background image

 

 

_____________________________________________________________________________________________________ 

Topvex TR03-06 

 

 Operation and Maintenance instructions 

 

205353

 

 

Systemair AB

 

6

 
Changing parameters 

In some menus there are parameters that can be set. This will be indicated by the LED 



flashing. To 

change a parameter, first press the OK button, the LED 



changes to a steady light. A cursor will appear 

at the first settable value. If you wish to change the value, do so by pressing the UP/DOWN buttons. In 
numbers containing several digits you can move between the digits using the LEFT/RIGHT-buttons.  
When the desired value is displayed press OK. Settings outside the intervals is not registered, preset 
values counts. If there are further settable values displayed the cursor will automatically move to the next 
one. To pass a value without changing it, press RIGHT.  
To abort a change and return to the initial setting, press and hold the C-button until the cursor disappears. 

 
 
 

Navigating the menus 

The start display (the display normally shown) is at the root of the menu tree.  

 

Pressing DOWN 

 will move you through the menu choices, in this the lowest level. UP 

 will move you 

back through the choices.  

 

To enter a higher menu level, use UP or DOWN to place the display marker opposite the menu you wish to 
access and press RIGHT 

.  

If you have sufficient log on privileges the display will change to the menu you have chosen. 

 

At each level there may be several new menus through which you may move using the UP/DOWN buttons. 
Sometimes there are further sub menus linked to a menu or menu item. This is indicated by an arrow 
symbol at the right-hand edge of the display. To choose one, use RIGHT 

 again. To back down to a 

lower menu level, use LEFT 

.  

 

 
Alarms 

Alarm button (pos.1 in fig. 2) opens the alarm queue. Press this button and active and non-acknowledged 
alarms will be displayed in the menu window. The LED for alarms (pos.2 in fig. 2) is blinking if there are 
non-acknowledged alarms and steady if the alarms are still active but have been acknowledged. If there 
are multiple alarms use UP/DOWN buttons to move between them. An alarm can be acknowledged or 
blocked by using OK and UP/DOWN buttons. To abort and go back to start menu select Cancel and press 
LEFT button. 
 

Alarms –Overview 

Alarm fan motor 

DI1  Thermal contact in the fan motor tripped. Reset in Control panel. 

Overheat. DI2 

Thermal contact in the electric heater tripped (auto. reset: 60°C, manual reset: 
110°C). Manual reset is done by pressing the red button, marked RESET, on top of 
the connection box (pos.9 in fig. 1). 

Alarm VVX 

DI4  Malfunction on the rotating heat exchanger. Check the rotor transmission belt. 

Fire alarm 

DI5  External fire alarm contact tripped. Reset in Control panel. 

Filter to be changed 

Set time has expired. Reset in Control panel. 

Alarm frostprotect 

Outlet water below 8°C (temp. not changeable). Hot water heater. Reset in Control 
panel. 

Sensor error inlet 

Supply air sensor interruption. 

Sensor error exhaust 

 

Extract air sensor interruption. 

Sensor error outtemp. 

 

Outdoor air sensor interruption. 

Alarm output all alarms  DO5 Gives a signal (24V AC) whenever there is an A or B-alarm. 

Internal backup battery 
error  

Shows “Internal battery error” in the display 

 

Содержание Topvex TR03

Страница 1: ...Corrigo ver no 1 2 1 00 Topvex TR 03 TR04 TR06 Compact Air Handling Unit Operation and Maintenance instructions GB GB...

Страница 2: ...temair AB 2 Left model Right model Fig 1 Description 1 Connection Supply air 2 Connection Extract air 3 Connection Exhaust air 4 Connection Outside air 5 Supply air filter Topvex TR 04 6 Supply air fi...

Страница 3: ...ructions 205353 Systemair AB 3 Fig 2 Description Description 1 Alarm button 7 Connection block 2 Alarm LED 7a Yellow cable 3 Write enable LED 7b Orange cable 4 OK button 7c Red cable 5 Clearing button...

Страница 4: ...rning the design installation start up and operation which shall be obeyed to ensure the proper fail free operation of the unit The key to proper and safe operating of the unit is to read this manual...

Страница 5: ...ure is lower than the actual room temperature the actual room temperature is higher than the set room temperature limit The fans are stopped at the Stop Cooling Hour or if the following conditions are...

Страница 6: ...buttons Sometimes there are further sub menus linked to a menu or menu item This is indicated by an arrow symbol at the right hand edge of the display To choose one use RIGHT again To back down to a l...

Страница 7: ...or Manual shut off Service Login with 1111 to service level Log s out after 5 minutes of inactivity with main supply on Time Date Set the present time date and weekday Set the units ON time for each w...

Страница 8: ...ol Recycling to Active or Not Active Preset is Not Active Function Starts the heat exchanger to recycling the cold extract air temperature when the extract temperature is 3K lower than the Outdoor air...

Страница 9: ...r or Push button closes Only when the unit is running in Off mode DI4 Alarm VVX Stop the fans and close the dampers accessories when the alarm is activated DI5 Is only shown when the Fire function is...

Страница 10: ...possible to set the output signal within a range from 0 to10V AO3 Control signal 0 10V to the supply and extract fan Show and Set the digital outputs output 24V AC DO1 Damper motor on off Opens the d...

Страница 11: ...K button at the same time as the main voltage is switched on Change codeword Set a new code for Service level 4 Display unit type E DSP preset 5 Modbus Comm Not Active or Active Preset is Not Active M...

Страница 12: ...l to clean the exchanger regularly to maintain high efficiency The heat exchanger can easily be taken out of the unit Wash in hot soapy water or use pressure air Do not use detergent containing ammoni...

Страница 13: ...Exhaust air damper if used opens C Change of filters required D Cleaning of diffusers louvers required E Cleaning of fans exchanger block required F Is roof unit air intake clogged G Duct system Check...

Страница 14: ...te 5 Product code specification Commissioning It is possible to manually regulate the set airflow with 2 potentiometers situated in the electrical compartment fig 7 This enables the fan motors to be r...

Страница 15: ...el size Series no Filter replaces interval set Present time and date set Week scheduler settings Preset On time is Period 1 07 00 16 00 Monday Sunday Medium fan speed Period 2 00 00 00 00 Monday Sunda...

Страница 16: ...t 12 0 C C Max supply set point 30 0 C C Air flow Fan speed Low 35 of max Fan speed Fan speed Medium 75 of max Fan speed Fan speed Maximum 100 of max Fan speed Extended Forced running Running time 240...

Страница 17: ...he rights at any time without prior notice make changes and improvements to the contents of this manual Systemair AB Industriv gen 3 739 30 Skinnskatteberg Phone 46 222 440 00 Fax 46 222 440 99 www sy...

Отзывы: