Topvex TR03-06
Operation and Maintenance instructions
205353
Systemair AB
16
Function
Preset value
Set value
Temperature.
Control function Temp.
Supply
Supply outdoor
Extract
Supply Supply outdoor
Extract
Control Temp.
18,0 °C
°C
Outdoor compensating
Outdoor temp.
-20,0 °C
Compensation: 20,0 °C
°C
+15,0 °C
Compensation: 0,0 °C
°C
Min. supply set point
12,0 °C
°C
Max. supply set point
30,0 °C
°C
Air flow
Fan speed Low
35% of max. Fan speed
%
Fan speed Medium
75% of max. Fan speed
%
Fan speed Maximum
100% of max. Fan speed
%
Extended/Forced
running
Running time
240 Minutes *)
Minutes *)
Filter alarm
Replaces interval
6 Months
Months
Cooling
Status
Not active
Active
Cool Recycling
Status
Not active
Active
Free Cooling
Status
Not active
Active
Outdoor temp activation:
22°C
°C
Outdoor temp night:
High: 15°C Low: 5°C
High:
°C Low:
°C
Room temp min:
18°C
°C
Fire function
Status
Not active
Active
Running mode at activated
fire alarm
Unit shut off
High fan speed
*) Set the minutes to 0 when using an external Timer.