Page 28
7.6 Air heat exchanger
Coils are made of copper pipes in staggered rows,
mechanically expanded inside an aluminium finned
pack.
7.7 Fans Control
Fans are of directly coupling propeller type, provided
with aluminium blade with wing profile.
Each fan is provided with galvanised steel accident-
prevention guard.
Finally, motors are completely closed, protection class
IP54, protection thermostat immersed in windings.
Components:
1) Compressor Tandem Scroll Type
2) Air cooled condenser
3) Filter Drier
4) Electronic expansion valve
5) Globe valve
6) Check valve
7) Liquid receiver
8) Four-way valve
9) Suction accumulator
10) Sight glass
11) Heat exchanger (dual type)
12) Desuperheathers (optional)
Safety /control devices:
A - High Pressure switch (42 bar)
AT - High Pressure transducer
BT - Low Pressure transducer
C - Water differential pressure switch (105 bar)
D - Air temperature sensor
E - Outlet water temperature sensor
F - Inlet water temperature sensor
G - PED pressure relief valve (46 bar)
H - Defrost temperature sensor
S - 5/16” Shrader connenction (service only)
Pipe connection with Shrader Valve
General Description
VLH refrigeration diagram