Safety Information

 

All fans are intended for transportation of air in air handling 
systems. They are meant to be used after building them into 
machines or duct systems or after contact protection grid 
has been installed. (SS-EN 294). No moving parts shall be 
accessible after installation. The fans are not to be used in 
hazardous environments or connected to flue ducts. The 
fans must not be installed outdoors, (with exception of roof 
fans). Safety accessories (i.e. motor protection, safety grille) 
may not be dismounted, short cut or disconnected. 
CAUTION Before servicing or maintenance, switch off 
power, (all-pole circuit breaker), and make sure the impeller 
has come a standstill. CAUTION The fans can have sharp 
edges and corners which may cause injuries. CAUTION Be 
careful when opening the fans service-hatches (swing-out), 
the fan and motor assembled on the hatch is relatively 
heavy. 

Transportation and Storage 

All fans are packaged at the factory to withstand normal 
transport handling. When handling the goods use suitable 
lifting equipment in order to avoid damage to fans and 
personnel. Do not lift the fans by the connecting cable, 
connection box, impeller or inlet cone. Avoid blows and 
shock loads. Store the fans in a dry place protected from 
weather and dirt until final installation. 

Installation 

Refer to Safety information above. Installation, electrical 
connection and commissioning are only to be carried out by 
authorised personnel and in accordance with requirements 
and demands. Electrical connection according to the wiring 
diagram in the terminal box, markings on terminal blocks or 
on cable. The terminal box is accessed by removing the top 
cover of the fan by 4 screws. CAUTION Do not use metal 
compression gland fittings with plastic terminal boxes. Use 
a dummy plug seal for the compression gland fitting as well.  
The fan must be installed so that vibrations are not 
transmitted to duct systems or frame of building. (Suitable 
accessories like fast clamps and diffusers are available). 
Make sure the assembly of the fan is firmly fixed and stable. 
The fan can be mounted in any direction unless stated 
otherwise. If the roof fan is installed so that it can be 
dismounted a revision switch has to be applied. The fan 
should then be connected with a cable suitable for outdoor 
connection (cable diameter 7-13mm). When mounting is 
made directly onto a circular duct the square mounting plate 
is removed. The fastening screws on the bottom are then 
srewed into the holes of the inlet part. 
The fans must be assembled so that service and 
maintenance can be performed easily and safely. Disturbing 
noise can be avoided by installing silencer (available 
accessory).  
 
For frequency regulation an all pole sinus filter must be 
mounted between motor and frequency controller (version 
all poles: phase to phase, phase to earth). Fans are meant 
for continuous use within the temperature range stated.  

Operation 

Before initial operation, check the following: 
- Electrical connection has been properly completed. 
- Protective conductor has been connected. 

- Safety devices in place (protection grid) 
- Leftover installation materials and foreign materials have 
been removed from the casing. 
 
When putting into operation, check the 
following: 
- Connection data corresponds to the specifications on the 
nameplate: Maximum v6%, -10%, according to IEC 
38. Rated current must not be exceeded with more than 5% 
at rated voltage. CAUTION When speed regulating by 
reducing the voltage the motor current may exceed the 
rated current at a lower voltage. In this case the motor 
windings are protected by the thermal contact. The 
minimum static fall of pressure must observed. 
- Smoothness of motor operation, (no abnormal noises). 

Maintenance, Service and Repair 

Before maintenance, service or repair make sure that: 
- Power supply is interrupted (all-pole circuit breaker). 
- Fan impeller has come to a complete standstill 
- Observe personnel safety regulations! 
 
The fan should be cleaned when necessary, at least 1/year 
to avoid imbalance and unnecessary damage to the 
bearings. A filter will prolong the time interval between each 
cleaning of the fan. (It is sometimes recommended to install 
a filter guard). The fan bearings are maintenance free and 
should only be replaced if damaged. Do not use a high-
pressure cleaner (steam jet) when cleaning the fan. Make 
sure the fan impeller's balance weights are not moved or 
the fan impeller distorted. Listen for abnormal operating 
noise. 
 

Resetting of the thermal trips 

Automatic thermal trips resets it selves after the motor has 
cooled. (TW) 
Manual thermal trips (SP1) are reset by disconnecting the 
mains for approx. 10-60min. 
 
Make sure the fan has not been blocked or that the motor 
protection has tripped. Contact the supplier if the motor 
does not start after controlling and/or resetting the motor 
protection. 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 