Certain flexible hose threaded connectors are supplied with sealing paste. If this is not the case,
use Teflon tape to create a tight seal.
7.
Each unit must be equipped with isolation valves on the water inlet and outlet pipes. The return
isolation valve is used for both cutting off the water supply and balancing the installation’s water
flow. As it is used to establish the balance of the flows,
it must be equipped with a lockable
position end stop
. This end stop ensures that, after the valve is closed, it can only be re-opened
as far as the position required to maintain a balanced water flow.
8.
Use steel, copper or P.V.C. pipes for the condensates drainage pipe. Each unit is supplied with a
connector for condensates drainage.
9.
The condensates drainage line must comprise a siphon and run from the unit on a downward
slope of at least 2%. Generally, the siphon is connected directly to the unit’s condensates
drainage outlet. A length of plastic pipe can be used between the siphon and the condensates
drainage line.
A complete condensates drainage system with copper or P.V.C. pipe can also be used.
Screw-on connectors shall be fitted to facilitate drainage pipe removal if copper pipe is used for
the drainage pipe work.
10.
No point of the condensates drainage pipe work should be located above the level of one of
the units’ condensate drainage outlet connection.
11.
The circuits’ high points must be bled of air.
12.
Comply with current regulations in terms of dielectric isolation of the connectors and the pipe
work.
Coil at the unit blowing
(standard)
Coil at the return air intake
(on request)