DIM119E
8 (10)
F-27506-1
VB-72XX Two Way Globe Valve, Forta Floating Control Setup Reference
Forta Proportional Control Auxiliary Switch (Optional) Setup Reference
Valve Type
Valve
position with
D2 powered
Switch 1 Switch 2 Switch 7
Power up
Position
Power to
D2 input
terminal
Feedback
signal
Power to
D1 input
terminal
Feedback
signal
Table 4
VB-72xx 2 way valves
Forta M400A / M800A Base Floating Configuration
Program Switch Position
Input / Output
VB-722x stem
up closed
OFF
ON
OFF
Retract
No Flow
Retract
No Flow
2 vdc
Extend
Full Flow
10 vdc
VB-722x stem
down open
OFF
ON
ON
Retract
No Flow
Extend
Full Flow
10 vdc
Retract
No Flow
2 vdc
VB-722x stem
up closed
ON
ON
ON
Extend
Full Flow
Retract
No Flow
10 vdc
Extend
Full Flow
2 vdc
VB-722x stem
down open
ON
ON
OFF
Extend
Full Flow
Extend
Full Flow
2 vdc
Retract
No Flow
10 vdc
VB-721x stem
up open
ON
ON
ON
Extend
No Flow
Retract
Full Flow
10 vdc
Extend
No Flow
2 vdc
VB-721x stem
down closed
ON
ON
OFF
Extend
No Flow
Extend
No Flow
2 vdc
Retract
Full Flow
10 vdc
VB-721x stem
up open
OFF
ON
OFF
10 vdc
Retract
Full Flow
2 vdc
Retract
Full Flow
Retract
Full Flow
2 vdc
Extend
No Flow
DA = Full open, full flow, 10vdc output / Full closed, no flow, 2vdc output
RA = Full open, full flow, 2vdc output / Full closed, no flow 10vdc output
Programming Note:
The above switch positions are the base programming configurations, in the base
configurations all other switches should be
switched off
. Once the base programming configuration has
been set up you may wish to add additional program features and functions that are listed below.
10 vdc
VB-721x stem
down closed
OFF
ON
ON
Retract
Full Flow
Extend
No Flow
Switch 1
CLOSE
OPEN
Switch 2
CLOSE
OPEN
% of Valve Travel
0
10
20
30
40
50
60
70
80
90
100
Table 3
Auxiliary Switches
2 - SPDT
Closed
Open
Closed
Open
Closed
Open
Closed
Open
KC1 - K1
X
X
X
X
KC1 - K2
X
X
X
X
KC2 - K3
X
X
X
X
KC2 - K4
X
X
X
X
Proportional Control
Action
Low Signal Input
High Signal Input
Optional Auxiliary Switch Function (S2)
Example A
Example B
Example C
Example D
Proportional Control
Program Switch 1off
Program Switch 1on
Program Switch 1off
Program Switch 1on
Power Up
Power Up
Power Up
Power Up
Retracted
Extended
Retracted
Extended
Program Switches 1 off, 7 off
Program Switches 1 on, 7 on
Program Switches 1 off, 7 on
Program Switches 1 on, 7 off
Retracts
Retracts
Extends
Extends
Note: This table shows the auxiliary switch action based on the dip switch 1 and 7 settings. You should program the dip switches on the actuator
based on the application requirements, once programmed review this chart to determine the action of the auxiliary switches and wire the switches
accordingly. IF YOU CHANGE EITHER DIP SWITCH 1 or 7 TO GET A DIFFERENT CONTACT CLOSURE YOU WILL CHANGE THE
EXTEND/RETEACT MOVEMENT OF THE ACTUATOR.
Note: With power to the actuator off, Auxiliary Switches are made KC1 to K1 and KC2 to K3. Upon power up switches will
make as shown above after auto start up calibration.
Extends
Extends
Retracts
Retracts
With the actuator powered and being controlled by the input signal the optional auxiliary switches only transfer contacts as follows,
driving from full retract to full extend the auxiliary contacts transfer when the actuator is about 95% of full extend travel. When the
actuator drives from full extend to full retract the contacts will transfer when the actuator is about 95% of full retract travel.