Page 37
English
Technical data
VLH S
1004
1104
1204
Power supply
V/ph/Hz
400 (±10%) / 3 / 50
Number of circuits
2
2
2
Capacity steps
%
25-50-75-100
23-50-73-100
25-50-75-100
Refrigerant
Type / GWP
R410A / 2.088
Charge 1/2
(1)
kg
30,5/30,5
34/34
37,5/37,5
tCO
2
eq
63,7/63,7
71,0/71,0
78,3/78,3
Compressor
Type
Scroll
Number
4
4
4
Start-up type
Direct
N°of loading stages
0/100
0/100
0/100
Evaporator
Type
Plate
Number
1
1
1
Water flow rate
l/s
11,2
12,4
13,5
Pressure drop
kPa
24,2
29,5
35,2
Water volume
l
25,2
25,2
25,2
Condenser
Type
Coil
Hydraulic connections
Type
Threaded Gas Male
Inlet diameter
inch
3”
3”
3”
Outlet diameter
inch
3”
3”
3”
Weights
Shipping weight
kg
2140
2230
2240
Operating weight
kg
2165
2255
2265
Additional Weights
HSE* versions
kg
40
40
40
Desuperheater versions
kg
30
30
30
With one pump
kg
90
95
95
With two pumps
kg
205
215
215
With pump and tank 500 lt
kg
350
350
350
With pumps and tank 500 lt
kg
400
400
400
Copper Fins
kg
700
880
880
Dimensions
Length
mm
4300
4300
4300
Width
mm
1100
1100
1100
Height
mm
2300
2300
2300
(1) The refrigerant value are indicative values for standard units. The actual data are indicated on the unit label.
(*) High Efficiency Units (HSE) with inverter fans.