t.a.c. Forta M400A Скачать руководство пользователя страница 6

DIM119E

6 (10)

F-27506-1

PROGRAM  SWITCH  SETTINGS

Figure 8

Function in the

Description

“OFF” pos.

“ON” position

1

Retract

Extend (see sw7)

Valve closing screw direction

2

Proportional

Floating

Control Mode

3

Sequence

Sequence control

4

0-10 V

2-10 V

Input Voltage range

5

0-5 V, 2-6 V

5-10 V, 6-10 V

Part of voltage range

6

60 s

300 s

Running time (Floating control only)

7

Normal

Inverted (see SW 1)

Direction  of  movement

8

Normal

Linear/Logarithmic

Valve characteristic

9

Operation

Stroke position

Input signal/stroke calibration

adjust (mom.)

(*) There are nine switches in a row on the

circuit board. The factory shipped
default switch positions are all “OFF.”

1

Valve Closing Screw

Upon power up with switch 1 OFF the
actuator will fully retract before the input
control signal takes control. If switch 1 is
ON the actuator will fully extend before
the input control signal takes over. This
switch will change the proportional or
floating input signal to direct or reverse
action similar to switch 7

2

Control signal—Prop / Float

TAC Forta can either be controlled by a
Proportional signal (SW2 OFF), or a
floating signal (SW2 ON)

3

Sequence or parallel control—
– – – / SEQ

With sequence (or parallel) control (SEQ),
two actuators/valves can be controlled by
only one proportional control signal.

Switch 2 must be OFF, switch 3 must be
ON and switch 5 will configure the range.

Note if sequence or parallel control is not
used switch 3 must be in the off position

4

Voltage range

You can choose whether to use the control
signal voltage range 0-10Vdc (SW4 off)

or 2-10Vdc (SW4 on).

5

Part of voltage range—
0-5, 2-6 / 5-10, 6-10

Allows you to select 0-5/2-6v or 5-10/6-
10v working range.

If SW5 is OFF the 0-5/2-6v range is
selected, If SW5 is ON the 5-10/6-10v is
selected

Note switch 5 is only active if switch 2 is
OFF and switch 3 is ON.

6

If switch 2 is ON SW6 controls run time,
SW 6 OFF equals 60 sec, ON equals 300
sec run time.

7

Direction of movement—
NORM / INV

Changes the proportional or floating input
signal to direct or reverse action similar to
switch 1

8

Linearization

SW 8 OFF normal
SW8 ON Linear electronic control
The motorized valve characteristics can
be modified. If you wish for the
characteristics to be affected, the
setting LIN/LG will make the characteristics
of an equally modified percentage (EQM)
valve almost linear.

On the other hand, with LIN/LG setting a
motorized valve equipped with a linear
valve will operate with ”Quick open
characteristics.”

Note!

 For the actuator to register

new settings of the switches, the
supply voltage must be removed by
cutting power to the actuator or
lowering the manual override lever,
then change any of switches one
through 8 as required and then
restore power to the actuator or raise
the manual override level.

Please refer to illustration on page 2,
figure 2.

Note: After mounting the actuator on a
valve, dipswitch 9  must be momentarily
switched off to on to off with the actuator
powered for proper actuator valve
stroke calibration.

9 (OP/ADJ)

Input Signal/Stroke calibration SW9 OFF
normal operation

This switch is only used to calibrate the
input control signal and the valve stroke.
To calibrate, power to the actuator must
be on, momentarily turn switch 9 on and
then off. The actuator will automatically
match the control input signal to the valve
stroke (switch 9 must be left in the off
position for normal operation).

*See note below!

Refer to the following selection guides for selection of the available Actuator Valve combinations
VB-7xxx Selection Guide F-27490 or VB-8xxx/VB-9xxx Selection Guide F-27491 before using the
tables on pages 7, 8 and 9

ACTUATOR  VALVE  SELECTION

Содержание Forta M400A

Страница 1: ...throughout stroke Easy One Touch input signal stroke calibration APPLICABLE LITERATURE Forta VB 7xxx Selection Guide F 27490 Forta VB 8xxx VB 9xxx Selection Guide F 27491 AV 811 Linkage VB 7xxx F 27442 AV 812 Linkage VB 8xxx VB 9xxx F 27443 AV 800 Series Linkage Adapters for Competitors Valves F 27470 Stroke 3 8 to 2 9 52mm Stroke Timing Floating 60 or 300 sec selectable Proportional 15 sec 1 2 st...

Страница 2: ...h manual override lowered MAN For normal operating the handle must be raised AUTO Position feedback M400A M800A actuators are equipped with a 2 10 vdc position feedback FUNCTION DIMENSIONS The actuator may be mounted horizontally vertically and in any position in between but not upside down see figure 3 Forta M400A M800A actuators mount directly on two and three way VB 7xxx globe valves using the ...

Страница 3: ...led with 3 conductors with very long lengths floating control where control signal reference is connected to G the motor current of the actuator will cause varying voltage loss in the cable and thus in the reference level Forta which has a highly sensitive control signal input will detect the varying signal and follow it which makes it difficult for the actuator to find a stable position Cable Len...

Страница 4: ...DIM119E 4 10 F 27506 1 WIRING EXAMPLES Figure 6 ...

Страница 5: ...5 10 DIM119E F 27506 1 Figure 7 ...

Страница 6: ...If SW5 is ON the 5 10 6 10v is selected Note switch 5 is only active if switch 2 is OFF and switch 3 is ON 6 If switch 2 is ON SW6 controls run time SW 6 OFF equals 60 sec ON equals 300 sec run time 7 Direction of movement NORM INV Changes the proportional or floating input signal to direct or reverse action similar to switch 1 8 Linearization SW 8 OFF normal SW8 ON Linear electronic control The m...

Страница 7: ...put RA Full open full flow 2vdc output Full closed no flow 10vdc output VB 721x stem down closed OFF OFF ON Retract Full Flow Extend No Flow 10 vdc No Flow 2 vdc Full Flow Valve Type Valve position at low signal input Switch 1 Switch 2 Switch 7 Power up Position Low end of signal input range Feedback signal action port B Table 2 VB 73x3 3 way valves Forta M400A M800A Base Proportional Configuratio...

Страница 8: ...tem down closed OFF ON ON Retract Full Flow Extend No Flow Switch 1 CLOSE OPEN Switch 2 CLOSE OPEN of Valve Travel 0 10 20 30 40 50 60 70 80 90 100 Table 3 Auxiliary Switches 2 SPDT Closed Open Closed Open Closed Open Closed Open KC1 K1 X X X X KC1 K2 X X X X KC2 K3 X X X X KC2 K4 X X X X Proportional Control Action Low Signal Input High Signal Input Optional Auxiliary Switch Function S2 Example A...

Страница 9: ...e the base programming configuration has been set up you may wish to add additional programming features and functions that are listed below Switch 1 CLOSE OPEN Switch 2 CLOSE OPEN of Valve Travel 0 10 20 30 40 50 60 70 80 90 100 Table 6 Auxiliary Switches 2 SPDT Closed Open Closed Open Closed Open Closed Open KC1 K1 X X X X KC1 K2 X X X X KC2 K3 X X X X KC2 K4 X X X X Floating Control contact mad...

Страница 10: ... class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in residential installations This equipment generates uses and can rediate radio frequency energy and may cause harmful interference if not installed and used in acordance with the instructions Even when instructions are followed there is no guarantee...

Отзывы: