Smoke Vent System RZN 4402/04-K

installation

Safety system protects human life and material assets!

Once a year functional testing by a specialist company

authorized by the manufacturer.

Connection, mounting and functional testing by a

specialist company authorized by the manufacturer.

Green control diodes in the buttons must constantly lighten,

otherwise see "Informations for Starting".

Repair power failure at once. Emergency power supply for 72 hours.

Approval-
Number:
G 501002

Guarantee

You will get 

2 years 

guarantee for all D+H products from date of verified handing over of the

system up to maximal 3 years after date of delivery, when mounting and starting has been
carried out by a D+H authorized  

distributor

.

D+H guarantee is expired, with connection of D+H components with external systems or
with mixing of  D+H products with parts of other manufacturers.

W x H x D = 250 x 250 x 91

W x H x D = 400 x 300 x 120

Содержание RZN 4402-K

Страница 1: ...by the manufacturer Green control diodes in the buttons must constantly lighten otherwise see Informations for Starting Repair power failure at once Emergency power supply for 72 hours Approval Numbe...

Страница 2: ...y the latest maintenance instructions Following tests must be carried out in the course of maintenance Outside examination inspection of system components Measuring of insulation resistances Checking...

Страница 3: ...ation of German Insurer against damage of property VdS and the respective local authorities Recommended is that maintenance work should be carried out by authorized specialist companies only Only regu...

Страница 4: ...nts Retrofitable System Overview Drive group signal indicating board acoustical optical alarm devices signal contact 230V 50Hz Mains supply wind rain transmitter smoke vent button min 2 piece ventilat...

Страница 5: ...x 262 x 81mm Mounting of housing 1 joint rod door plaster cross for flush mounting cable cover cable bushing only surface mounting housing flush mounted wall hook optional flush mounted set UPS 44 K n...

Страница 6: ...of fire walls must not be inadmissibly influenced Sound insulation is impaired by flush mounting Final mounting 3 Mount and connect central pcb 4 Screw down cable cover 5 Unhinge door of the door fra...

Страница 7: ...n cover plate in control panel View motherboard RZN 4402 04 K fire recognition element thermo maximum signal fuse drive fuse external detector Dip switch mains conne ction LED failure group LED contro...

Страница 8: ...in the ceiling Size kind and arrangement of the opening is of decisive significance for an optimal effect of the smoke and heat vent system The important thing here is that an escape must not be hind...

Страница 9: ...H N surface 24 VDC circa 1 5m above upper edge firm flooring by customer 55mm flush socket Vent button 24 VDC e g LT 43 circa 1 2 above upper edge firm flooring at flush type by others 55mm flush sock...

Страница 10: ...e by thermal ascending force and by automatic fire recognition devices thermal detector smoke detector and they release either self acting or manual by smoke detectors at an early stage of a fire and...

Страница 11: ...pinched in control panel for transport Take it off there and connect according to plan Terminal resistors must remain at binder RM 1 2 when no fire detector or external control exists Fire detectors...

Страница 12: ...12 20 RZN 4402 04 K Rev 3 8 Parallel Connection of Smoke Vent Buttons RT 42...

Страница 13: ...re pinched in control panel for transport Take it off there and connect according to plan Terminal resistors must remain at binder RM 1 2 when no fire detector or external control exists Fire detector...

Страница 14: ...02 04 K line line control alarm close RM RT smoke vent button RT 43 H smoke vent button RT 43 N 10kW 10kW alarm alarm control control line line line line malfunction close close 2 2 7 8 7 3 3 1 1 6 6...

Страница 15: ...15 20 RZN 4402 04 K Rev 3 8 Parallel Connection of 2 x 2 Smoke Vent Buttons RT43 H N...

Страница 16: ...Magnetic clamp The resistor must not be used when line connections with 2 detector dependency are employed Connection of several fire detectors Connection of one fire detector terminal resistor line 1...

Страница 17: ...wires Mot a Mot b derive off in par allel monitoring will be looped through all cables up to group end Example 1 1 line Simple installation but unfavourable for voltage drop All drives on one line Exa...

Страница 18: ...be reset under special conditions only Performance check alarm reset and ventilation 10k resistance in smoke vent button 10k resistance in fire detector Stop module 2x47k in conduit box Connect mains...

Страница 19: ...ossible then If Dip switch 5 is on OFF the function power failure CLOSED will be ineffective see Dip switch 4 Dip switch 6 on ON Ventilation flap opens up to final position by single pressing on vent...

Страница 20: ...red display diode extinguishes in button and control panel Smoke vent must close Automatic fire detectors Release smoke detector individual by D H smoke detector tester as an alternative by cigarette...