Preset value
Set value
Temperature.
Control function Temp.
Supply
Supply outdoor
Exhaust
Supply
Supply outdoor
Exhaust
Control Temp.
18,0 °C
°C
Outdoor compensating
Outdoor temp.
-20,0 °C
Compensation: 20,0 °C
°C
+15,0
°C
Compensation: 0,0 °C
°C
Min. supply set point
12,0 °C
°C
Max. supply set point
30,0 °C
°C
Air flow
Topvex 1000, 1500
Fanspeed Medium
180,0 V
V
Fanspeed Low
130,0 V
V
Topvex 2000
Fanspeed Medium
65 % of max. Fan speed
%
Extended running
Running time
240 Minutes *)
Minutes *)
Filter alarm
Replaces interval
6 Month
Month
Cooling
Status
Not active
Active
Cool Recycling
Status
Not active
Active
Fire function
Status
Not active
Active
Running mode at activated
fire alarm
Unit shut off
High fan speed
Frost protection
(supply air)
Status
Not active
Active
Alarm limit
10 °C
°C
*) Set the minutes to 0 when using an external Timer.