Table 7.2
List of
ODU
error codes:
Error
Code
E
0
ODU
communication fault
X
F1
PTC error
E1
Three
-
phase power supply
phase protection
F3
Error in temperature sensor at T6B
plate heat e
x
changer outlet
E2
Communication error between
indoor and outdoor units
F
5
Error in temperature sensor at T6A
plate heat e
x
changer inlet
E
4
Error in condenser
temperature sensor (T3) or
ambient temperature sensor
(T
4
)
P
0
I
nverter compressor top temperature
protection
E
5
Voltage protection
P1
H
igh pressure protection
E
7
D
ischarge temperature sensor
fault
P2
Low pressure protection
E8
ODU
address error fault
X
P3
Compressor overcurrent protection
X
E9
D
rive mismatching fault
P
4
Protection against e
x
cessive
discharge temperature of compressor
EL
Reserved
P
5
H
igh temperature protection of
condenser
XH0
Communication error between
I
R3
4
1 and master chip
P9
D
C Fan Error
H
1
Communication chip and
master chip communication
fault
PF
Reserved
H
2
ODU
qty decrease fault
PL
Protection against e
x
cessive
temperature of the inverter module
H
3
ODU
qty increase fault
PP
Protection against e
x
cessively low
discharge superheat
Code
Error
Error
D
efinition and
D
escription
Error
D
efinition and
D
escription
38
Содержание SYS WSC 86
Страница 44: ...16117100001523 MD18U 003DW ...