Operation
General
Topvex unit with Electrical heater have 3 minutes of re-cooling after that it has been turned off.
N.B.
If activating the fire alarm when the heater is on the fan stops immediate without re-cooling, this can
cause the overheating protection to trip. See page 3
Alarms –Overview
how to reset.
When changing a parameter in the control system it takes up to 1 minute for the change to be carried out.
Set the menu language
Press the OK button while switching on the mains supply.
Press the OK button. Choose language with the UP / DOWN buttons. Confirm the choice with the OK
button. Press the LEFT button to go back in the menus.
The language can also be change in the
Language
menu, see
Control unit, manual (page 7)
.
Control panel
How to operate
See
fig 2
.
The menus in the Corrigo E are organized in a horizontal tree structure. The UP / DOWN-buttons are used
to move between menus at the present menu level. The RIGHT / LEFT buttons are used to move between
menu levels. When changing parameters the UP / DOWN buttons are used to increase or decrease the
value of the parameter and the RIGHT / LEFT buttons to move between digits within the parameter.
The OK button is used to confirm the choice of a parameter setting.
The C button is used to abort an initiated parameter change and restore the original value.
The ALARM button is used to access the alarm list.
Changing parameters
In some menus there are parameters that can be set. This will be indicated by the LED
flashing. To
change a parameter, first press the OK button, the LED
changes to a steady light. A cursor will appear
at the first settable value. If you wish to change the value, do so by pressing the UP / DOWN buttons. In
numbers containing several digits you can move between the digits using the LEFT / RIGHT-buttons.
When the desired value is displayed press OK. Settings outside the intervals is not registered, preset
values counts. If there are further settable values displayed the cursor will automatically move to the next
one. To pass a value without changing it, press RIGHT.
To abort a change and return to the initial setting, press and hold the C-button until the cursor disappears.
Navigating the menus
The start display (the display normally shown) is at the root of the menu tree.
Pressing DOWN
▼
will move you through the menu choices, in this the lowest level. UP
▲
will move you
back through the choices.
To enter a higher menu level, use UP or DOWN to place the display marker opposite the menu you wish to
access and press RIGHT
►
.
If you have sufficient log on privileges the display will change to the menu you have chosen.
At each level there may be several new menus through which you may move using the UP / DOWN
buttons.
Sometimes there are further sub menus linked to a menu or menu item. This is indicated by an arrow
symbol at the right-hand edge of the display. To choose one, use RIGHT
►
again. To back down to a
lower menu level, use LEFT
◄
.