
Note: This table shows the auxiliary switch action based on the dip switch 1 and 7 settings. You should program the dip switches on the
actuator based on the application requirements, once programmed review this chart to determine the action of the auxiliary switches and wire the
switches accordingly. IF YOU CHANGE EITHER DIP SWITCH 1 or 7 TO GET A DIFFERENT CONTACT CLOSURE YOU WILL CHANGE THE
EXTEND/RETRACT MOVEMENT OF THE ACTUATOR.
Extends
Extends
Retracts
Retracts
Note
: With power to the actuator off, Auxiliary Switches are made KC1 to K1 and KC2 to K3. Upon power up
switches will make as shown above after auto start up calibration.
Retracts
Retracts
Extends
Extends
Program Switches 1off, 7off
Program Switches 1on, 7on
Program Switches 1off, 7on
Program Switches 1on, 7off
Retracted
Extended
Retracted
Extended
Powered
Powered
Powered
Powered
Example D
Floating Control
Program Switch 1off
Program Switch 1on
Program Switch 1off
Program Switch 1on
Optional Auxiliary Switch Function (S2)
Example A
Example B
Example C
With the actuator powered and being controlled by the input signal the optional auxiliary switches only transfer contacts as
follows, driving from full retract to full extend the auxiliary contacts transfer when the actuator is about 95% of full extend travel.
When the actuator drives from full extend to full retract the contacts will transfer when the actuator is about 95% of full retract
travel.