Installation |

13

1. Make sure that all of the cable joints and the two transparent pressure measuring tubes to the extract air fan are cor-

rect assembled between the unit parts.

2. Wire the prepared control cable to the Topvex TR electrical cabinet (in the supply air part), use the prepared grom-

mets. Connect the wires to the terminal blocks in the electrical cabinet according to labelling on the wires and the
electrical wiring diagram. See also the chapter Internal electrical connections.

3. Connect the unit electrically to the mains (400V 3N~, 50Hz) through the all pole circuit breaker, safety switch (acces-

sory). The wiring is led through the top of the unit casing directly to the Topvex SoftCooler electrical connection box.
Dimension the wires and fuses according to chapter 4.2.2.

4. Do the electrical connections for the Topvex TR air handling unit according to the installation instructions that follows

that unit.

6.8.1

External/Internal connections

See also the enclosed wiring diagram.

Mains power supply (and in some cases By-pass damper) is the only external connection that should be connected to
the Topvex SoftCooler.

Table 1 External connections

Terminal
block

Description

Remark

PE

Ground

400V 3N~, 50Hz,
supplied via safety
switch

N

N

Earthed neutral (supply voltage)

L1

L1

Phase (supply voltage)

L2

L2

Phase (supply voltage)

L3

L3

Phase (supply voltage)

28

G

By-pass damper”DBEH” exhaust air (option)

24V AC

29

GO

By-pass damper ”DBEH” exhaust air (option)

Neutral (24 VAC)

The already prepared operating cable in Topvex SoftCooler is to be drawn to the electrical cabinet in the supply part of
the Topvex air handling unit and connected to the terminal blocks with the same numbers as the cable markings.

Table 2 Internal connections

Terminal
block

Description

Remark

G

G

24V AC

4

DI ref

Referens

10

DO ref

Referens

12

DO

Exhaust air damper. A signal from control unit is lead via the
relay R2 to terminal 28 for controlling of the by-pass
damper (accessory).

24V AC, 0.5A

14

DO

A signal from control unit for starting

Step controller 1

step 1

indicates a cooling demand. The signal controls relay

R2 that is then closing the by-pass damper (accessory).

24V AC, 0.5A

15

DO

A signal from control unit for starting

Step controller 1

step 2

indicates a cooling demand. The signal controls relay

R1 that is then starting the compressor.

24V AC, 0.5A

74

DI

Alarm indication cooling

Malfunction cooling (SEQ-

C)

.

NO

90

AO ref

Reference

94

AO

Control signal from control unit for cooling. Controls the
frequency converter "FC".

0-10V DC

208767 | A006

Содержание Topvex TR 09 Series

Страница 1: ...Document in original language 208767 A006 Topvex SoftCooler TR09 15 Access control system Installation instructions GB...

Страница 2: ...208767 A006...

Страница 3: ...ing the unit 7 6 4 Dividing the Topvex TR air handling unit 9 6 5 Duct connections 11 6 6 Condensation and Heat Insulation 11 6 7 Condensation drain 12 6 8 Electrical connection 12 7 Function Descript...

Страница 4: ......

Страница 5: ...er or lower limbs EN 60204 1 Safety of machinery Electrical equipment of machines Part 1 General requirements EN 60335 1 Household and similar electrical appliances Safety Part 1 General requirements...

Страница 6: ...ape well Duct connections duct ends should be covered during storage and installation Do not connect tumble dryers to the ventilation system 3 Refrigerant Control Reporting Topvex SoftCooler TR comes...

Страница 7: ...ig 1 Dimensions mm TR09 TR15 Drawn as left hand unit Model AA B C D E F G I J K L TR09 2630 1630 1120 810 895 104 129 129 105 210 700 TR12 2770 1740 1230 930 965 76 104 104 105 215 800 TR15 2820 1980...

Страница 8: ...9230 20 5 5 4 3 Components Fig 2 Connections and basic components in left hand connected units Position Description 1 Compressor 2 Condenser coil 3 Evaporator coil 4 Filter drier with sight glass 5 E...

Страница 9: ...7 8 Fig 3 Electrical cabinet Position Description 1 Terminal block mains supply 2 Circuit breaker MCB oil heaters 3 Relays 4 Terminal block internal external connections 5 Frequency converter with dis...

Страница 10: ...here how to install Topvex SoftCooler are meant for indoor installation Place the unit on a horizontal flat surface It s important that the unit is completely levelled before it is put into operation...

Страница 11: ...Installation without by pass left hand unit Position Description Supply air Exhaust air Outdoor air Extract air 1 VAV Pressure transmitters accessory 2 Damper and motor outdoor air accessory 3 Damper...

Страница 12: ...tion Description Supply air Exhaust air Outdoor air Extract air 1 Exhaust air By pass 2 VAV Pressure transmitters accessory 3 Damper and motor outdoor air accessory 4 Damper and motor exhaust air acce...

Страница 13: ...it casing directly to the elec trical connection box See enclosed wiring diagram and chapter 6 8 1 table 2 for more information Warning The units electrical connection to the mains power supply must b...

Страница 14: ...10 Installation A Fig 6 Illustration shows the left handed version of the unit 208767 A006...

Страница 15: ...ct connections on top of the unit Outdoor air Supply air Extract air and 2 Exhaust air Duct connections can be done on two different ways with or without a by pass function for the exhaust air For duc...

Страница 16: ...SoftCooler Use the included plastic connection pipe which is to be cut to the correct height H according to the below figure See the below table for the relation of hight H and maximum under pressure...

Страница 17: ...al block Description Remark PE Ground 400V 3N 50Hz supplied via safety switch N N Earthed neutral supply voltage L1 L1 Phase supply voltage L2 L2 Phase supply voltage L3 L3 Phase supply voltage 28 G B...

Страница 18: ...Fig 11 With by pass left hand unit Position Description EF Extract air fan SF Supply air fan SS Temp sensor supply air OS Temp sensor outdoor air ETS Temp sensor extract air UC Control unit RC Rotor...

Страница 19: ...ssor CPR are step less controlled between in the frequency converter FC set minimum and maximum frequency 7 4 Power limitation The frequency converter FC is continuously sensing the condensing pressur...

Страница 20: ...chapter 6 8 1 External Internal connections Internal operating cable connected see chapter 6 8 1 External Internal connections The two transparent pressure measuring tubes to the extract fan connected...

Страница 21: ...ply and extract fan via the Topvex air handling units safety switch Turn on the mains supply for the Topvex SoftCooler via the working switch make sure that the voltage is on the display in the freque...

Страница 22: ...the Topvex SoftCooler be closed for at least 5 minutes before reading Output frequency Param d001 Output current Param d002 Condenser pressure Param d004 Output frequency __________________Hz Output c...

Страница 23: ...208767 A006...

Страница 24: ...ler TR09 15Access control system Installation instructions 208767 en_GB 2020 01 27 A006 Systemair Sverige AB Industriv gen 3 SE 739 30 Skinnskatteberg Sweden Phone 46 222 440 00 Fax 46 222 440 99 www...

Отзывы: