Globe Valve Actuators General Instructions

DIM119E

12 Mar 2008

TECHNICAL  DATA,  M400A  /  M800A

TAC Forta M400A / M800A

Forta M400A / M800A series Non-Spring Return linear actuators
are design to mount directly onto globe valves with linkage kits
ordered separately, M400A requires AV-811 linkage kit for
mounting to VB-7xxx valves and the M800A requires AV-811
linkage kit for mounting to VB-7xxx or AV-812 for mounting to
VB-9313-0-5-xx valves. 

Applications include chilled or hot

water and steam. Field selectable input signals include
reverse and direct acting, Floating or Proportional 0-10, 2-
10 vdc or 4-20 ma with 500 ohm resistor (supplied) plus
proportional sequencing input signal ranges.

FEATURES
- Floating configuration controlled by a SPDT floating

controllers

- Proportional configuration 0-10, 2-10 vdc or 4-20 ma

with the addition of a 500 ohm resistor included
Direct/Reverse action switch selectable

- 90 lbf (400N) linear force
- 180 lbf (800N) linear force
- 24 Vac powered
- Die-cast housing with plenum rated plastic cover for

NEMA 2 (IP54) applications

- Manual override to allow positioning of valve
- Electronic valve sequencing and Electronic flow curve

(equal percentage or Linear) selection.

- Torque overload protection throughout stroke
- Easy “One Touch” input signal/stroke calibration

APPLICABLE LITERATURE

-

Forta/VB-7xxx Selection Guide, F-27490

-

Forta/VB-8xxx, VB-9xxx Selection Guide, F-27491

-

AV-811 Linkage VB-7xxx, F

-27442

-

AV-812

Linkage VB-8xxx, 

VB-9xxx, F

-27443

-

AV-800 Series Linkage Adapters for Competitors

  Valves, F-27470

Stroke

>3/8" to 2" (9-52mm)

Stroke Timing

Floating 60 or 300 sec selectable
Proportional  15 sec @1/2" stroke

Feedback AO

2-10 vdc

Power Supply Type

Half Wave

Motor Type

Brushless  DC

Enclosure

NEMA 2 (IP 54) with both conduit
connectors used. NEMA 1 IP40 with
one connector used.

Sound Power Level

max 32 dba

Ambient Temperature
Storage

-13 °F-+149 °F (-25

- +65 

°C

) ambient

Operational

122 °F (50 °C) For Chilled water
applications
113 °F (45°C) ambient at 281 °F
(138°C) Fluid temperature
107 °F (42 °C

)

ambient at 300 °F

(149 °C) Fluid temperature
100 °F (38 °C) ambient at 340 °F
(171

°

C) Fluid temperature

90°F (32°C) ambient at 366 °F
(186 °C) Fluid temperature

Min.  Operating  Temp.

14 °F (-10 °C)

Ambient Humidity

15 to 95 % RH non condensing

Materials
  Housing

Die-Cast Aluminum

  Cover

UL94 plenum rated plastic

Weight

3.96 lb (1.8kg)

Dimensions

Figure 1

Model

Power

Running VA

Transformer

Size VA

Floating

Control

Proportional Control

Feedback

Force lbf

2-SPDT Aux 

Switch

M400A

No

M400A-S2

24vac 4a res

M800A

No

M800A-S2

24vac 4a res

2-10vdc

* 4-20mA with 500 ohm resistor

Model Chart

90 (400 N)

180 (800 N)

24vac ±10%

50-60Hz

6

15

30

50

Yes

0-10vdc, 2-10vdc or 

4-20mA*

Agency  Listings

UL873, cULus, C-tick, CE

Содержание Forta M400A

Страница 1: ...throughout stroke Easy One Touch input signal stroke calibration APPLICABLE LITERATURE Forta VB 7xxx Selection Guide F 27490 Forta VB 8xxx VB 9xxx Selection Guide F 27491 AV 811 Linkage VB 7xxx F 27442 AV 812 Linkage VB 8xxx VB 9xxx F 27443 AV 800 Series Linkage Adapters for Competitors Valves F 27470 Stroke 3 8 to 2 9 52mm Stroke Timing Floating 60 or 300 sec selectable Proportional 15 sec 1 2 st...

Страница 2: ...h manual override lowered MAN For normal operating the handle must be raised AUTO Position feedback M400A M800A actuators are equipped with a 2 10 vdc position feedback FUNCTION DIMENSIONS The actuator may be mounted horizontally vertically and in any position in between but not upside down see figure 3 Forta M400A M800A actuators mount directly on two and three way VB 7xxx globe valves using the ...

Страница 3: ...led with 3 conductors with very long lengths floating control where control signal reference is connected to G the motor current of the actuator will cause varying voltage loss in the cable and thus in the reference level Forta which has a highly sensitive control signal input will detect the varying signal and follow it which makes it difficult for the actuator to find a stable position Cable Len...

Страница 4: ...DIM119E 4 10 F 27506 1 WIRING EXAMPLES Figure 6 ...

Страница 5: ...5 10 DIM119E F 27506 1 Figure 7 ...

Страница 6: ...If SW5 is ON the 5 10 6 10v is selected Note switch 5 is only active if switch 2 is OFF and switch 3 is ON 6 If switch 2 is ON SW6 controls run time SW 6 OFF equals 60 sec ON equals 300 sec run time 7 Direction of movement NORM INV Changes the proportional or floating input signal to direct or reverse action similar to switch 1 8 Linearization SW 8 OFF normal SW8 ON Linear electronic control The m...

Страница 7: ...put RA Full open full flow 2vdc output Full closed no flow 10vdc output VB 721x stem down closed OFF OFF ON Retract Full Flow Extend No Flow 10 vdc No Flow 2 vdc Full Flow Valve Type Valve position at low signal input Switch 1 Switch 2 Switch 7 Power up Position Low end of signal input range Feedback signal action port B Table 2 VB 73x3 3 way valves Forta M400A M800A Base Proportional Configuratio...

Страница 8: ...tem down closed OFF ON ON Retract Full Flow Extend No Flow Switch 1 CLOSE OPEN Switch 2 CLOSE OPEN of Valve Travel 0 10 20 30 40 50 60 70 80 90 100 Table 3 Auxiliary Switches 2 SPDT Closed Open Closed Open Closed Open Closed Open KC1 K1 X X X X KC1 K2 X X X X KC2 K3 X X X X KC2 K4 X X X X Proportional Control Action Low Signal Input High Signal Input Optional Auxiliary Switch Function S2 Example A...

Страница 9: ...e the base programming configuration has been set up you may wish to add additional programming features and functions that are listed below Switch 1 CLOSE OPEN Switch 2 CLOSE OPEN of Valve Travel 0 10 20 30 40 50 60 70 80 90 100 Table 6 Auxiliary Switches 2 SPDT Closed Open Closed Open Closed Open Closed Open KC1 K1 X X X X KC1 K2 X X X X KC2 K3 X X X X KC2 K4 X X X X Floating Control contact mad...

Страница 10: ... class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in residential installations This equipment generates uses and can rediate radio frequency energy and may cause harmful interference if not installed and used in acordance with the instructions Even when instructions are followed there is no guarantee...