background image

 

 

_____________________________________________________________________________________________________ 

Topvex TR03-06 

 

 Operation and Maintenance instructions 

 

205353

 

 

Systemair AB

 

12

Warning 

In order to avoid electrical shock, fire or other damage that might occur in connection with faulty use and 
operation of the unit, it is important to consider the following: 

 

  The system must be installed according to the mounting instructions. 

  Insulate mains supply before service or cleaning of the heat recovery unit. 

  Tumble dryer must not be connected directly to the ventilation system. 

  Make sure the filter is mounted in its place before running the system. 

  Maintenance must be performed according to the instructions. 

 

Maintenance 

Maintenance of the Topvex should normally be carried out 3 – 4 times a year. Apart from general cleaning 
the following should be observed: 

 

1.  Changing Supply/Extract air filter (indicates as “filter to be changed” in the control panel, 1-2 
times per year or as necessary) (fig.3) 

The bag filter cannot be cleaned and must be changed as necessary. New filters can be ordered from 
Systemair. Operation time between filter changes must be re-set after filter change, see page 8 

Filter 

alarm

. To change the alarm activating time, see page 8 

Filter alarm

Initial pressure drop is approx. 70 Pa and the final pressure is approx. 220 Pa. 

NB: For size Topvex TR 04 an extra space of 150mm to the wall from the side of the unit is needed 
to remove the supply air filter when the door is opened. 

 

2.  Checking the heat exchanger (Once a year), (fig.4) 

After long times use dust may build up in the exchanger and block the airflow. It is vital to clean the 
exchanger regularly to maintain high efficiency. The heat exchanger can easily be taken out of the unit. 
Wash in hot soapy water or use pressure air. Do not use detergent containing ammonia. 

 

Note!

  Make sure that the rotor motor is not exposed to moisture. 

 

3.  Checking the fans (once a year), (fig.5) 

Even if the required maintenance, such as changing of filters is carried out, dust and grease may slowly 
build up inside the fan (pos.12 and 13 in fig. 1). This will reduce the efficiency. 
The fans may be cleaned with a cloth or a soft brush. Do not use water. White spirit can be used to remove 
obstinate settlements. Allow drying properly before remounting. 

 

4.  Cleaning extract louvers and inlet diffusers (when necessary) 

The system supplies outdoor air to the building and extracts the used indoor air via the duct system and 
diffusers/louvers.  Diffusers and louvers are mounted in ceilings/walls in bedroom, living room, wet rooms, 
WC etc. Remove diffusers and louvers and wash in hot soapy water as required. (Diffusers/louvers must be 
put back with their original settings and positions in order not to unbalance the system). 

 

5.  Checking the outdoor air intake 

Leaves and pollution could plug up the air intake grille and reduce the capacity. Check the air intake grille 
at least twice a year, and clean if necessary. 

 

6.  Checking the duct system (when necessary) 

Dust and grease settlements may build up in the duct system even if filters are changed regularly. This will 
reduce the efficiency of the installation. The duct runs should therefore be cleaned/changed when 
necessary. Steel ducts can be cleaned by pulling a brush soaked in hot soapy water, through the duct via 
diffuser/louver openings or special inspection hatches in the duct system (if fitted). 

 

NOTE!

 In addition roof cowl must be checked once a year and cleaned as necessary. 

 

Содержание Topvex TR03

Страница 1: ...Corrigo ver no 1 2 1 00 Topvex TR 03 TR04 TR06 Compact Air Handling Unit Operation and Maintenance instructions GB GB...

Страница 2: ...temair AB 2 Left model Right model Fig 1 Description 1 Connection Supply air 2 Connection Extract air 3 Connection Exhaust air 4 Connection Outside air 5 Supply air filter Topvex TR 04 6 Supply air fi...

Страница 3: ...ructions 205353 Systemair AB 3 Fig 2 Description Description 1 Alarm button 7 Connection block 2 Alarm LED 7a Yellow cable 3 Write enable LED 7b Orange cable 4 OK button 7c Red cable 5 Clearing button...

Страница 4: ...rning the design installation start up and operation which shall be obeyed to ensure the proper fail free operation of the unit The key to proper and safe operating of the unit is to read this manual...

Страница 5: ...ure is lower than the actual room temperature the actual room temperature is higher than the set room temperature limit The fans are stopped at the Stop Cooling Hour or if the following conditions are...

Страница 6: ...buttons Sometimes there are further sub menus linked to a menu or menu item This is indicated by an arrow symbol at the right hand edge of the display To choose one use RIGHT again To back down to a l...

Страница 7: ...or Manual shut off Service Login with 1111 to service level Log s out after 5 minutes of inactivity with main supply on Time Date Set the present time date and weekday Set the units ON time for each w...

Страница 8: ...ol Recycling to Active or Not Active Preset is Not Active Function Starts the heat exchanger to recycling the cold extract air temperature when the extract temperature is 3K lower than the Outdoor air...

Страница 9: ...r or Push button closes Only when the unit is running in Off mode DI4 Alarm VVX Stop the fans and close the dampers accessories when the alarm is activated DI5 Is only shown when the Fire function is...

Страница 10: ...possible to set the output signal within a range from 0 to10V AO3 Control signal 0 10V to the supply and extract fan Show and Set the digital outputs output 24V AC DO1 Damper motor on off Opens the d...

Страница 11: ...K button at the same time as the main voltage is switched on Change codeword Set a new code for Service level 4 Display unit type E DSP preset 5 Modbus Comm Not Active or Active Preset is Not Active M...

Страница 12: ...l to clean the exchanger regularly to maintain high efficiency The heat exchanger can easily be taken out of the unit Wash in hot soapy water or use pressure air Do not use detergent containing ammoni...

Страница 13: ...Exhaust air damper if used opens C Change of filters required D Cleaning of diffusers louvers required E Cleaning of fans exchanger block required F Is roof unit air intake clogged G Duct system Check...

Страница 14: ...te 5 Product code specification Commissioning It is possible to manually regulate the set airflow with 2 potentiometers situated in the electrical compartment fig 7 This enables the fan motors to be r...

Страница 15: ...el size Series no Filter replaces interval set Present time and date set Week scheduler settings Preset On time is Period 1 07 00 16 00 Monday Sunday Medium fan speed Period 2 00 00 00 00 Monday Sunda...

Страница 16: ...t 12 0 C C Max supply set point 30 0 C C Air flow Fan speed Low 35 of max Fan speed Fan speed Medium 75 of max Fan speed Fan speed Maximum 100 of max Fan speed Extended Forced running Running time 240...

Страница 17: ...he rights at any time without prior notice make changes and improvements to the contents of this manual Systemair AB Industriv gen 3 739 30 Skinnskatteberg Phone 46 222 440 00 Fax 46 222 440 99 www sy...

Отзывы: